SPECIFICATION
JMF Series 11 Version - 1
Model Indoor Unit
ELSI-JMF024-N11
Model Outdoor Unit
ELAU-JMF024-H11
Installation Method of Pipe
Flared
Characteristics
Units
Cooling
Heating
Average
Capacity
(1)
kW
6.154
6.740
EER /COP
(2)
W/W
2.81
3.21
Energy efficiency class
C
C
Power supply
V/Ph/Hz
220-240V/Single/50Hz
Circuit breaker rating
A
25
INDOOR
Fan type & quantity
Cross flow fan x1
Fan speeds
H/M/L
RPM
1180/1100/900
1180/1100/950
Air flow
(3)
H/M/L
m3/hr
1150/1050/900
1150/1050/930
External static pressure
Min-Max
Pa
0
Sound power level
(4)
H/M/L
dB(A)
47/44/40
Sound pressure level
(5)
H/M/L
dB(A)
57
Moisture removal
l/hr
3
Condensate drain tube I.D
mm
16
Dimensions
WxHxD
mm
1045 x315x235
Weight
kg
12
Package dimensions
LxWxH
mm
1135x395x315
Packaged weight
kg
15.5
Stacking height
units
8
OUTDOO
R
Refrigerant control
Capillary
Compressor type, model
ROTARY
Fan type & quantity
Axial x 1
Fan speeds
H/L
RPM
870
Air flow
H/L
m3/hr
2500
Sound power level
(4)
H/L
dB(A)
62
Sound pressure level
(5)
H/L
dB(A)
72
Dimensions
WxHxD
mm
820 x595x330
Weight
kg
44
Package dimensions
LxWxH
mm
940x415x645
Packaged weight
kg
46
Stacking height
Units
3
Refrigerant type
R410A
Refrigerant charge (standard connecting tubing length)
kg(5m)
1.6
Additional charge per 1 meter
gr / 1m
40
Connections between units
Liquid line
In.(mm)
3/8"(9.52)
Suction line
In.(mm)
5/8"(15.9)
Max.tubing length
m.
25
Max.height difference
m.
10
Operation control type
Remote control
Heating elements
kW
Others