ADDRESSING PROCEDURE
Each unit address is selected via the DIP switch SW2 (with 8 selectors).
Individual micro-switch values :
DIP switch
1
2
3
4
5
6
7
8
ON
1
2
4
8
16 32 64 128
OFF
0
0
0
0
0
0
0
0
Each machine connected to a µBMS central supervision unit or a
MODBUS system must receive an address according to the procedure
below.
BEFORE STARTING THE ADDRESSING PROCEDURE YOU MUST MAKE SURE
THAT THE UNIT IS SWITCHED OFF AND THAT THERE IS NO POSSIBILITY OF IT
STARTING UP UNEXPECTEDLY.
Addressing examples :
DIP switch
1
2
3
4
5
6
7
8
ON
OFF
Value
1
0
0
0
0
0
0
0
Adress = 1 :
DIP switch
1
2
3
4
5
6
7
8
ON
OFF
Value
0
2
0
8
16
0
0
0
Adress = 26 :