Outdoor Unit
Installation
Page 26
B
A
D
The mounting dimensions vary among
different outdoor units.
The fixing bolt head diameter should be
more than 12mm.
Outdoor Unit Dimentsion (mm)
Mounting Dimentsion (mm)
W
H
D
A
B
952
1333
415
634
404
900
1170
350
590
378
Outdoor Unit Dimentsion (mm)
Mounting Dimentsion (mm)
W
H
D
A1
A1
D
B
A2
A2
B
1128
1555
426
668
494
206
W
H
Step 2: Install drain joint (Heat pump
unit only)
Before bolting the outdoor unit in place, you
must install the drain joint at the bottom of
the unit. Note that there are two different
types of drain joints depending on the type
of outdoor unit.
If the drain joint comes with a rubber seal
(see
Fig. A
), do the following:
1.
Fit the rubber seal on the end of the drain joint
that will connect to the outdoor unit.
2.
Insert the drain joint into the hole in the base
pan of the unit.
3.
Rotate the drain joint 90° until it clicks in place
facing the front of the unit.
4.
Connect a drain hose extension (not included)
to the drain joint to redirect water from the
unit during heating mode.
If the drain joint doesn’t come with a rubber
seal
(see
Fig. B
), do the following:
1.
Insert the drain joint into the hole in the base
pan of the unit. The drain joint will click in
place.
2.
Connect a drain hose extension (not included)
to the drain joint to redirect water from the
unit during heating mode.
Seal
Drain joint
(A)
(B)
Base pan hole of
outdoor unit
Seal
IN COLD CLIMATES
In cold climates, make sure that the drain
hose is as vertical as possible to ensure
swift water drainage. If water drains too
slowly, it can freeze in the hose and flood
the unit.
Step 3: Anchor outdoor unit
Outdoor unit A
Outdoor unit B