12-3
CONTROL SYSTEM
Revision 0
Service Manual - EDS
12.3
General functions
12.3.1
COMP operation
For each Mode including POWER OFF & SB, a Min time delay of 3 min
before COMP restarting, excluding DEICING Mode
The Min operation time of COMP under different operating conditions is
Operation Mode
Min operation time of
COMP
.
n
i
m
3
s
e
d
o
M
o
t
u
A
r
o
l
o
o
C
,
t
a
e
H
Fan, Dry
2YHUÀR
w, Protection modes, or mode change
ignored
12.3.2
IFAN operation
x
Min time interval between IFAN speed change in AUTOFAN Mode, is 30 sec.
x
Min time interval between IFAN speed change in H/M/L Mode is 1 sec.
x
IFAN speed in Heat/Cool Autofan Mode is determined according to the following table:
'
d
e
e
p
S
N
A
F
I
T
'
T
t
H
G
I
H
2
2
t '
T
t
D
E
M
1
1
t '
W
O
L
T
where
in Heat Mode:
'
T = SPT-RT
in Cool Mode:
'
T = RT-SPT
Note:
x
In Heat Mode, the rules in section 4.0.3 have the higher priority.
x
The table above can be represent by a hysteresis curve which
will minimize the switching of the IFAN relay and will minimize the
change in IFAN speed:
T [
o
c]
L
M
H
IFAN speed
3
2
1
12.3.3
OFAN operation
x
Min time interval between OFAN ON/OFF state change is 30 sec.
x
In general, OFAN starts together with COMP.
12.3.4
HE operation
x
Minimum Heaters ON or OFF time is 30 sec.
x
Heaters can be activated only if IFAN is on.
Summary of Contents for ONG3-18
Page 39: ...8 2 WIRING DIAGRAMS Revision 0 Service Manual EDS 8 2 Indoor Unit EDS100 EDS120 ...
Page 40: ...8 3 WIRING DIAGRAMS Revision 0 Service Manual EDS 8 3 Outdoor unit GCN9 GCN12 ...
Page 41: ...8 4 WIRING DIAGRAMS Revision 0 Service Manual EDS 8 4 Outdoor unit GC10 34 GC45 ...
Page 42: ...8 5 WIRING DIAGRAMS Revision 0 Service Manual EDS 8 5 Outdoor unit ONG3 17 ...
Page 43: ...8 6 WIRING DIAGRAMS Revision 0 Service Manual EDS 8 6 Outdoor unit GCZ22 ...
Page 113: ... 2 MODES OF OPERATION FUNCTIONS AND FEATURES ...