12-18
CONTROL SYSTEM
SM HAFRPM 2-A.1 GB
3. When Dry is changed from ON to OFF or vice versa, the limits mentioned in (1) & (2)
are ignored. The COMP operation is only controlled by the 3 min Min OFF time and
1 min Min ON time.
4. In Dry Mode, IFAN is LOW when COMP is ON, and is OFF when COMP is OFF.
5. HEs are always OFF in Dry Mode.