13-2
TROUBLESHOOTING
SM HAFRPM 2-A.1 GB
No. SYMPTOM PROBABLE
CAUSE
CORRECTIVE
ACTION
11
One of the protections is
activated and compressor
is stopped with no apparent
reason.
Control problem or
refrigeration system problem.
Perform diagnostics to detect
active protection, and take action
accordingly.
12
Compressor motor is noisy
and no suction is present.
Wrong phase order to
compressor.
Check compressor phase order.
13
Water leakage from indoor
unit.
Indoor unit drainage tube is
blocked.
Check and open drainage tube.
14
Freezing of outdoor unit in
HEAT Mode and outdoor unit
base is blocked with ice.
Connect base heater.
15
Unit operates with wrong fan
speeds or wrong frequency.
Wrong jumper settings.
Perform diagnostics to obtain unit
model or if operating by EEPROM
parameters.
16
Filter LED comes ON after 512
hours of operation
Clogged air-filter
Replace air-filter. Press the RESET
button.