![Airwell DLS 43 DCI Service Manual Download Page 14](http://html1.mh-extra.com/html/airwell/dls-43-dci/dls-43-dci_service-manual_2880116014.webp)
2-7
PRODUCT DATA SHEET
SM DLSDCI 3-A.1 GB
2.7
DLS 43 DCI 1 PH
Model Indoor Unit
DLS 43 DCI
Model Outdoor Unit
YBD 042 H11
Installation Method
DUCTED
Characteristics
Units
Cooling
Heating
Capacity - Nominal (Minimum ~ Maximum)
(1)
Btu/hr
42,650 (15,350-49,470)
47,770 (15,350-54,590)
kW
12.5 (4.5-14.5)
14.0 (4.5-16.0)
Power Input - Nominal (Minimum ~ Maximum)
( (1)
W
3,730 (1,400-4,850)
4,100 (1,100-5,050)
EER (Cooling) or COP(Heating)
(1)
W/W
3.35
3.41
{ !"{@ "&
-
A
B
Power Supply
V/Ph/Hz
230 / 1 / 50
Rated Current (Nominal)
A
17.4
18.4
Starting Current
A
<10
Circuit Breaker Rating
A
32
INDOOR
Fan Type & Quantity
CENTRIFUGAL
Fan Speed
H/M/L
RPM
870
650
560
[
(2)
H/M/L
m
3
/hr
2025
1450
1250
External Static Pressure
Nom-Max
Pa
50-100
Sound Power Level
(3)
H/M/L
dB (A)
71
67
62
Sound Pressure Level
(4)
H/M/L
dB (A)
52
49
47
Moisture Removal (Nominal)
L/hr
3.3
Condensate Drain Tube I.D.
mm
16
Dimensions
W/H/D
mm
854
300
816
Weight
kg
33
Package Dimensions
W/H/D
mm
1010
342
917
Packaged Weight
kg
38
Units per Pallet
Units
6
Stacking Height
Units
6
OUTDOOR
Refrigerant Control
Electronic Expansion Valve
Compressor Type, Model
Scroll, ANB42
Motor type
DCBL Inverter
Fan Type & Quantity
[}=
Fan Speed
RPM
850-150 (continuous)
[
Max
m
3
/hr
5,700
Sound Power Level
Nom
dB (A)
68
70
Sound Pressure Level
Nom
dB (A)
56
58
Dimensions
W/H/D
mm
900
1255
340
Weight
kg
110
Package Dimensions
W/H/D
mm
985
1395
435
Packaged Weight
kg
120
Units per Pallet
Units
1
Stacking Height
Units
1
Refrigerant Type
R410A
Refrigerant Chargeless Distance
kg/m
3.3 / 30
Additional Charge Per 1 Meter
g/m
40
Connections
Between Units
Liquid Line
In (mm)
3/8” (9.53)
Suction Line
In (mm)
3/4” (19.0)
Max. Tubing Length
m
70
Max. Height Difference
m
30
Operation Control Type
LCD Remote Control
Heating Elements
kW
BH 70W - optional
Others
(1)
Rating conditions in accordance with EN14825 and EN14511 (for ducted units).
(2)
[
(3)
Sound power in ducted units is measured at air discharge.
(4)
Sound pressure level measured at 1.0 meter distance from unit.
Summary of Contents for DLS 43 DCI
Page 62: ...SM DLSDCI 3 A 2 GB 9 2 WIRING DIAGRAMS 9 3 Indoor Unit DLS 43 DCI...
Page 117: ...12 4 CONTROL SYSTEM SM DLSDCI 3 A 1 GB 12 11 7 Segment Legend 7 7 segments lege end...
Page 154: ...SM DLSD CONTRO DCI 3 A 2 OL SYSTEM M 15 2...
Page 155: ...SM DLSD CONTRO DCI 3 A 2 OL SYSTEM M 15 3...
Page 156: ...SM DLSD CONTRO DCI 3 A 2 OL SYSTEM M 15 4...