ELECTRONIC FUNCTION
JMF Series 35 Version - 1
9.4.2.4 Low evaporator coil temperature T2 protection
TE6
T2
On
Off
TE5
When the evaporator coil temp.T2 keeps lower than TE5 for 5 minutes, the compressor and
outdoor fan will shut off. When T2 is higher than TE6, the compressor and outdoor fan will restart
up.
9.4.2.5 High condenser temperature T3 protection(only for ELSI-JMF024-N11)
When T3
≥
TE10, the compressor will stop and restart until T3<TE11.
During the protection, the outdoor fan keeps working.