2-6
PRODUCT DATA SHEET
SM YBD018 1-A.1 GB
2.6
SLS 50 DCI / YBD018
(1)
Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
(2)
Airflow without external static pressure.
(3)
Sound power in ducted units is measured at air discharge.
(4)
Sound pressure level measured at 1-meter distance from unit.
Units
Btu/hr
kW
kW
W/W
V
Ph
Hz
A
W
W
A
A
H/M/L
RPM
H/M/L
m3/hr
Min
Pa
H/M/L
dB(A)
H/M/L
dB(A)
l/hr
mm
WxHxD
mm
kg
WxHxD
mm
kg
units
units
H
RPM
H
m3/hr
H
dB(A)
H
dB(A)
WxHxD
mm
kg
WxHxD
mm
kg
Units
units
kg(7.5m)
In.(mm)
In.(mm)
m.
m.
kW
Model Indoor Unit
SLS 50 DCI
Model Outdoor Unit
YBD 018
Installation Method of Pipe
Ducted
Characteristics
Cooling
Heating
Capacity (4)
17060(5120-19790)
19110(4440-23200)
5.0(1.5-5.8)
5.6(1.3-6.8)
Power input (4)
1.51(0.4-2.0)
1.55(0.34-2.0)
EER (Cooling) or COP(Heating) (4)
3.31
3.61
Energy efficiency class
A
A
Power supply
220-240
1
50/60
Rated current
6.8
6.9
Power factor
0.97
0.97
Prated (IDU)
Prated (IDU+ODU)
2400
Starting current
10.5
Circuit breaker rating
20
INDOOR
Fan type & quantity
Centrifugal x 2
Fan speeds
1100/980/860
Air flow (1)
710/600/540
External static pressure
0
Sound power level (2)
54/51/48
Sound pressure level(3)
35/32/29
Moisture removal
1.5
Condenstate drain tube I.D
19
Dimensions
750x630x200
Net Weight
30
Package dimensions
885x695x226
Packaged weight
24
Units per pallet
14 units per pallet
Stacking height
7 levels
OUTDOOR
Refrigerant control
EEV
Compressor type,model
Rotary,Panasonic 5RS132ZAD21
Fan type & quantity
Propeller(direct) x 1
Fan speeds
910
Air flow
2160
Sound power level
63
Sound pressure level(3)
53
Dimensions
795x610x290
Net Weight
38
Package dimensions
945x655x395
Packaged weight
41
Units per pallet
9 units per pallet
Stacking height
3 levels
Refrigerant type
R410A
S
WDQGDUG
charg
H
1.26
Additional charge
No need
Connections
between units
Liquid line
1/4"(6.35)
Suction line
1/2"(12.7)
Max.tubing length
Max. 20
Max.height difference
Max. 10
Operation control type
Remote control
Heating elements (Option)
Others