FWDB Low temperature floor ceiling-Technical Manual R32-50Hz
5 Insulation Work
5.1Insulation material and thickness
5.1.1. Insulation material
Insulation material should adopt the material which is able to endure the pipe’s temperature: no
less than 70
℃
in the high-pressure side, no less than 120
℃
in the low-pressure side(For the cooling type
machine, no requirements at the low-pressure side.)
Example: Heat pump type----Heat-resistant Polyethylene foam (withstand above
120
℃
)
Cooling only type----Polyethylene foam (withstand above 100
℃
)
5.1.2. Thickness choice for insulation material
Insulation material thickness is as follows:
Pipe diameter (mm)
Adiabatic material thickness
Refrigerant pipe
Φ6.4—Φ25.4
10mm
Φ28.6—Φ38.1
15mm
Drainage pipe
Inner diameterΦ20—Φ32
6mm
5.2 Refrigerant pipe insulation
5.2.1. Work Procedure
①
Before laying the pipes, the non-jointing parts and non-connection parts should be heat
insulated.
②
When the gas proof test is eligible, the jointing area, expanding area and the flange area should be heat
insulated
5.2.2. Insulation for non-jointing parts and non-connection parts
wrong
right
Gas pipe and liquid pipe should
not be put together to insulate
Insulate the gas pipe
(cooling only)
Insulate the gas pipe and
liquid pipe
50
Summary of Contents for AW-FWDB018-N91
Page 15: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 13 4 Service Space ...
Page 18: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 16 6 2 AW FWDB024 N91 ...
Page 33: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 4 2 AW YMDB024 H91 31 ...
Page 39: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 8 2 AW YMDB024 H91 37 ...
Page 57: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 55 ...