13-10
TROUBLESHOOTING
SM FLODCI 2-A.4 GB
13.2
Troubleshooting for GC 24 / 30
WARNING!!!
When Power Up – the whole outdoor unit controller, including the wiring, is under
HIGH VOLTAGE!!!
Never open the Outdoor unit before turning off the Power!!!
When turned off, the system is still charged (400V)!!!
It takes about 1 Min. to discharge the system.
Touching the controller before discharging may cause an electrical shock!!!
13.2.1
General System Failures and Corrective Actions
No
Symptom
Probable Cause
Corrective Action
1
Indoor unit power supply indicator
(Red LED) does not light up.
No power supply
Check power supply. If OK,
check display and display
wiring. if OK, replace
controller
2
Indoor unit does not respond to
remote control message
Remote control
message not reached
the indoor unit
Check remote control
batteries, if OK, check
display and display wiring,
if OK, replace display
PCB. If still not OK replace
controller
3
Indoor unit responds to remote
control message but Operate
indicator (Green LED) does not
light up
Problem with display
PCB
Replace display PCB.
If still not OK replace
controller
4
Indoor fan does not start (louvers
are opened and Green LED is
ON)
Unit in heat mode and
coil is still not warm
Change to cool mode
Outdoor unit is in
opposite mode
Change operation mode
Problem with controller
or capacitor
Change to high speed
and Check power supply
to motor is higher than
130VAC (for triack
controlled motor) or higher
than 220VAC for fixed
speed motors, if OK replace
capacitor, if not OK replace
controller
5
Indoor fan works when unit is
OFF, and indoor fan speed is
not changed by remote control
command.
Controller problem
Replace controller
6
Water leakage from indoor unit
Indoor unit drainage
tube is blocked
Check and open drainage
tube