
4
4
- 77
3-WAY FLOW LOGIC Unit Specifications
4
5. Ceilin
g
-Mounted Type
Unit
s
pecification
s
(E)
MODEL No.
Indoor Unit
S
T-NPFL 48
POWER
S
OURCE
220 - 230 - 240 V / single-phase / 50 Hz
PERFORMANCE
Cooling
Heating
Capacity
kW
14
16.0
BTU / h
47,800
54,600
Air circulation (Hi / Me / Lo)
m
3
/h
1800 / 1560 / 1320
Moisture removal (High)
Liters/h
5.6
–
ELECTRICAL RATING
S
Voltage rating
240
220
230
240
Available voltage range
198 – 264
198 – 264
Running amperes
A
V
V
0.69
0.63
0.60
0.69
0.63
0.62
Power input
W
85
86
88
84
85
86
Power factor
%
56
59
61
55
59
58
Max. starting amperes
A
3
3
3
3
3
3
FEATURE
S
Controls
Microprocessor
Timer
ON / OFF Timer (Max. 72 hr)
Fan speeds
3 and Automatic control
Air filter
Washable, easy access, long life (2,500 hr)
Refrigerant control
Electronic expansion valve
Operation sound (Hi / Me / Lo)
dB-A
43 / 40 / 37
Refrigerant tubing connections
Flare type
Refrigerant tube diameter
Narrow tube mm (in.)
9.52 (3/8)
Wide tube
mm (in.)
15.88 (5/8)
Drain connection
20A, OD26 mm
Remote controller
Optional (RCIRP-FL)
Refrigerant tubing kit / Accessories
Optional / –
Color (Approximate value)
Munsell 10Y 9.0 / 0.4, RAL 9010-GL
DIMEN
S
ION
S
& WEIGHT
Package dimensions
Unit dimensions
Unit dimensions
Height
mm (in.)
210 (8-9/32)
280 (11-1/32)
1670 (65-24/32)
780 (30-23/32)
0.365 (12.9)
Width
mm (in.)
1595 (62-25/32)
Depth
mm (in.)
680 (26-25/32)
Net weight
kg (lbs.)
Shipping weight
kg (lbs.)
Shipping volume
m
3
(cu. ft)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27°C DB / 19°C WB; Outdoor air temperature 35°C DB
Heating: Indoor air temperature 20°C DB; Outdoor air temperature 7°C DB / 6°C WB
220
230
33 (73)
37 (82)
04-218 Airwell-4_4-5.qxp 01/06/2007 13:09 Page 77