CONTROL
SYSTEM
12-2
Service Manual – YBZ DCI 1-A.1 GB
12.1.2 Compressor
Frequency
Control
12.1.2.1 Compressor frequency setting
The Load calculation is done by each indoor unit controller, based on a PI control scheme which
is based on the difference between SPT and RAT.
ODU controller will decide the compressor frequency based on the total load from all the indoors.
Compressor frequency will be limited within following ranges:
Minimum Frequency (MinFreq)
Maximum Frequency (MaxFreq) *
Mode
YBZ214 YBZ318 YBZ430 YBZ214 YBZ318 YBZ430
Cooling 15
15
15
110
110
110
Heating 15
15
15
110
110
110
* Maximum frequency is also decided by different indoor combinations.
12.1.2.2 Frequency Changes Control
Frequency change rate is 1 Hz/sec.
12.1.2.3 Compressor Starting Control
12.1.2.4 Minimum On and Off Time
Prohibit turning ON the compressor for 3 minutes after turning it off. (Except during deicing
protection)
Prohibit turning OFF the compressor for 7 minutes after turning it on (except protections required
immediate compressor stop)
Summary of Contents for YBZ214
Page 16: ...OUTLINE DIMENSION 4 2 Service Manual YBZ DCI 1 A 1 GB 4 2 Indoor HZD018 HYD018...
Page 17: ...OUTLINE DIMENSION Service Manual YBZ DCI 1 A 1 GB 4 3 4 3 Outdoor YBZ214...
Page 18: ...OUTLINE DIMENSION 4 4 Service Manual YBZ DCI 1 A 1 GB 4 4 Outdoor YBZ318 YBZ430...
Page 35: ...WIRING DIAGRAM 9 2 Service Manual YBZ DCI 1 A 1 GB 9 3 YAZ214...
Page 36: ...WIRING DIAGRAM Service Manual YBZ DCI 1 A 1 GB 9 3 9 4 YAZ318...
Page 37: ...WIRING DIAGRAM 9 4 Service Manual YBZ DCI 1 A 1 GB 9 5 YAZ430...
Page 38: ...WIRING DIAGRAM Service Manual YBZ DCI 1 A 1 GB 9 5 9 6 Wiring connection between IDU and ODU...
Page 39: ...WIRING DIAGRAM Service Manual YBZ DCI 1 A 1 GB 10 1 10 REFRIGERATION DIAGRAMS...
Page 40: ...TUBING CONNECTIONS Service Manual YBZ DCI 1 A 1 GB 11 1 11 TUBING CONNECTIONS...
Page 76: ...EXPLODED VIEW SPARE PART LIST Service Manual YBZ DCI 1 A 1 GB 15 15 APPENDIX...