![Airwell ONG3-18 Service Manual Download Page 78](http://html1.mh-extra.com/html/airwell/ong3-18/ong3-18_service-manual_2879884078.webp)
12-28
CONTROL SYSTEM
Revision 0 Service Manual - EDS
d.
STEP 4 : AUTO LED WALK TEST.
x
All the LEDS will turn OFF.
x
All the LEDS will turn ON for 1 second one by one in the following
sequence:
STAND-BY
OPERATE
TIMER
FILTER
COOL
HEAT.
x
In PRX all the LEDS will turn ON for 1 second one by one in the following
sequence : 18 °c
20 °c 22 °c 24 °c 26 °c 28 °c 30 °c
High IFAN
Auto IFAN
Med IFAN
Low IFAN
STAND-BY
TIMER
FILTER
COOL HEAT.
e.
STEP 5: AUTO REALY WALK TEST:
x
All relays will energize one by one in the following sequence:
COMPRESSOR
OUTDOOR FAN R. V.
HEATER 1 HEATER 2
INDOOR WATER PUMP
SWING or OUTDOOR WATER PUMP
INDOOR FAN: LOW MID HIGH.
x
When the relay walk test is completed, the next test will start
automatically.
f.
STEP 6: FREQUENCY TESTING:
x
If the frequency measuring process fails the COOL LED will turn ON.
In order to move to the next step, press ON/OFF button on the remote
control.
g.
STEP 7: INPUT TEST.
x
The test purpose is to check the analog real time indicators (thermistors,
LEVEL and clock) according to the table below.
LED Indicator
Condition for LED to be ON
r
o
t
s
i
m
r
e
h
t
m
o
o
R
D
E
L
Y
B
T
S
z
25°c
r
o
t
s
i
m
r
e
h
t
li
o
c
r
o
o
d
n
I
D
E
L
R
E
P
O
z
25°c
TIMER LED
Outdoor coil thermistor
z
25°c
FILTER LED
Clock
3
&
2
L
E
V
E
L
D
E
L
L
O
O
C
4
L
E
V
E
L
D
E
L
T
A
E
H
h.
STEP 8: TIMING RESET TEST (WATCH DOG).
x
The test purpose is to verify that the CPU rise time after power failure
is between 1 to 3 sec, test results are indicated on the LEDS : STAND-
BY,OPER, TIMER and FILTER turning ON one by one.
x
The results of the test are coded as follows:
Pass condition:
1 sec - STAND-BY and OPER are turned ON
2 sec - STAND-BY, OPER and TIMER are turned ON
Summary of Contents for ONG3-18
Page 39: ...8 2 WIRING DIAGRAMS Revision 0 Service Manual EDS 8 2 Indoor Unit EDS100 EDS120 ...
Page 40: ...8 3 WIRING DIAGRAMS Revision 0 Service Manual EDS 8 3 Outdoor unit GCN9 GCN12 ...
Page 41: ...8 4 WIRING DIAGRAMS Revision 0 Service Manual EDS 8 4 Outdoor unit GC10 34 GC45 ...
Page 42: ...8 5 WIRING DIAGRAMS Revision 0 Service Manual EDS 8 5 Outdoor unit ONG3 17 ...
Page 43: ...8 6 WIRING DIAGRAMS Revision 0 Service Manual EDS 8 6 Outdoor unit GCZ22 ...
Page 113: ... 2 MODES OF OPERATION FUNCTIONS AND FEATURES ...