APPLIANCE CONFIGURATION
FACTORY CONFIGURATION
Type
J1
J2
Description
RC
OFF
OFF
Cooling and thermodynamic Heating
SH
OFF
ON
Thermodynamic C thermodynamic
Heating or electric heating depending on
appliance return water temperature
ST
ON
OFF
Cooling only
RH
ON
ON
Cool + heat by electric heat
CLIENT SETTINGS
Jumper
Configuration
J3
OFF
the fan is controlled via the compressor and the ICT
sensor in Heating mode.
ON
the fan operates continuously in Heating mode,
except in OFF mode.
J4
OFF
No anti-stratification mode
ON
Anti-stratification mode active. Fan cycling
J5
OFF
ambient temperature is measured at the RCL.
ON
ambient temperature is measured with the Return
sensor (RT) located on the appliance.
Jumper
Configuration
J6
OFF
Normal mode
ON
Forced mode dry contact (
remote ON/OFF)