![Airwell AW-FWDB018-N91 Service Manual Download Page 17](http://html1.mh-extra.com/html/airwell/aw-fwdb018-n91/aw-fwdb018-n91_service-manual_2879982017.webp)
FWDB Low temperature floor ceiling-Technical Manual R32-50Hz
15
6. Capacity Table
Cooling
6.1 AW-FWDB018-N91
MODEL
AW-FWDB018-N91
COOLING
OUTDOOR TEMPERATURE DRY
Indoor Conditions
21ºC
25ºC
30ºC
35ºC
40ºC
45ºC
49ºC
21ºC D
15ºC W
Total capacity kW
5.09
5.06
5.03
4.99
4.95
4.91
4.88
Input kW.
1.42
1.43
1.45
1.46
1.51
1.56
1.61
24ºC D
17ºC W
Total capacity kW
5.25
5.22
5.18
5.15
5.10
5.06
5.03
Input kW.
1.44
1.45
1.46
1.48
1.54
1.58
1.63
27ºC D
19ºC W
Total capacity kW
5.41
5.38
5.34
5.30
5.26
5.22
5.18
Input kW.
1.45
1.46
1.48
1.50
1.55
1.61
1.65
29ºC D
21ºC W
Total capacity kW
5.48
5.44
5.40
5.36
5.32
5.28
5.24
Input kW.
1.47
1.49
1.51
1.53
1.57
1.63
1.67
32ºC D
23ºC W
Total capacity kW
5.58
5.55
5.51
5.47
5.42
5.38
5.34
Input kW.
1.48
1.49
1.51
1.53
1.58
1.64
1.69
Summary of Contents for AW-FWDB018-N91
Page 15: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 13 4 Service Space ...
Page 18: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 16 6 2 AW FWDB024 N91 ...
Page 33: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 4 2 AW YMDB024 H91 31 ...
Page 39: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 8 2 AW YMDB024 H91 37 ...
Page 57: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 55 ...