12-28
CONTROL SYSTEM
SM HAFRPM 2-A.1 GB
12.13 SPT adjustment in Sleep Mode
1. In cool, auto cool or dry modes, the SPT adjustment is positive (from 0 to +3
o
c).
2. In heat or auto heat modes, the SPT adjustment is negative (from 0 to -3
o
c).
3. In other modes, there is no SPT adjustment.
4. The SPT adjustment is cancelled when the Sleep mode is cancelled.
SPT
Time [Hr]
4
8
5
3
2
6
Start
Sleep
7
RT
SPT-1
SPT-2
SPT-3
SPT+2
SPT+1
SPT+3
1
7 Hours Sleep operation
for Normal Sleep Mode
Unit is turned to SB
after Sleep
Cool, Dry modes
Heat mode
Note: If Off-timer is active, the unit may go to SB before or after 7 hours of sleep
operation.