0
10
20
30
40
50
60
70
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
Tw
u
[°
C]
Tae [°C]
1
2
2
3
Size
190
300
190S
300S
Ventilation
Type of fan
Centrifugal
Air flow
m
3
/h
270
414
270
414
Available pressure head
Pa
25
45
25
45
Integration
Solar coil surface
m
2
-
-
1,10
1,30
Solar coil material
-
-
Enamel Steel
bar
-
-
10
10
Maximum operating pressure
MPa
-
-
1
1
1. Inlet water temperature 15 °C, accumulator set 45°C, air on source side 15°C D.B /12°C W.B.
2. The product complies with the European Directive ErP, which includes the Commission Delegated Regulation (EU) N. 812/2013 and the Commission Delegated Regulation N.
814/2013, Average Climate, Heat Pump Water Heater
3. The product complies with the European Directive ErP, which includes the Commission Delegated Regulation (EU) N. 812/2013 and the Commission Delegated Regulation N.
814/2013, Warmer Climate, Heat Pump Water Heater
4. The product complies with the European Directive ErP, which includes the Commission Delegated Regulation (EU) N. 812/2013 and the Commission Delegated Regulation N.
814/2013, Colder Climate, Heat Pump Water Heater
5. Data referred to completely ducted unit.
6. Maximum temperature that can be reached during Anti-legionella mode(Dinsifect)
*It contains fluorinated greenhouse gases
Size
190
300
190S
300S
Power supply
(1)
V
220-240/1/50
220-240/1/50
220-240/1/50
220-240/1/50
F.L.A. - Current absorbed at the maximum allowed conditions
A
16
,10
16,50
16
,10
16,50
F.L.I. - Power absorbed at full load (at the maximum allowed condi-
tions)
kW
3
,
7
0
3,75
3,70
3,75
M.I.C - Maximum inrush current
A
22,2
33,7
22,2
33,7
300 - 300S
1. Use range of the heat pump
2. Use range of the electrical heating element
3. Use range of the electrical heating element only in Anti-Legionella mode
(Disinfect)
Twu [°C] water temperature in the accumulator
Tae [°C] air temperature at exchanger inlet
190 - 190S
Electrical data
1) Power supply 220-240/1/50 Hz
For power voltages other than the standard, contact the
Airwell
technical department
The units are conforming with the prescriptions of European Standards EN 60204 and EN 60335
Warning: when defining the correct size, verify that all absorption is compliant with current electrical supply
contracts in force in the country of installation
Operating limits
Summary of Contents for AW-TDF Series
Page 90: ...Parts unit 190 Description...
Page 91: ...Parts unit 190 Description...
Page 92: ...Parts unit 190 Description...
Page 93: ...Parts unit 300 Description El ectr ical heate r...
Page 94: ...Parts unit 300 Description...
Page 95: ...Parts unit 300 Description...
Page 129: ......
Page 159: ......