![Airwell DLS 43 DCI Service Manual Download Page 10](http://html1.mh-extra.com/html/airwell/dls-43-dci/dls-43-dci_service-manual_2880116010.webp)
SM DLSDCI 3-A.2 GB
2-3
PRODUCT DATA SHEET
2.3
DLSE 30 DCI
Model Indoor Unit
AWSI-DLSE030 –N11
Model Outdoor Unit
AWAU-YBDE030-H11
Installation Method
DUCTED
Characteristics Units
Cooling
Heating
Average Warmer
Pdesign kW
7.5
8.6
8.6
SEER / SCOP
(2)
W/W
5.5
3.9
4.3
Energy efficiency class
A
A
A+
Annual energy consumption
kWh
1224
4502
2680
Tbiv
o
C N/A -3 6
Tol
o
C N/A -15
-15
Capacity Range
(1)
(min÷max)
kW
2.8÷8.4
2.8÷9.4
Power supply
V/Ph/Hz
220-240V/Single/50Hz
Circuit breaker rating
A
20
INDOOR
Fan type & quantity
Centrifugal x 1
Fan speeds
T/H/M/L
RPM
760/700/60/410
Air flow
(3)
T/H/M/L
m3/hr
1410/1290/1140/950
External static pressure
Min-Max
Pa
25-80
Sound power level
(4)
H/M/L
dB(A)
65/63/60/56
Sound pressure level
(5)
H/M/L
dB(A)
48/46/43/39
Moisture removal
l/hr
2.7
Condensate drain tube I.D
mm
19
Dimensions WxHxD
790x256x749
790x256x749
Weight kg
31
Package dimensions
WxHxD
960x300x855
959x315x854
Packaged weight
kg
33.5
Units per pallet
units
6
Stacking height
units
6
OUTDOOR
Refrigerant control
EEV
Compressor type, model
Twin Rotary DC Inverter
Fan type & quantity
Axial x 1
Fan speeds
H/L
RPM
300 – 850 (continuous)
Air flow
H/L
m3/hr
3400
Sound power level
(4)
H/L
dB(A)
68
Sound pressure level
(5)
H/L
dB(A)
56
Dimensions WxHxD
mm
900x860x340
Weight kg
66
Package dimensions
WxHxD
mm
985x905x435
Packaged weight
kg
68.5
Units per pallet
Units
6
Stacking height
units
2 levels
Refrigerant type
R410A
Refrigerant charge(standard connecting
tubing length)
Kg(7.5m) 2.10
Additional charge per 1 meter
gr / 1m
7.5m < 0gr < 15m < 50gr per 1m < 50m
Connections between
units
Liquid line
In.(mm)
3/8"(9.53)
Suction line
In.(mm)
5/8"(15.88)
Max. tubing length
m.
Max.50
Max. height
difference
m. Max.25
Operation control type
Remote control
Heating elements
kW
Others
(1) Rating conditions in accordance with EN14825 and EN14511 (for ducted units).
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1.4 meter distance from unit.
Summary of Contents for DLS 43 DCI
Page 62: ...SM DLSDCI 3 A 2 GB 9 2 WIRING DIAGRAMS 9 3 Indoor Unit DLS 43 DCI...
Page 117: ...12 4 CONTROL SYSTEM SM DLSDCI 3 A 1 GB 12 11 7 Segment Legend 7 7 segments lege end...
Page 154: ...SM DLSD CONTRO DCI 3 A 2 OL SYSTEM M 15 2...
Page 155: ...SM DLSD CONTRO DCI 3 A 2 OL SYSTEM M 15 3...
Page 156: ...SM DLSD CONTRO DCI 3 A 2 OL SYSTEM M 15 4...