Airstream EXPERT PN110 User Manual Download Page 38

38

EXPERT PN110   rev.23

EXPERT PN110

Water meters —

 This menu shows the water 

meter consumptions that were measured 
every hour for the past 7 days. *

This history is 

accessible if the water meter is enabled (sec. 4.6.1).

Feeders —

 This menu shows the feeder run 

times that were measured every hour for the 
past 7 days.  *

This history  is accessible if feeders 

are enabled  (sec. 3).

Heaters —

 This menu shows the heater run 

times that were measured every hour for the 
past 7 days.  

Set Points —

 This menu shows the tempera-

ture set points that were measured every hour 
for the past 7 days.  

12.5.  Animal Age & Count

Animal age: 

Some parameters of the control-

ler can automatically change over time as 
the animals grow up (temperature curve for 
instance). For this reason, you must set the 
animal age as shown below.

Animal count 
(current count / mortality / culled / marketed) 

At the beginning of a batch, you must specify 
the initial number of animals. You will then 
be able to adjust the number of animals as 
changes occur (mortalities, culled, and mar-
keted animals).

ALL histories of the controller are reset 
when a new group starts (i.e., the animal 
age switches from 0ff to 1 day). 

The animal age automatically goes to 
0 day (Off) when entering in Clean Mode.

1. Select:

»

AGE & MORTALITY

Age & Mortality
Age:      10 days
New Dead 

0

Today's Dead 

0

Total Dead 

0

New Culled 

0

Today's Culled  0
Total Culled 

0

New Marketed 

0

Today's Market. 0
Current Size  500
Initial Size  500
Dead Yesterday  0
Cul. Yesterday  0
Dead 2 Days ago 0
Cul. 2 Days ago 0
Mark 2 Days ago 0
...

2.  Set the following parameters:

Age —

 Set the animal age. It can be adjusted 

from 0 days to 450 days. 

New Dead / Culled / Marketed —

 Enter the 

number mortalities, of culled animals and of 
marketed animals as it occurs. Once a value 
is posted, the parameter displayed on screen 
automatically goes back to “0”. The posted 
value is then removed from the current animal 
count and is logged in the respective history 
menus (Today & Total Died ,Culled or Mar-
keted history).

Today's Dead / Culled / Marketed —

 The 

controller displays the number of animals that 
have died, that have been culled and that have 
been marketed since the beginning of the day. 
These values cannot be changed.

Total Dead / Culled / Marketed —

 The control-

ler displays the number of animals that have 
died, that have been culled and that have been 
marketed since the beginning of the batch. 
These values cannot be changed.

Current Size —

 The current count is automati-

cally adjusted when the number of mortali-
ties, of culled animals and marketed animals 
changes.

Initial Size —

 Specify the initial number of 

animals in the room.

7-day History (Dead, Culled & Marketed) —

 The 

controller displays the daily number of dead, 
culled and marketed animals for the past 7 days. 
These values cannot be modi

fi

 ed.

11

EXPERT PN110   rev.23

EXPERT PN110

4.6.4.2.  Fan Stage Relays 

1. Select:

»

RELAY SETTINGS*

»

2. Fan Stages

»

Select the desired fan stage

*A password is required to access this menu (sec. 
4.2).

Stage 1 Relays:
Variable 1    On(1)
Variable 2   Var(1)
Relay 1      On (1)
Relay 2      Off(1)
Relay 3    Timer(1)
...

Relay 13    Off  (1)
Relay 14    Off  (1)
On Time      15sec
Off Time      0sec

2.  Put a check mark to identify the relay(s) 
used in the selected fan stage.

Variable Output Status —

2 variable outputs 

can be used to provide variable-speed ventila-

tion. If they are used, assign each of them to 

proper fan stages.

Var —

 The variable fan output is assigned 

to the fan stage and operates in variable 

mode: when the stage starts, the variable 

fan starts running at its minimum intensity. 

The fan intensity gradually increases as the 

room temperature increases.

On —

 The variable fan output is assigned 

to the fan stage and operates in on/off 

mode: the fan runs at 100% when the fan 

stage is on and stops when the stage is off.

Off —

 The variable output is not assigned.

If the last fan stage uses a variable output, 

the output must use the on/off operating 

mode. Do not set the operating mode of 

the last fan stage to the variable mode.

Relay Status —

 Put a check mark to assign 

a relay to the output or select 

"Timer"

 if load 

connected to the relay must run in timer 
mode.

Timer —

 If timer-based relays are assigned 

to some fan stages set the

 “On Time” 

and the

“O

  Time” 

of the timer.

4.6.4.3.  

Natural Curtain Relays 

Relays 7-8 and relays 13-14 have specially 
been designed to connect actuators. When 
actuators are connected to these relays, their 
open and close relays can never be activated 
at the same time. 

1. Select:

»

RELAY SETTINGS*

»

3. Curtain**

»

x. Curtain x Open

 or

»

x. Curtain x Close

*A password is required to access this menu (sec. 
4.2).
**This menu is accessible if the natural curtain is 
enabled (sec. 4.5).

Curtain Open Relay
0        1
12345678901234
     



2.  Put a check mark to identify the relay used 
to open or to close the curtain.

4.6.4.4. Inlet 

Relays

Relays 7-8 and relays 13-14 have specially 
been designed to connect actuators. When 
actuators are connected to these relays, their 
open and close relays can never be activated 
at the same time. 

1. Select:

»

RELAY SETTINGS*

»

4. Inlet**

»

1. Inlet Open

 or

»

2. Inlet Close

*A password is required to access this menu (sec. 
4.2).
* This menu is accessible if the inlet is enabled 
(sec. 4.5).

Inlet Open Relay
0        1
12345678901234



2.  Put a check mark to identify the relay used 
to open or to close the air inlet.

4.6.4.5.  Stir Fan Relays 

1. Select:

»

RELAY SETTINGS*

»

5. Stir Fan**

*A password is required to access this menu (sec. 4.2).
**This menu is accessible if the stir fan output is 
enabled (sec. 4.5).

Stir Fan Relays
0        1
12345678901234



2.  Put a check mark to identify the relay(s) 
used by the stir fan.

4.6.4.6.  Cooling Output Relays 

It is possible to assign the same relays to 
the cooling and soaking outputs. In this 
case, the relays switch whenever one of 
the two outputs is activated. 

1. Select:

»

RELAY SETTINGS*

»

6. Cooling**

*A password is required to access this menu (sec. 
4.2).
**This menu is accessible if the cooling output is 
enabled (sec. 4.5).

Cooling Relays
0        1
12345678901234



2.  Put a check mark to identify the relay(s) 
used by the cooling output.

Summary of Contents for EXPERT PN110

Page 1: ...M 890 00001 rev 23 REV 17 EXPERT PN110 Temperature controller User s Manual...

Page 2: ...used in a manner not specified by the manu facturer Every effort has been made to ensure that this manual is complete accurate and up to date The information contained in it is however subject to chan...

Page 3: ...6 2 3 0 10V Ventilation Outputs 19 6 3 Air Inlets 20 6 3 1 Principle of Operation 20 6 3 2 Settings 20 6 3 3 Actuator Reset 21 6 3 4 Inlet Calibration 22 6 3 5 Opening Compensations 22 6 3 6 Static P...

Page 4: ...he alarm system and keep this information for future reference Model EXPERT PN110 Serial number Date installed 45 EXPERT PN110 rev 23 EXPERT PN110 M Marketed animals 37 Measuring units 7 Memory card T...

Page 5: ...e sensors 7 days Outside temperature sensor 7 days Humidity sensor 7 days Static pressure sensor 7 days Daily water consumption 60 days Run time of each heater 75 days Run time of each feeder 75 days...

Page 6: ...r fan output is ON DE ICING PURGE Turns on when a curtain is operaing in de icing purge mode CLOCK OUTPUT 1 2 Turns on when clock output 1 2 is active 0 10V OUTPUT 1 2 Turns on when 0 10V output 1 2 i...

Page 7: ...notification appears fol low the steps outlined in section 4 1 Setting the Time Date Once the time and date have been adjusted the notification message disappears the sys tem clock is set and accurate...

Page 8: ...er opening stage is used to direct the airflow more efficiently during periods of warm weather Select Yes to enable the inlet over opening function or select No to disable it This parameter is accessi...

Page 9: ...Allow purge By default the controller automatically disables the curtain purge when using the interlock function Select Yes if you purge cycles to continue within that mode Use Cooling The controller...

Page 10: ...his rate can be adjusted from 1 to 100 liters or gallons per pulse 1 Select WATER 1 Water history Water Consumption Calib 1gal p Min 1 Max 100 2 Press the UP arrow key The water flow per pulse is disp...

Page 11: ...he desired fan stage A password is required to access this menu sec 4 2 Stage 1 Relays Variable 1 On 1 Variable 2 Var 1 Relay 1 On 1 Relay 2 Off 1 Relay 3 Timer 1 Relay 13 Off 1 Relay 14 Off 1 On Time...

Page 12: ...the down arrow key to scroll down the water consumption history Water Consumption Previous P and Last L 24 Hours 1 Select WATER 2 Last 48Hr Water Consumption L 24Hr 0Gal P 24Hr 0Gal Water Consumption...

Page 13: ...SetPoint Yes Night Min Vent Yes DayTime 6 00 NightTime 18 00 Transition 60min Min V1 10 Min V2 25 2 Set the following parameters Night Set Point Select Yes to use a differ ent target temperature at n...

Page 14: ...temperatures are not allowed 4 All ten steps must be specified If you don t need ten different steps repeat the last temperature for each unnecessary step Note that the temperature curve must be turne...

Page 15: ...ontroller will set off an alarm Last 24h Previous 24h x 100 Hi Alarm Previous 24h Case 2 If less water was consumed in the last 24 hours than in the 24 hours that precede the controller will determine...

Page 16: ...this cycle increases as the RH level increases ON OFF Output Status RH Heat Timer Time ON Time Cycle Time 2 High RH Comp on the Min Vent Speed The controller can compensate for a high hu midity level...

Page 17: ...atures of fan stages are defined with respect to the set point and with respect to each other This means that when one of these values is adjusted all the consecutive values are adjusted by the same a...

Page 18: ...110 rev 23 EXPERT PN110 intensity This parameter is accessible if the brooder mode is set to 0 10V in the installation menu see section 3 Min Output Set the minimum intensity of the brooder heater in...

Page 19: ...f the Hi fire option is used set this temperature separately for the regular and Hi Fire brooder steps 8 3 2 0 10V Brooder Heater The 0 10V brooder heater starts heating at minimum intensity when the...

Page 20: ...ir Inlet Min Vent Stage 1 ON T Stage 2 ON T Stage 3 Off T Stage 3 ON T Room T Last Stage starts Over opening bandwidth optional Inlet Opening Closed Min vent opening Stage 1 min opening Stage1 opening...

Page 21: ...if the over opening function is enabled in the Installation Setup see section 4 5 Total open Enter the exact time that is required to reach the actuator s maximum limit switch The controller will lim...

Page 22: ...e if the compensation value is set to 1 WC and the static pressure is 0 05 WC above the high static pressure set point the inlet will open of 5 to help decrease the static pressure in the building The...

Page 23: ...e output s start temperature The output is disabled when the temperature falls below its stop temperature see graph on the right 2 Stir fans in cold temperature conditions When the room temperature is...

Page 24: ...utside temperature to adjust the opening and clos ing times of the curtains As the outside temperature increases the curtains Opening ON Time is increased causing the curtains to open faster As the ou...

Page 25: ...utside temperature to adjust the opening and clos ing times of the curtains As the outside temperature increases the curtains Opening ON Time is increased causing the curtains to open faster As the ou...

Page 26: ...e output s start temperature The output is disabled when the temperature falls below its stop temperature see graph on the right 2 Stir fans in cold temperature conditions When the room temperature is...

Page 27: ...e if the compensation value is set to 1 WC and the static pressure is 0 05 WC above the high static pressure set point the inlet will open of 5 to help decrease the static pressure in the building The...

Page 28: ...if the over opening function is enabled in the Installation Setup see section 4 5 Total open Enter the exact time that is required to reach the actuator s maximum limit switch The controller will lim...

Page 29: ...ir Inlet Min Vent Stage 1 ON T Stage 2 ON T Stage 3 Off T Stage 3 ON T Room T Last Stage starts Over opening bandwidth optional Inlet Opening Closed Min vent opening Stage 1 min opening Stage1 opening...

Page 30: ...f the Hi fire option is used set this temperature separately for the regular and Hi Fire brooder steps 8 3 2 0 10V Brooder Heater The 0 10V brooder heater starts heating at minimum intensity when the...

Page 31: ...110 rev 23 EXPERT PN110 intensity This parameter is accessible if the brooder mode is set to 0 10V in the installation menu see section 3 Min Output Set the minimum intensity of the brooder heater in...

Page 32: ...atures of fan stages are defined with respect to the set point and with respect to each other This means that when one of these values is adjusted all the consecutive values are adjusted by the same a...

Page 33: ...this cycle increases as the RH level increases ON OFF Output Status RH Heat Timer Time ON Time Cycle Time 2 High RH Comp on the Min Vent Speed The controller can compensate for a high hu midity level...

Page 34: ...ontroller will set off an alarm Last 24h Previous 24h x 100 Hi Alarm Previous 24h Case 2 If less water was consumed in the last 24 hours than in the 24 hours that precede the controller will determine...

Page 35: ...temperatures are not allowed 4 All ten steps must be specified If you don t need ten different steps repeat the last temperature for each unnecessary step Note that the temperature curve must be turne...

Page 36: ...SetPoint Yes Night Min Vent Yes DayTime 6 00 NightTime 18 00 Transition 60min Min V1 10 Min V2 25 2 Set the following parameters Night Set Point Select Yes to use a differ ent target temperature at n...

Page 37: ...the down arrow key to scroll down the water consumption history Water Consumption Previous P and Last L 24 Hours 1 Select WATER 2 Last 48Hr Water Consumption L 24Hr 0Gal P 24Hr 0Gal Water Consumption...

Page 38: ...he desired fan stage A password is required to access this menu sec 4 2 Stage 1 Relays Variable 1 On 1 Variable 2 Var 1 Relay 1 On 1 Relay 2 Off 1 Relay 3 Timer 1 Relay 13 Off 1 Relay 14 Off 1 On Time...

Page 39: ...his rate can be adjusted from 1 to 100 liters or gallons per pulse 1 Select WATER 1 Water history Water Consumption Calib 1gal p Min 1 Max 100 2 Press the UP arrow key The water flow per pulse is disp...

Page 40: ...Allow purge By default the controller automatically disables the curtain purge when using the interlock function Select Yes if you purge cycles to continue within that mode Use Cooling The controller...

Page 41: ...er opening stage is used to direct the airflow more efficiently during periods of warm weather Select Yes to enable the inlet over opening function or select No to disable it This parameter is accessi...

Page 42: ...notification appears fol low the steps outlined in section 4 1 Setting the Time Date Once the time and date have been adjusted the notification message disappears the sys tem clock is set and accurate...

Page 43: ...r fan output is ON DE ICING PURGE Turns on when a curtain is operaing in de icing purge mode CLOCK OUTPUT 1 2 Turns on when clock output 1 2 is active 0 10V OUTPUT 1 2 Turns on when 0 10V output 1 2 i...

Page 44: ...e sensors 7 days Outside temperature sensor 7 days Humidity sensor 7 days Static pressure sensor 7 days Daily water consumption 60 days Run time of each heater 75 days Run time of each feeder 75 days...

Page 45: ...he alarm system and keep this information for future reference Model EXPERT PN110 Serial number Date installed 45 EXPERT PN110 rev 23 EXPERT PN110 M Marketed animals 37 Measuring units 7 Memory card T...

Page 46: ...6 2 3 0 10V Ventilation Outputs 19 6 3 Air Inlets 20 6 3 1 Principle of Operation 20 6 3 2 Settings 20 6 3 3 Actuator Reset 21 6 3 4 Inlet Calibration 22 6 3 5 Opening Compensations 22 6 3 6 Static P...

Page 47: ...used in a manner not specified by the manu facturer Every effort has been made to ensure that this manual is complete accurate and up to date The information contained in it is however subject to chan...

Page 48: ...M 890 00001 rev 23 REV 17 EXPERT PN110 Temperature controller User s Manual...

Reviews: