Wellea Monobloc
61
4.9
HF Troubleshooting
Digital display output
4.9.1
Description
4.9.2
Refrigerant system EEPROM error.
Wellea
Mono stops running.
Error code is displayed on refrigerant system main PCB and user interface.
Possible causes
4.9.3
Refrigerant system main PCB EEPROM is not connected properly.
Refrigerant system main PCB damaged.
Procedure
4.9.4
HF
Refrigerant system EEPROM
1
is not
connected properly
Yes
Ensure the EEPROM is connected
properly
No
Replace refrigerant system main PCB
Notes:
1.
Refrigerant system main PCB EEPROM is designated IC23 on the refrigerant system main PCBs (labeled 29 in Figure 4-2.2 in Part 4, 2.3 “Main PCBs for
Refrigerant System, Inverter Modules and Filter Boards”), designed IC13 on the refrigerant system main PCBs (labeled 19 in Figure 4-2.4 in Part 4, 2.2
“Main PCBs for Refrigerant System, Inverter Modules and Filter Boards”), designed IC23 on the refrigerant system main PCBs (labeled 26 in Figure 4-2.6 in
Part 4, 2.2 “Main PCBs for Refrigerant System, Inverter Modules and Filter Boards”).