13-16
TROUBLESHOOTING
SM FLODCI 2-A.4 GB
13.2.4
Fault Code for Indoor unit
Pressing Mode button for long will activate diagnostic mode by the acknowledgment of 3 short beeps
and lighting of COOL and HEAT LED’s.
Entering diagnostics in STBY mode allows only viewing of status (fault-display).
In diagnostic mode, system problems / information will be indicated by blinking of Heat & Cool
LED’s.
The coding method will be as follows:
Heat led will blink 5 times in 5 seconds, and then will be shut off for the next 5 seconds. Cool Led will
blink during the same 5 seconds according to the following table:
No
Fault Name
5
4
3
2
1
1
RT-1 is disconnected
0
0
0
0
1
2
RT-1 is shorted
0
0
0
1
0
3
RT-2 is disconnected
0
0
0
1
1
4
RT-2 is shorted
0
0
1
0
0
…
Reserved
0
0
1
0
1
7
Communication mismatch
0
0
1
1
1
8
No Communication
0
1
0
0
0
9
No Encoder
0
1
0
0
1
10
Reserved
0
1
0
1
0
11
Outdoor Unit Fault
0
1
0
1
1
…
Reserved
17
Defrost protection
1
0
0
0
1
18
Deicing Protection
1
0
0
1
0
19
Outdoor Unit Protection
1
0
0
1
1
20
Indoor Coil HP Protection
1
0
1
0
0
21
Overflow Protection
1
0
1
0
1
…
Reserved
24
EEPROM Not Updated
1
1
0
0
0
25
Bad EEPROM
1
1
0
0
1
26
Bad Communication
1
1
0
1
0
27
Using EEPROM data
1
1
0
1
1
28
Model A
1
1
1
0
0
29
Model B
1
1
1
0
1
30
Model C
1
1
1
1
0
31
Model D
1
1
1
1
1
1 - ON,
0 - OFF
Only one code is shown. Order of priority is lower to the higher number. Diagnostics is continuously
ON as long power is on.
CONTENTS