Boost Function
This function
is used when large amount of exhaust and fresh air is needed (at the time of
using kitchen/bathroom/wc, etc.) while ventilation is still going on. There are 2 boost functions
on controller. One of them is on control panel, the other one is on control board:
1.
“Boost” function is activated by pressing on Basic Panel and
on Pro Panel for
3 seconds. After unit runs at boost speed (maximum speed) and during boost time
(15 minutes) , it begins to run at the speed value that is set before boost function is
activated.
2.
There is one dry contact relay input and one 230V input on control board. If one of
these inputs is activated, unit begins to run at “boost” speed. When activated input is
passive again, unit begins to run at the speed value that is set before boost function is
activated.
Note 1:
Boost speed and boost time are changeable on Pro Panel.
Note 2:
During operating at boost function on Basic Panel, “high” (H), “medium” (M) and “low”
(L) speed leds are on at the same time.
BMS Function
BMS Function
makes the unit to be monitored on a central automation system.
1.
Dry contact outputs: There are 2 dry contact outputs. Working status and failure status
of the unit can be monitored.
2.
Dry contact input: Operation of the unit (on/off) can be done by dry contact input. When
this function is active, you can’t turn on/off the unit on control panel. To activate this
function, turn “dip switch 4” on.
Modbus Function
Modbus function
helps to monitor the unit and change all possible functions on a central
automation system.
Weekly Timer Function
Weekly timer
function is available on Pro Panel. Unit can be programmed to operate
automatically on certain periods of the week. Three options are available:
1.
5+0: Active for 5 weekdays, off on weekends
2.
5+1: Active on 5 weekdays and saturday, off on sunday
3.
5+2: Active for all days of the week