ELB:Electricity Leakage Breaker.
AH : Assistant heater.
Electrical characteristics
Specifications for field supplied ELB and wire
Unit
Power supply
Fan motor
Model
Hz
Volts
MCA
MFA
KW
FLA
SXV007
50
220~240
0.37
16
0.06
0.18
SXV009
0.37
16
0.06
0.18
SXV012
0.37
16
0.06
0.18
SXV015
0.68
16
0.13
0.41
SXV018
0.68
16
0.13
0.41
SXV021
0.68
16
0.13
0.41
SXV024
0.68
16
0.13
0.41
Model
Power supply wiring
Remote controller wiring
communication wiring
Field ELB
Wire and Size
Wire
Size
SXV007
16A
Must comply
with maximum
current and local
codes(0.75mm
2
)
Twisted-pair wires
1.0mm
2
SXV009
SXV012
SXV015
SXV018
SXV021
SXV024
NOTE:
�
All field supplied parts and materials and
electrics works must conform to local codes.
�
Use copper wire only.
�
All wiring must be performed by an authorized
electrician.
�
Every indoor unit must have a sub circle
breaker and the whole system must have a
main circle breaker.
�
Be sure to ground the air conditioner.
�
The appliance shall be installed in accordance
with national wiring regulations ,and shall be
provided to ensure all-pole disconnection from
the supply mains, and distance between the
poles shall be more than 3 mm .
MCA : Min. Circuit Amps (A)
MFA : Max. Fuse Amps(A)
KW : Fan Motor Rated output(KW)
FLA : Full Load Amps(A)
CHECK ITEMS
NOTE:
For the piping and wiring methods,leakage test,vacuum process and installation setting
through HMI, please refter to “Outdoor unit Installation Manual”.
Power supply
Main R/C
Bus Wiring
BEFORE POWER ON
■ Is there any gas leakage at flare nut connections?
■ Has the heat insulation been carried out at flare nut connection?
■ Is the connecting cable being fixed to terminal board firmly?
■ Is the connecting cable being clamped firmly?
■ Is the drainage ok? (Refer to "Drainage test section)
■ Is the earth wire connection properly done?
■ Is the indoor unit properly hooked to the installation plate?
■ Is the power supply voltage complied with rated value?
AFTER POWER ON
■ Is there any abnormal sound?
■ Is the cooling operation normal?
■ Is the thermostat operation normal?
■ Is the remote control's LCD operation normal?