![Airwell ONG3-18 Service Manual Download Page 12](http://html1.mh-extra.com/html/airwell/ong3-18/ong3-18_service-manual_2879884012.webp)
Model Indoor Unit
EDS 120
Model Outdoor Unit
GC 45
Installation Method of Pipe
Flared
Characteristics
Units
Cooling
Heating
Capacity (4)
Btu/hr
43670
54590
kW
12.80
16.00
Power input (4)
kW
4.56
4.98
EER (Cooling) or COP(Heating) (4)
W/W
2.81
3.21
Energy efficiency class
C
C
Power supply
V
380-415
Ph
3
Hz
50
Rated current
A
9.2
8.7
Power factor
0.85
0.85
Prated (IDU)
W
308
Prated (IDU+ODU)
W
5800
Starting current
A
65.8
Circuit breaker rating
A
15
IN
D
OOR
Fan type & quantity
DirectX2
Fan speeds
H/M/L
RPM
1257/1056/1021
Air flow (1)
H/M/L
m3/hr
2000/1692/1452
External static pressure
Min
Pa
0
Sound power level (2)
H/M/L
dB(A)
64/61/59
Sound pressure level(3)
H/M/L
dB(A)
51/48/46
Moisture removal
l/hr
3.7
Condenstate drain tube I.D
mm
19.05
Dimensions
WxHxD
mm
1785X611X250
N
et
Weight
kg
50
Package dimensions
WxHxD
mm
1935X628X280
Packaged weight
kg
55
Units per pallet
units
5
Stacking height
units
5
OU
T
D
OOR
Refrigerant control
Capillary Tube
Compressor type,model
Srcoll JT160BCBY1L
Fan type & quantity
Propeller (direct) * 2
Fan speeds
H
RPM
780
Air flow
H
m3/hr
4680
Sound power level
H
dB(A)
64
Sound pressure level(3)
H
dB(A)
56
Dimensions
WxHxD
mm
950X1270X340
N
et
Weight
kg
120
Package dimensions
WxHxD
mm
1108X1286X473
Packaged weight
kg
139
Units per pallet
Units
1
Stacking height
units
1
Refrigerant type
R22
Standard charge
kg(7.5m)
3.97
Additional charge
7.5m
˘
Lin
İ
50m: +35g/m
Connections
between units
Liquid line
In.(mm)
3/8"(9.53)
Suction line
In.(mm)
3/4"(19.05)
Max.tubing length
m.
Max. 50m
Max.height difference
m.
Max. 10m
Operation control type
Remote control
Heating elements (Option)
kW
Others
(1)Airflow in ducted units;at nominal external static pressure 30Pa.
(2)Sound power in ducted units is measured at air discharge.
(3)Sound pressure level measured at 1-meter distance from unit.
(4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
(5)The declared value's tolerance is in accordance with EN14511.
(5)The declared value's tolerance is in accordance with EN14511.
PRODUCT DATA SHEET
2-6
Revision 0
Service Manual - EDS
Summary of Contents for ONG3-18
Page 39: ...8 2 WIRING DIAGRAMS Revision 0 Service Manual EDS 8 2 Indoor Unit EDS100 EDS120 ...
Page 40: ...8 3 WIRING DIAGRAMS Revision 0 Service Manual EDS 8 3 Outdoor unit GCN9 GCN12 ...
Page 41: ...8 4 WIRING DIAGRAMS Revision 0 Service Manual EDS 8 4 Outdoor unit GC10 34 GC45 ...
Page 42: ...8 5 WIRING DIAGRAMS Revision 0 Service Manual EDS 8 5 Outdoor unit ONG3 17 ...
Page 43: ...8 6 WIRING DIAGRAMS Revision 0 Service Manual EDS 8 6 Outdoor unit GCZ22 ...
Page 113: ... 2 MODES OF OPERATION FUNCTIONS AND FEATURES ...