Page 27
Row s of series installation
L
≤
H
L
≤
1/2H
L
A
25 cm / 9.8” or more
1/2H < L
≤
H
30 cm / 11.8” or more
L
>
H
Can not be installed
The relations betw een H, A and L
are as follow s.
Outdoor Unit Dimentsion (mm)
Mounting Dimentsion (mm)
W
H
D
A
B
681
434
285
460
292
700
550
275
450
260
300
333
363
420
555
554
702
810
770
800
845
946
487
514
540
673
298
340
350
403
W
H
A
B
D
Outdoor unit C
L
H
300 cm / 118” or more
A
60 cm / 23.6”
or more
150 cm / 59”
or more
25 cm / 9.8”
or more
25 cm / 9.8”
or more
When connecting refrigerant piping,
do not
let substances or gases other than the specified
refrigerant enter the unit. The presence of other
gases or substances will lower the unit’s capacity,
and can cause abnormally high pressure in the
refrigeration cycle. This can cause explosion
and injury.
Refrigerant Piping
Connection
Oil traps
CAUTION
If oil flows back into the outdoor unit’s
compressor, this might cause liquid
compression or deterioration of oil return.
Oil traps in the rising gas piping can prevent
this.
An oil trap should be installed every 6m(20ft) of
vertical suction line riser (
<
36000Btu/h unit).
An oil trap should be installed every 10m(32.8ft)
of vertical suction line riser (≥36000Btu/h unit).
10m/32.8ft
(≥36000Btu/h unit)
6m/20ft
(
<
36000Btu/h unit)
10m/32.8ft
(≥36000Btu/h unit)
6m/20ft
(
<
36000Btu/h unit)
Indoor unit/
Outdoor unit
Indoor unit/
Outdoor unit
Refrigerant
piping
Connection