4
4
- 94
3-WAY FLOW LOGIC Unit Specifications
6. Concealed Duct Type
Indoor unit (B)
MODEL No.
S
T-NDLP 9
S
ource
220 - 230 - 240 V /
s
ingle-pha
s
e / 50 Hz
Controller P.C.B. A
ss
’y
CR-TRP50A-B (Microprocessor)
Fan (Number…diameter)
mm
Centrifugal (1 … ø 190)
Fan motor
Model…Nominal output
W
SFG4X-51C3P … 50 W
Source
220 - 230 - 240 V / single-phase / 50 Hz
No. of pole…r.p.m. (230 V, High)
rpm
4P …
8
34
Coil resistance
Ω
BRN – WHT :
76.
88
ORG – YEL
:
14.42
(Ambient temperature 20
°
C)
WHT – VLT
:
12.66
–
:
26.76
VLT – ORG :
21.01
BLK – PNK
:
25.17
Safety device
Operating temperature
Open
°
C
130
±
5
(115
±
5)
Close
°
C
Run capacitor
VAC,
μ
F
450 VAC, 1.5
μ
F
Electronic expan
s
ion valve
Coil
UKV-U031E
Coil resistance (at 20
°
C)
Ω
ORG – GRY : 46
YEL – GRY : 46
RED – GRY : 46
BLK – GRY : 46
Valve body
UKV-1
8
D31
Heat exchanger
Coil
Aluminum plate fin / Copper tube
Rows…fin pitch
mm
2…1.5
Face area
m
2
0.113
Drain pump
ADP-1413
Rated
V, W
AC230 V, 50 Hz, 12 W
Total head & capacity
500 mm, 400 cc/min
YEL
BLK