7
UNIT INSTALLATION
AWN / AWC CONSOLE UNIT
All units are to be installed against a wall as a floor console with support feet, or wall mounting as per dimensional
data. On the fan coil units equipped with support feet, we recommend you to fix the unit to the wall through the
both oblong holes located on the upper part of the unit chassis.
On the
AWC
model, to hang the unit to the wall, it is necessary to remove the cabinet.
Drill holes on the wall in accordance to the dimensions mentioned. Install the fixing screws (contractor supply).
Place the chassis unit over the fixing screws through the oblong holes and screw it directly to the wall.
Ensure adequate space for pipings and electrical connection, and check side of connection.
Sizes
Dimensions (mm)
A
B
C(*)
D
E
F
10 **
360
210
100
360
150
16
20
500
210
100
360
150
16
30
685
210
100
360
150
16
40
870
210
100
360
150
16
50
1055 210
100
360
150
16
60
1240 210
100
360
150
16
70
1055 208
100
365
157
18
80
1240 208
100
365
157
18
90
1425 208
100
365
157
18
* On units with front air intake, dimension C is not required.
** Not available on version AWC and AHC.
A
D
E
B
C
9
F
Ø16
Floor level
AHN / AHC CEILING UNIT
The
AHN
/
AHC
units are designed for ceiling mounting. Recommended fixing by M8 threaded rod or 8 mm
diameter anchor bolts (contractor supply).
When the
AHN
units are ducted at the inlet side, the controller return sensor must be located outside the fan
compartment in order to ensure its good operation.
For the
AHC
model with cabinet, it is necessary to remove the cabinet before installing it.
Follow instructions for cabinet removal.
Drill holes in the ceiling in accordance with dimensions mentioned. Install the fixing screws (contractor supply).
Place the chassis unit on the fixing points and screw it directly to the ceiling, or to the veritable support.
The fan coil unit should be pitched towards the drain side, to facilitate condensate evacuation.
Recommended fixing by M8 threaded rod with H8
hexagonal nut or 8 mm diameter anchor.
Summary of Contents for AHC 10
Page 2: ...II...
Page 19: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO...
Page 25: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO VII SE3530 10 90 CMV...
Page 26: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO VIII SE3531 10 90 CMV TBV...
Page 27: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO IX SE3532 10 90 CMV TBV1...
Page 28: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO X SE3533 10 90 CMV TBMV1...
Page 29: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XI SE3534 10 90 CMV TBV...
Page 30: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XII SE3535 10 90 AQUANET BMS BMS GND 12V RCW RCW...
Page 32: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XIV SE3537 10 90...