TROUBLESHOOTING
13-4
Service Manual
– YBZE DCI 1-A.1 GB
13.1.5
Checking the refrigeration system
Checking system pressures and other thermodynamic measures should be done when system
is in Test Mode (in Test mode, system operates in fixed settings). The performance curves
given in this manual are given for unit performance in test mode when high indoor fan speed is
selected.
Entering test mode please refer to section 12- Control system.
13.2
Simple procedures for checking the Main Parts
13.2.1
Checking Mains Voltage.
Confirm that the Mains voltage is between 198 and 264 VAC. If Mains voltage is out of this
range, abnormal operation of the system is expected. If in range check the Power (Circuit)
Breaker and look for broken or loosed cable lugs or wiring mistake(s).
13.2.2
Checking Power Input.
If Indoor unit power LED is unlighted, power down the system and check the fuse of the Indoor
unit. If the fuse is OK replace the Indoor unit controller. If the fuse has blown, replace the fuse
and power up again.
Checking Power Input procedure for the Outdoor unit is the same as with the Indoor unit.
13.2.3
Checking the Outdoor Fan Motor.
Check the voltage between any two pins of connector OFAN on controller, normal voltage is
280~380VDC
13.2.4
Checking the Compressor.
The compressor is brushless permanence magnetic DC motor. Three coil resistance is
same. Check the resistance between three poles. The normal value should be with the
almost same value. Pay attention U,V, W are respective to connect to
RED,YELLOW,BLUE
wires.
13.2.5
Checking the Reverse Valve (RV).
Running in heating mode, check the voltage between two pins of reverse valve connector,
normal voltage is 220VAC.
Summary of Contents for AWAU-YBZE218-H11
Page 4: ......
Page 14: ......
Page 16: ......
Page 19: ...PERFORMANCE DATA Service Manual YBZE DCI 1 A 1 GB 5 1 5 PERFORMANCE DATA...
Page 20: ......
Page 21: ...PRESSURE CURVES Service Manual YBZE DCI 1 A 1 GB 6 1 6 PRESSURE CURVES...
Page 22: ......
Page 24: ......
Page 26: ......
Page 31: ...WIRING DIAGRAM Service Manual YBZE DCI 1 A 1 GB 9 5 9 6 Wiring connection between IDU and ODU...
Page 32: ......
Page 33: ...WIRING DIAGRAM Service Manual YBZE DCI 1 A 1 GB 10 1 10 REFRIGERATION DIAGRAMS...
Page 34: ......
Page 35: ...TUBING CONNECTIONS Service Manual YBZE DCI 1 A 1 GB 11 1 11 TUBING CONNECTIONS...
Page 36: ......
Page 50: ......
Page 68: ...EXPLODED VIEW SPARE PART LIST 15 12 Service Manual YBZE DCI 1 A 1 GB APPENDIX...