11

6.2 

Recommendation For Interconnection Tubing Installation   

Three possible versions are schematically illustrated: 

1) The outdoor unit installed above the indoor unit (Figure 10) - such installation requires an oil trap

in the suction line at the lowest point of the riser. The radius of the oil trap should be as short as 
possible (See Figure 11). Horizontal runs of suction line should have a 0.5% minimum pitch
toward the outdoor unit. Liquid line should follow the suction line (except for trap). In case the 
insulation must be partially removed for installation purposes, it is imperative that lines be fully 
insulated with Armaflex, or equivalent insulation, after installation has been completed. 

1. Air 
2. Air 
3. Suction 

Line 

4.  Oil trap every 

3 m. 

5. Liquid 

Line 

6. Indoor 

unit 

7. See 

Table 

8. Outdoor 

Unit 

Figure 10. Interconnecting Tubing - Outdoor Unit

above Indoor Unit 

Figure 11

.

Tube Bending 

2) The outdoor unit is installed below the indoor unit (Figure 12) - no trap is required in such

installation. Besides it, the same applies as above. 

3) The units are installed at the same level (Figure 13) - no trap is required in such installation. 

Besides it, the same applies as above. 

1. Air 
2.  Outdoor Unit  
3. Liquid 

Line 

4. Suction 

Line 

5. Indoor 

Unit 

1. Air 
2.  Outdoor Unit  
3. Suction 

Line 

4. Liquid 

Line 

5.  Indoor Unit   

Figure 12. Interconnecting Tubing - Outdoor Unit
                 Below Indoor Unit 

Figure 13. Interconnecting Tubing - Outdoor Unit  and
                 Indoor Unit at the Same  Level 

Summary of Contents for DSD 40 RCA Series

Page 1: ...ENTRAL AIR CONDITIONER SPLIT SYSTEM WITH ELECTRONIC CONTROL SERIES INSTALLATION INSTRUCTIONS DSD 40 RCA GCD 40 RC DSD 40 RCA GCD 40 RCX DSD 50 RCA GCD 50 RCX DSD 60 RCA GCD 60 RCX DSD CAT NO ENG 6 5 9...

Page 2: ...g mounting 8 OUTDOOR UNIT INSTALLTION 9 INSTALLATION OF INTERCONNECTING TUBING BETWEEN INDOOR AND OUTDOOR UNIT 10 General 10 Recomendation for interconnecting tubing installation 11 Setting in operati...

Page 3: ...le No 1 If longer tubing is required consult your dealer b Outdoor unit installation should provide for Easy service access Minimum disturbance to the owner and nearby neighbors A minimum distance of...

Page 4: ...ntrol Unit Port 8 Main Power Port Figure 1 Indoor Unit Outline Dimensions Return Air Spigot Connection Size W H DSD 40 RCA GCD 40 RC DSD 40 RCA GCD 40 RCX DSD 50 RCA GCD 50 RCX DSD 60 RCA GCD 60 RCX D...

Page 5: ...tion tube connector flared 3 Liquid tube connector flared 4 Service valves 5 Service taps 6 Air inlet 7 Air outlet Figure 2 General dimensions of GCD 40 RC GCD 40 RCX GCD 50 RCX outdoor units WALL 300...

Page 6: ...3 General dimensions of GCD 60 RCX outdoor unit Figure 3A Example of Installation OUTDOOR UNIT Condenser GCD 60 RCX WALL 300 MIN 300 MIN WALL 600 MIN WALL 1000 MIN WALL 500 MIN FROM TOP MINIMUM CLEAR...

Page 7: ...to the unit without interference b The unit should not be installed close to rooms where noise should be avoided bedrooms children rooms etc The location should allow good air circulation 1 Frame inst...

Page 8: ...le with a minimum dimension of 700x300 mm or similar cross section with full acoustical lining inside and no more than two long radius elbows The cross section at the duct connection to the unit shall...

Page 9: ...ion 4 3 Ceiling Mounting The indoor unit can be mounted using spring or serrated rubber isolators a Spring isolators mounting Insert four 3 8 stu in the ceiling according to the dimensions of the spri...

Page 10: ...this type of installation 1 Concrete Ceiling 2 Bolt for Ceiling Insert 3 Leveling Nut 4 Fastening Nut Figure 7 Indoor Unit Installation Ceiling Mounting using Rubber Isolators 5 OUTDOOR UNIT INSTALLA...

Page 11: ...inimum If bends are necessary perform them only by using professional tube benders and not manually Make sure that tubing is insulated on its entire length including tube ends and quick connectors or...

Page 12: ...ith Armaflex or equivalent insulation after installation has been completed 1 Air 2 Air 3 Suction Line 4 Oil trap every 3 m 5 Liquid Line 6 Indoor unit 7 See Table 8 Outdoor Unit Figure 10 Interconnec...

Page 13: ...1 9 2 1 3 8 1 2 5 8 3 4 1 Copper Tube 2 Flaring Tool Figure 15 Tube flaring 6 3 3 Evacuation and setting in operation a Connect two charging hoses equipped with a push pin on one side as shown in Fig...

Page 14: ...ce Connection 1 Charging Set 2 Vacuum Pump 3 Outdoor Unit 4 Service Port 5 Valve Cap 6 3 Way Suction Valve 7 Service Port Optional 8 3 Way Liquid Valve 9 Indoor unit 10 Suction Flare Connection 11 Liq...

Page 15: ...with water and verify its free flow through the drain line Verify also absence of any water leakage underneath the unit 8 ELECTRICAL CONNECTIONS 8 1 Power Supply WARNING Electrical connection shall be...

Page 16: ...d control optional 2 Terminal board 8 Power supply 3 Interconnecting cable 9 Semi automatic breaker by installer 4 Indoor unit 10 Indoor safety breaker 10A 5 Display control unit 11 Terminal board 6 W...

Page 17: ...the unit is connected to the power supply the outdoor unit controller will start a self test for correct phase order and after a few seconds GREEN LED 1 will light on If the RED LED 2 and GREEN LED 3...

Page 18: ...holes in the wall to match the holes in the Display Control Unit install the inserts and fasten the unit to the wall with 3 screws The Display Control Unit 4 is provided of a special communication ca...

Page 19: ...Gold Green Black Brown Purple Yellow Orange Red Figure 21 Connection to a single Display Control Unit 1 Main Control Board on Indoor Unit 2 Distribution Board Cat N 402729 3 Communication cable Cat N...

Page 20: ...ore be determined as follows a Avoid installation at location exposed to direct sunlight or near heat sources b Select a location free of any obstructions such as curtains etc c Select a neutral zone...

Page 21: ...mote control commands 4 2 Outdoor unit Check for any abnormal noise or vibrations during operation of the air conditioner Check that the noise condensate drainage or air flow does not disturb the neig...

Page 22: ...5 ADELAIDE Offices on the Park Suite 27 8 Greenhill Road Wayville SA 5034 TEL 08 8372 7866 FAX 08 8372 7816 PERTH Suite 23 350 Cambridge St Wembley WA 6014 TEL 08 9284 0800 FAX 08 9284 0600 NEWCASTLE...

Reviews: