Wellea Monobloc
22
5.8
Module Temperature Protection Control
This control protects the module from abnormally high temperatures only for
MHC-V5(7,9)W/D2N8.
Figure 3-6.3: Module Temperature Protection Control
When the module temperature rises at or above 72°C the system displays C7 protection and the unit stops running. When
the module temperature drops at or below 68°C, the compressor enters re-start control.
Module temperature ≥ 72°C
Module temperature ≤ 68°C
Normal operation
Module Temperature Protection, error code C7 is displayed