10 appliances can be connected to a single RCL remote control module.
The maximum distance between the RCL and the first unit is 30 metres.
The maximum distance between the RCL and the furthest unit is 100 metres.
Use screened twisted pair telephone
wire with a section of between 0.12
and 0.5 mm² for wiring.
100 m maximum between the
RCL and the last appliance.
30 m maximum
between the
RCL and the first
appliance.
10 HRW
MAXIMUM
µBMS SUPERVISION MODULE
The µBMS supervision module / micro supervisor can be connected to a maximum of 100 appliances and enables
independent control of up to 15 independent zones. Each zone has its own ON/OFF programming as well as
customised set temperature settings.
The programming (ON/OFF, set temperature, Mode, etc.) of the zone 0, enables the µBMS supervision module
to send the command to all the units at the same time.
²
The maximum distance between the RCL and the first unit is 30 metres.
²
The maximum distance between the RCL and the furthest unit is 100 metres.
²
The maximum distance between the µBMS supervision module and the first unit is 30 metres.
²
The maximum distance maximum between the µBMS supervision module and the furthest unit is
1,000 metres.
CENTRALE DE
1 2 3 4
SUPERVISION
µBMS
ZONE N°1
ZONE N°2
RS 485
12V
GND
30m MAXI
1000m MAXI
RCL
4
3
2
1
1 2
4
3
RS 485
12V GND
CARTE
STORM 2
A- B+
A B
HRW 1
1 2
4
3
RS 485
12V GND
CARTE
STORM 2
A- B+
HRW 2
1 2
4
3
RS 485
12V GND
CARTE
STORM 2
A- B+
HRW 3
100m MAXI
100 HRW
MAXIMUM
1000 m maximum between the
µBMS and the last appliance
Note
: When the µBMS supervision is used, all the units must have an address (Refer to "Addressing Procedure").
The units in the same area have the same address.
Use screened twisted pair
telephone wire with a
section of between 0.12
and 0.5 mm² for wiring.
The use of the µBMS recall command is not compatible with the modbus communication.
The same terminals and addressing DIPs are used in both connection cases.