background image

12

6.3   Setting in Operation 

WARNING

This paragraph describes the necessary steps for setting the unit into operation; be sure to follow the 
instructions, to assure proper functioning of the air-conditioner.  
The outdoor unit is recharged with the correct amount of refrigerant. In extended runs, for additional 
refrigerant charge please refer to the outdoor unit name plate. This process shall be performed only by 
qualified refrigeration technicians with a professional charging set. 

6.3.1  Flare preparation 

a)  Cut the tube, using a tube cutter. Make 

sure that the cut is perpendicular to the 
tube axis and free of metal shavings (See 
Figure 14).

b)  Slip the flare-nut over the tube, secure the 

tube in the flaring tool, as shown in Figure 
15 and perform the flare on the tube end. 
The tube projection length (a) from the 
flaring block varies with tube diameter and 
shall be set as indicated in the table. Apply 
few drops of refrigeration oil to the tube 
before flaring. 

CORRECT

90º

INCORRECT

Figure 14. Tube cutting

6.3.2

Connecting the tubes

(See Figure 16)

Connect and tighten the flare nuts to the refrigeration valves 
on the outdoor unit and to the male connectors 
of the indoor unit. Coat the flared surfaces lightly with 
refrigeration oil to improve sealing. 

Note:

 First tighten manually the flare nuts, then use a 

wrench. See Table No. 2 for tightening torque values.  

A (mm) 

TUBE OD

1.3
1.6
1.9
2.1

3/8” 
1/2” 
5/8” 
3/4” 

1. Copper 

Tube 

2. Flaring 

Tool 

Figure 15. Tube flaring 

6.3.3   Evacuation and setting in operation  

a)  Connect two charging hoses equipped with a push-pin on one side, as shown in Figure 

16. Connect  the two hose en without the push-pin to the LOW (suction) and HIGH (liquid)
sides of the charging set; remove the guard caps from the service ports of the tree-way 
suction and liquid valves and connect the hose en with the push-pins to the service ports 
(See Figure 17) on units without service valve on the liquid port, connect only the tube to
the suction 3-way valve. 

b)  Connect the center hose of the charging set to a vacuum pump. 

CAUTION

c)  Turn on the vacuum pump and make sure that the low pressure gauge reading moves  

from 0 kPa to 101 kPa; then evacuate the system for 10 minutes.

If gauge needle does not move from 0 kPa to 101 kPa, this indicate a leak. Take the

following measures: tighten all connections; if leaking stops when the tubing connections 
are tightened, proceed from step c. If leaking persist even after connections are tighten, 
detect the leak and repair it; be sure to proceed only after all leaks have been eliminated. 

d)  Close the valves of both the suction and liquid sides of the charging set and turn off the 

vacuum pump. Make sure that the gauge needle does not move for about 5 minutes. 

e)  Disconnect the charging hoses from the vacuum pump and from the service ports of both 

the
tree-way valves. 

f)  Replace the service port and valve caps of both tree-way valves and tighten them with a 

torque wrench; see table of torque values in Figure 16.

Summary of Contents for DSD 40 RCA Series

Page 1: ...ENTRAL AIR CONDITIONER SPLIT SYSTEM WITH ELECTRONIC CONTROL SERIES INSTALLATION INSTRUCTIONS DSD 40 RCA GCD 40 RC DSD 40 RCA GCD 40 RCX DSD 50 RCA GCD 50 RCX DSD 60 RCA GCD 60 RCX DSD CAT NO ENG 6 5 9...

Page 2: ...g mounting 8 OUTDOOR UNIT INSTALLTION 9 INSTALLATION OF INTERCONNECTING TUBING BETWEEN INDOOR AND OUTDOOR UNIT 10 General 10 Recomendation for interconnecting tubing installation 11 Setting in operati...

Page 3: ...le No 1 If longer tubing is required consult your dealer b Outdoor unit installation should provide for Easy service access Minimum disturbance to the owner and nearby neighbors A minimum distance of...

Page 4: ...ntrol Unit Port 8 Main Power Port Figure 1 Indoor Unit Outline Dimensions Return Air Spigot Connection Size W H DSD 40 RCA GCD 40 RC DSD 40 RCA GCD 40 RCX DSD 50 RCA GCD 50 RCX DSD 60 RCA GCD 60 RCX D...

Page 5: ...tion tube connector flared 3 Liquid tube connector flared 4 Service valves 5 Service taps 6 Air inlet 7 Air outlet Figure 2 General dimensions of GCD 40 RC GCD 40 RCX GCD 50 RCX outdoor units WALL 300...

Page 6: ...3 General dimensions of GCD 60 RCX outdoor unit Figure 3A Example of Installation OUTDOOR UNIT Condenser GCD 60 RCX WALL 300 MIN 300 MIN WALL 600 MIN WALL 1000 MIN WALL 500 MIN FROM TOP MINIMUM CLEAR...

Page 7: ...to the unit without interference b The unit should not be installed close to rooms where noise should be avoided bedrooms children rooms etc The location should allow good air circulation 1 Frame inst...

Page 8: ...le with a minimum dimension of 700x300 mm or similar cross section with full acoustical lining inside and no more than two long radius elbows The cross section at the duct connection to the unit shall...

Page 9: ...ion 4 3 Ceiling Mounting The indoor unit can be mounted using spring or serrated rubber isolators a Spring isolators mounting Insert four 3 8 stu in the ceiling according to the dimensions of the spri...

Page 10: ...this type of installation 1 Concrete Ceiling 2 Bolt for Ceiling Insert 3 Leveling Nut 4 Fastening Nut Figure 7 Indoor Unit Installation Ceiling Mounting using Rubber Isolators 5 OUTDOOR UNIT INSTALLA...

Page 11: ...inimum If bends are necessary perform them only by using professional tube benders and not manually Make sure that tubing is insulated on its entire length including tube ends and quick connectors or...

Page 12: ...ith Armaflex or equivalent insulation after installation has been completed 1 Air 2 Air 3 Suction Line 4 Oil trap every 3 m 5 Liquid Line 6 Indoor unit 7 See Table 8 Outdoor Unit Figure 10 Interconnec...

Page 13: ...1 9 2 1 3 8 1 2 5 8 3 4 1 Copper Tube 2 Flaring Tool Figure 15 Tube flaring 6 3 3 Evacuation and setting in operation a Connect two charging hoses equipped with a push pin on one side as shown in Fig...

Page 14: ...ce Connection 1 Charging Set 2 Vacuum Pump 3 Outdoor Unit 4 Service Port 5 Valve Cap 6 3 Way Suction Valve 7 Service Port Optional 8 3 Way Liquid Valve 9 Indoor unit 10 Suction Flare Connection 11 Liq...

Page 15: ...with water and verify its free flow through the drain line Verify also absence of any water leakage underneath the unit 8 ELECTRICAL CONNECTIONS 8 1 Power Supply WARNING Electrical connection shall be...

Page 16: ...d control optional 2 Terminal board 8 Power supply 3 Interconnecting cable 9 Semi automatic breaker by installer 4 Indoor unit 10 Indoor safety breaker 10A 5 Display control unit 11 Terminal board 6 W...

Page 17: ...the unit is connected to the power supply the outdoor unit controller will start a self test for correct phase order and after a few seconds GREEN LED 1 will light on If the RED LED 2 and GREEN LED 3...

Page 18: ...holes in the wall to match the holes in the Display Control Unit install the inserts and fasten the unit to the wall with 3 screws The Display Control Unit 4 is provided of a special communication ca...

Page 19: ...Gold Green Black Brown Purple Yellow Orange Red Figure 21 Connection to a single Display Control Unit 1 Main Control Board on Indoor Unit 2 Distribution Board Cat N 402729 3 Communication cable Cat N...

Page 20: ...ore be determined as follows a Avoid installation at location exposed to direct sunlight or near heat sources b Select a location free of any obstructions such as curtains etc c Select a neutral zone...

Page 21: ...mote control commands 4 2 Outdoor unit Check for any abnormal noise or vibrations during operation of the air conditioner Check that the noise condensate drainage or air flow does not disturb the neig...

Page 22: ...5 ADELAIDE Offices on the Park Suite 27 8 Greenhill Road Wayville SA 5034 TEL 08 8372 7866 FAX 08 8372 7816 PERTH Suite 23 350 Cambridge St Wembley WA 6014 TEL 08 9284 0800 FAX 08 9284 0600 NEWCASTLE...

Reviews: