10
BORING THE WALL FOR PASSAGE OF THE HYDRAULIC PIPES
Mark the position of the hole at each side of the assembly panel as shown on the diagram, next drill these holes
under an angle of 5° downwards.
The hole downwards allows to avoid condensates or rain to enter inside.
Place a standard plastic tube Ø 70 mm in the hole.
One can also run the hydraulic connections in a chute again the wall. To do this, enlarge the pre-recessed part of the
plastic bottom in order to the able to position the inlet and outlet hoses as well as the condensate drainage line.
ASSEMBLY AND REMOVAL OF THE APPLIANCE FROM THE ASSEMBLY PANEL
See to it that the hydraulic links (insulated with 9mm thickness in the case of elastomer line, and 13mm in the case
of copper line), the electric cables and the drainpipe are insulated by means of an appropriate tube ("Armaflex"
type, 5 mm thickness); they should be covered all together with a plastic, non-adhesive strip, and passed through
the hole of the wall.
Hang the indoor unit on the 2 hooks located close to the upper edge of the assembly panel. Press the lower part
of the indoor unit against the assembly panel until the latches interlock in the slots and lock the indoor unit on the
assembly panel. Check that the unit is well locked on the panel by pulling the unit.
In order to remove the unit from the mounting plate, raise and pull outwar.
Make sure that the hooks are locked.
5°
A
B
1
2
1
Indoor unit
2
Fixing latch
3
Upper hooks
4
Lower hooks
1
Assembly panel
2
Lower hooks
3
Lifting
4
Pulling
Pre-recessed part to be enlarged for
passage in the chute
A
Outside dimension
B
Inside dimension
1
Drill press Ø 70 mm
2
Wall
CONNECTION OF HYDRAULIC LINKS
When making the connection
be sure to connect the entry water supply to the link with a colored stain on
the nut.
The appliance schould be cut off by putting stop valves on the water supply.
Summary of Contents for XLM OG 18
Page 2: ......
Page 10: ...8 CURVE OF PRESSURE DROP 0 5 10 15 20 25 30 35 0 100 200 300 400 500 600 700 800 l h PDC kPa...
Page 16: ...14 ELECTRICAL CONNECTIONS...
Page 24: ...22...
Page 25: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO...
Page 26: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO II...
Page 28: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO IV...
Page 29: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO V OPTIONS OPTIONS OPTIONEN OPCIONES OPZIONI 18 50...