CONTROL SYSTEM
Service Manual
– YBZE DCI 1-A.1 GB
12-9
12.7.4
Compressor over Heating Protection
The Discharging temperature is used as t
he compressor’s internal temperature. If the discharge
temperature rises above a certain level, the operating frequency upper limit is set to keep this
temperature from going up further.
Compressor frequency will be reduced when CTT reaches above 97C
Compressor will stop when CTT reaches 110C
If the unit stops as such protection for 6 times
(the counter will be cleared after the compressor has
run for 7min)
, it can not resume running automatically and display malfunction, it can resume by
remote control ON/OFF reset.
12.7.5
Compressor over Current Protection
Detect an input current by the CT during the compressor is running, and set the frequency upper
limit from such input current. In case of heat pump model, this control is the upper limit control
function of the frequency which takes priority of the lower limit of four way valve activating
compensation.
Detail
For model 14: Compressor will stop when AC current >= 16.0A for continuously 2.5s
For model 18/30: Compressor will stop when AC current >= 20.0A for continuously 2.5s
If the unit stops as such protection for 6 times (the counter will be cleared after the compressor has
run for 7min), it can not resume running automatically and display malfunction, it can resume by
remote control ON/OFF reset.
12.7.6
Outdoor Coil Deicing Protection
This protection is for Heat Pump Only
This protection is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor
heat exchanger temperature must be more than its setting values when finishing the deicing
protection.
In the deicing protection, IFAN is forced OFF.
12.7.6.1 Deicing Starting Conditions
The starting conditions must be made with the outdoor air temperature (OAT) and outdoor coil
temperature (OCT). Under the conditions that the system is in heating operation, after the time for
defrosting is judged to be satisfied, if the temperature for deicing is satisfied after detections for
continuous 1 minute, the deicing operation will start.
Summary of Contents for AWAU-YBZE218-H11
Page 4: ......
Page 14: ......
Page 16: ......
Page 19: ...PERFORMANCE DATA Service Manual YBZE DCI 1 A 1 GB 5 1 5 PERFORMANCE DATA...
Page 20: ......
Page 21: ...PRESSURE CURVES Service Manual YBZE DCI 1 A 1 GB 6 1 6 PRESSURE CURVES...
Page 22: ......
Page 24: ......
Page 26: ......
Page 31: ...WIRING DIAGRAM Service Manual YBZE DCI 1 A 1 GB 9 5 9 6 Wiring connection between IDU and ODU...
Page 32: ......
Page 33: ...WIRING DIAGRAM Service Manual YBZE DCI 1 A 1 GB 10 1 10 REFRIGERATION DIAGRAMS...
Page 34: ......
Page 35: ...TUBING CONNECTIONS Service Manual YBZE DCI 1 A 1 GB 11 1 11 TUBING CONNECTIONS...
Page 36: ......
Page 50: ......
Page 68: ...EXPLODED VIEW SPARE PART LIST 15 12 Service Manual YBZE DCI 1 A 1 GB APPENDIX...