Page 34
Electrical and
Gas Leak Checks
Electrical Safety Checks
After installation, confirm that all electrical wiring
is installed in accordance with local and national
regulations, and according to the Installation
Manual.
BEFORE TEST RUN
Check Grounding Work
Measure grounding resistance by visual detection
and with grounding resistance tester. Grounding
resistance must be less than 0.1
Ω
.
Note:
This may not be required for some
locations in North America.
DURING TEST RUN
Check for Electrical Leakage
During the
Test Run,
use an electroprobe and
multimeter to perform a comprehensive electrical
leakage test.
If electrical leakage is detected, turn off the unit
immediately and call a licensed electrician to find
and resolve the cause of the leakage.
Note:
This may not be required for some
locations in North America.
Gas Leak Checks
There are two different methods to check for gas
leaks.
Soap and Water Method
Using a soft brush, apply soapy water or liquid
detergent to all pipe connection points on the
indoor unit and outdoor unit. The presence of
bubbles indicates a leak.
Leak Detector Method
If using leak detector, refer to the device’s
operation manual for proper usage instructions.
AFTER PERFORMING GAS LEAK CHECKS
After confirming that the all pipe connection
points DO NOT leak, replace the valve cover on
the outside unit.
WARNING – RISK OF
ELECTRIC SHOCK
ALL WIRING MUST COMPLY WITH LOCAL
AND NATIONAL ELECTRICAL CODES,
AND MUST BE INSTALLED BY A LICENSED
ELECTRICIAN.
Before Test Run
Only perform test run after you have completed
the following steps:
•
Electrical Safety Checks
– Confirm that
the unit’s electrical system is safe and
operating properly
•
Gas Leak Checks
– Check all flare nut
connections and confirm that the system is
not leaking
•
Confirm that gas and liquid (high and low
pressure) valves are fully open
A: Low pressure stop valve
B: High pressure stop valve
C& D: Indoor unit flare nuts
Check-point of indoor unit
Check-point of outdoor unit
A
B
C
D
Electrical and Gas Leak Checks
Summary of Contents for AWAU-YGF009-H11
Page 38: ......
Page 75: ......
Page 78: ...03 07 07 1 08 2 09 3 10 4 10 5 11 13...
Page 80: ...EN 8 IEC 3...
Page 82: ...1 2 CEC NEC 3 4 5 6 7 3 1 8 9 10 11 R290 1 5 2 50 2 24 2 3 4 5 5...
Page 83: ...EN 25 3 IEC 6...
Page 86: ...SLEEP DRY FAN COOL 2 2 1 HEAT 2 2 1 8 DRY AUTO COOL COOL USB 2 1 1 2 1 1 LEDS EL0C EC 9...
Page 87: ...HEAT COOL 1 2 3 5 6 4 10...
Page 88: ...6 7 8 9 104 40 1 2 3 4 5 F lter 10 11...
Page 89: ...FAN 15 CL 240 4 CL 3 15 nF 2880 4 nF 3 12...
Page 90: ...COOL HEAT FAN 3 13...
Page 91: ...SILENCE SILENCE 14...
Page 92: ...3 E x P x F x EH xx EL xx EC xx PH xx PL xx PC xx 10 15...
Page 93: ...3 2 1 1 2 1 1 1 2 8 5 8 5 2 1 6 35 1 4i 3 8 9 52 3 8 9 52 1 2 12 7 5 8 16 3 4 19 3 2 1 16...
Page 94: ...1 5 9 15 2 3 12 4 75 12 4 75 90 55 2 3 4 4 5 6 7 8 9 8 17...
Page 95: ...1 1 3 2 4 2 4 3 6 5 6 5 7 8 7 8 9 10 11 11 1 2 1 2 3 4 5 6 7 8 9 10 11 18...
Page 96: ...1 5 9 15 4 75 12 4 75 12 90 55 2 3 2 0 2 5 19...
Page 98: ...4 5 1 2 Teflon 3 21...
Page 100: ...1 2 7 1 3 4 5 6 u 2 3 7 8 23...
Page 101: ...8 3 4 5 6 7 4 1 2 3 4 5 6 7 1 95 1 25 50 30 30 50 1 2 1 95 30 50 1 2 1 95 1 2 24...
Page 102: ...90 1 18 25 24 60 12 79 200 12 30 24 60...
Page 103: ...2 3 M10 1 90 3 4 1 2 2 26...
Page 105: ...4 2 3 u 4 5 6 PVC 7 8 1 H05V2V2 F H05VV F H07RN F H07RN F 1 57 40 1 2 3 4 5 6 7 L 28 40 1 57...
Page 109: ...8 5 1 4 9 10 11 1 2 3 4 10 76 15 5 5 12 13 76 6 5 7 32...
Page 110: ...16 5 25 7 5 0 25 6 35 12 x 0 26oZ ft x 0 13oZ ft 0 375 9 52 24 R32 R32 33...
Page 111: ...0 1 34...
Page 112: ...5 30 1 2 ON OFF 3 5 4 62 17 17 1 2 3 2 2 COOL 35...
Page 113: ......