FWDB Low temperature floor ceiling-Technical Manual R32-50Hz
1. Precaution on Installation
1.1. Measure the necessary length of the connecting pipe, and make it by the following way.
a. Connect the indoor unit at first, then the outdoor unit.
Bend the tubing in proper way. Do not harm them.
CAUTIONS:
Daub the surfaces of the flare pipe and the joint nuts with frozen oil, and wrench it for 3~4
rounds
With hands before fasten the flare nuts.
Be sure to use two wrenches simultaneously when you connect or disconnect the pipes.
Pipe gauge
Tightening torque
Flare dimension A
Min (mm) Max
Flare shape
Φ6.4
15
~
16N.m
(153
~
163 kgf.cm)
8.3
8.7
Φ9.5
25
~
26N.m
(255
~
265kgf.cm)
12.0
12.4
Φ12.7
35
~
36N.m
(357
~
367kgf.cm)
15.4
15.8
Φ15.9
45
~
47N.m
(459
~
480 kgf.cm)
18.6
19.1
Φ19.1
65
~
67N.m
(663
~
684kgf.cm)
22.9
23.3
b. The stop value of the outdoor unit should be closed absolutely (as original state). Every time you
connect it, first loosen the nuts at the part of stop value, then connect the flare pipe immediately (in 5
minutes). If the nuts have been loosened for a long time, dusts and other impurities may enter the pipe
system and may cause malfunction later. So please expel the air out of the pipe with refrigerant before
connection.
c. Expel the air after connecting the refrigerant pipe with the indoor unit and the outdoor unit. Then fasten
the nuts at the repair-points.
1.2. Locate The Pipe
a. Drill a hole in the wall (suitable just for the size of the wall conduit), then set on the fittings such as the
wall conduit and its cover.
b. Bind the connecting pipe and the cables together tightly with binding tapes. Do not let air in, which will
cause water leakage by condensation.
c. Pass the bound connecting pipe through the wall conduit from outside. Be careful of the pipe allocation
to do no damage to the tubing.
1.3. Connect the pipes.
1.4. Then, open the stem of stop values of the outdoor unit to make the refrigerant pipe connecting the
indoor unit with the outdoor unit in fluent flow.
1.5. Be sure of no leakage by checking it with leak detector or soap water.
1.6. Cover the joint of the connecting pipe to the indoor unit with the soundproof / insulating sheath (fittings),
and bind it well with the tapes to prevent leakage.
43
Summary of Contents for AW-FWDB018-N91
Page 15: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 13 4 Service Space ...
Page 18: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 16 6 2 AW FWDB024 N91 ...
Page 33: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 4 2 AW YMDB024 H91 31 ...
Page 39: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 8 2 AW YMDB024 H91 37 ...
Page 57: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 55 ...