8 - CONTROL
ATTENTION
The access to parameters or modifications are allowed only to the installer who assumes all responsibility, in case of
doubts please contact
Airwell
.
For any changes not permitted or not approved by
Airwell
, the same declines any responsibility for malfunctions and/
or damages to the unit/system.
PASSWORD-PROTECTED UNIT PARAMETERS (INSTALLER USE)
Number-
ing
Code
Descrip
Ɵ
on
default
Minimum
maxi-
mum
unit
1.01
AUTOText0
Automatic temperature setting X- axis set point 0
15
0
50
°C
1.02
AUTOText1
Automatic temperature setting X- axis set point 1
24
0
50
°C
1.03
AUTOSet0
Automatic temperature setting Y- axis set point 0
19
0
50
°C
1.04
AUTOSet1
Automatic temperature setting Y- axis set point 1
25
0
50
°C
1.05
EnOnOff
Unit switch mode
0: ON/OFF switch OFF signal is turned off, ON
boot
1: Wire controller control
2: Super terminal control
1
0
2
-
1.06
EnMode
Mode setting mode
0: ON/OFF signal ,ON heating,OFF cooling
1 : Wire controller setting;
2 : Super terminal control
3 : Set to automatic mode
1
0
3
-
1.07
EnFHC
Reserved
0
0
1
-
1.08
DeadZone
Automatic mode setting mode switching backlash
2
1
10
°C
1.09
TimeECO
Reserved
30
10
180
Min
1.1 0
TimeTestECO
Reserved
3
1
1 0
Min
1.11 TypeFireMode
Reserved
0
0
2
-
1.12 MaxReturn
Reserved
6
-10
15 °C
1.1 3
MaxAnAux
Reserved
100
50
100
%
1.1 4
Tregime
Reserved
60
10
500
Min
1.15 TempAmAux-
En
Reserved
5
-10
15
°C
1.16 TimecomAux
Reserved
20
10
120 Min
1.17 SetHeatECO
Reserved
18
14
28
°C
1.18
Set Cool ECO
Reserved
26
14
28
°C
1.19
BandPr
Reserved
2
1
10
°C