background image

30

EXPERT PN110   rev.23

EXPERT PN110

8.3. Brooder 

Heater

The controller can use a relay or it can use 
its second 0-10V output to control a brooder 
heater. Refer to the installation options in 
section 3 to enable the proper type of brooder 
output (relay or 0-10V).

Operating Temperature:

To operate the brooder heater, the control-
ler refers to the average reading of the 
temperature probes assigned to the output 
(see sec. 4.6.3). In addition, the operating 
temperatures of the brooder heater can ei-
ther be de

fi

 ned as absolute values or they 

can be related to the set point, which means 
they are automatically adjusted when the set 
point changes.  Refer to the installation menu 
in section 3 to determine if the operating 
temperatures must follow the temperature 
set point or not.

Brooder’s Hi Fire:  

With the Brooder Hi Fire 

option, the controller controls the brooder 
output in two different ways, just as if there 
were two brooder outputs (regular output 
and Hi-Fire output). The regular brooder 
output and the Hi-Fire output each uses its 
particular relay assignement and Start/Stop 
temperatures. Refer to section 3 to activate 
the brooder’s Hi 

fi

 re option. 

Closing the Curtains when Brooder Heater 
is ON:

The controller can automatically close the 
natural ventilation curtains when the brooder 
heater is on. Enable the 

"Interlock"

 option in 

section 3 to activate this function. 

Brooder Heater Curve:

The controller can adjust the start tempera-
ture of the brooder over time with a curve. 
Refer to section 8.3.3 for further information 
on the brooder curve.

8.3.1.  On/Off Brooder Heater

The on/off brooder heater turns on when the 
temperature of its probe(s) falls to the Start 
Temperature; it turns off when temperature 
increases and reaches the Stop Temperature. 

Operating Diagram 

of a Breeding Output

Brooder 

Output

Brooder

Hi Fire 

ON

Brooder

ON

Brooder

Hi Fire 

OFF

Brooder

OFF

Brooder 

Hi Stop 

Brooder 

Hi Start 

Brooder

Start

 T°

Brooder

Stop

 T°

T° of 

brooder

probes

1. Select:

»

START / STOP TEMPS

»

12. Brooders*

»

1. Settings

*  This menu is accessible if the brooder output is 

enabled (see sec. 3). 

Brooder Settings
Start Temp. 

78.0

Stop Temp. 

80.0

Hi Start Temp.  81.0
Hi Stop Temp.  83.0

2.  Set the following parameters: 

Start temperature —

 Set the temperature 

below which the brooder starts. If the Hi 

fi

 re 

option is used, set this temperature separately 
for the regular and Hi Fire brooder steps. *

This 

parameter cannot be modi

fi

 ed if the brooder curve is 

on. See  to section 8.3.3 to turn o

  this curve. 

Stop temperature —

 Set the temperature at 

which the brooder  stops. If the Hi 

fi

 re option 

is used, set this temperature separately for 
the regular and Hi Fire brooder steps.

8.3.2.  0-10V Brooder Heater

The 0-10V brooder heater starts heating 
at minimum intensity when the average 
temperature of its probes falls to the Start 
Temperature. It then increases in intensity 
as the temperature decreases and reaches its 
maximum heat intensity when the tempera-
ture gets lower than the Start Temperature 
— Differential. The brooder heater 

fi

 nally 

turns off when the temperature increases and 
reaches the Stop Temperature of the output.

0-10V Brooder 

Heater

Brooder Heat 

Intensity (%)

T° of 

brooder

probes

Differential

Off

Max

output

Min

output

Start

Stop

1. Select:

»

START / STOP TEMPS

»

12. Brooders*

»

1. Settings

*  This menu is accessible if the brooder output is 

enabled (see sec. 3). 

Brooder Settings
Start Temp.: 78.0
Stop Temp.:  80.0
Differential  2.0
Min Output    30
Max Output   100

2.  Set the following parameters: 

Start Temp. —

 Set the temperature below 

which the brooder heater starts running at 
minimum intensity. *

This parameter cannot be 

modi

fi

 ed if the brooder curve is on. Refer to section 

8.3.3 to turn o

  this curve. 

Stop Temp. —

 Set the temperature over which 

the brooder heater turns off.

Differential —

 Select the number of degrees 

below the Start Temperature at which the 
the brooder heater reaches its maximum 

19

EXPERT PN110   rev.23

EXPERT PN110

6.2.3.  0-10V Ventilation Outputs 

The controller has two 0-10V outputs that can 
either be used to control heaters or fans.  To 
operate these outputs, the controller refers 
to the average temperature reading of their 
assigned temperature probes (sec. 4.7.3). 

This section explains how 0-10V ventilation 
outputs work. 

The 0-10V ventilation outputs start at their 
minimum intensity when the average tem-
perature of their probes reaches the start 
temperature. They increase in intensity as 
the temperature increases; 0-10V outputs 
reach their maximum intensity when the tem-
perature rises to the 

“Maximum Temperature”

parameter setting.

Max

Min

OFF

Intensity

0-10V Ventilation 

Output

Avg T° 

of 0-10V 

output 

probes

Start T°

Max 

Stop T°

1. Select:

»

START / STOP TEMPS

»

5. 0-10V Outputs

»

Select the desired 0-10V Output

* This menu is accessible if a 0-10V output is enabled 
(sec. 4.5). 

Start Temp 75.0°F
Min:   10 Max:  100
Max Output at: 72.5
Stop at:       70.0

2.  Set the following parameters:

Start temperature —

 Set the start tempera-

ture to the desired value. 

Minimum & max speeds —

 Set the minimum 

and maximum speeds of the 0-10V output. 
The maximum speed must be greater than 
the minimum speed.

Maximum output at —

 Set the temperature at 

which the output reaches its maximum speed 
(this parameter must be set to a greater value 
than the start temperature). 

Stop at —

 This is the temperature below 

which the 0-10V output stops.

Summary of Contents for EXPERT PN110

Page 1: ...M 890 00001 rev 23 REV 17 EXPERT PN110 Temperature controller User s Manual...

Page 2: ...used in a manner not specified by the manu facturer Every effort has been made to ensure that this manual is complete accurate and up to date The information contained in it is however subject to chan...

Page 3: ...6 2 3 0 10V Ventilation Outputs 19 6 3 Air Inlets 20 6 3 1 Principle of Operation 20 6 3 2 Settings 20 6 3 3 Actuator Reset 21 6 3 4 Inlet Calibration 22 6 3 5 Opening Compensations 22 6 3 6 Static P...

Page 4: ...he alarm system and keep this information for future reference Model EXPERT PN110 Serial number Date installed 45 EXPERT PN110 rev 23 EXPERT PN110 M Marketed animals 37 Measuring units 7 Memory card T...

Page 5: ...e sensors 7 days Outside temperature sensor 7 days Humidity sensor 7 days Static pressure sensor 7 days Daily water consumption 60 days Run time of each heater 75 days Run time of each feeder 75 days...

Page 6: ...r fan output is ON DE ICING PURGE Turns on when a curtain is operaing in de icing purge mode CLOCK OUTPUT 1 2 Turns on when clock output 1 2 is active 0 10V OUTPUT 1 2 Turns on when 0 10V output 1 2 i...

Page 7: ...notification appears fol low the steps outlined in section 4 1 Setting the Time Date Once the time and date have been adjusted the notification message disappears the sys tem clock is set and accurate...

Page 8: ...er opening stage is used to direct the airflow more efficiently during periods of warm weather Select Yes to enable the inlet over opening function or select No to disable it This parameter is accessi...

Page 9: ...Allow purge By default the controller automatically disables the curtain purge when using the interlock function Select Yes if you purge cycles to continue within that mode Use Cooling The controller...

Page 10: ...his rate can be adjusted from 1 to 100 liters or gallons per pulse 1 Select WATER 1 Water history Water Consumption Calib 1gal p Min 1 Max 100 2 Press the UP arrow key The water flow per pulse is disp...

Page 11: ...he desired fan stage A password is required to access this menu sec 4 2 Stage 1 Relays Variable 1 On 1 Variable 2 Var 1 Relay 1 On 1 Relay 2 Off 1 Relay 3 Timer 1 Relay 13 Off 1 Relay 14 Off 1 On Time...

Page 12: ...the down arrow key to scroll down the water consumption history Water Consumption Previous P and Last L 24 Hours 1 Select WATER 2 Last 48Hr Water Consumption L 24Hr 0Gal P 24Hr 0Gal Water Consumption...

Page 13: ...SetPoint Yes Night Min Vent Yes DayTime 6 00 NightTime 18 00 Transition 60min Min V1 10 Min V2 25 2 Set the following parameters Night Set Point Select Yes to use a differ ent target temperature at n...

Page 14: ...temperatures are not allowed 4 All ten steps must be specified If you don t need ten different steps repeat the last temperature for each unnecessary step Note that the temperature curve must be turne...

Page 15: ...ontroller will set off an alarm Last 24h Previous 24h x 100 Hi Alarm Previous 24h Case 2 If less water was consumed in the last 24 hours than in the 24 hours that precede the controller will determine...

Page 16: ...this cycle increases as the RH level increases ON OFF Output Status RH Heat Timer Time ON Time Cycle Time 2 High RH Comp on the Min Vent Speed The controller can compensate for a high hu midity level...

Page 17: ...atures of fan stages are defined with respect to the set point and with respect to each other This means that when one of these values is adjusted all the consecutive values are adjusted by the same a...

Page 18: ...110 rev 23 EXPERT PN110 intensity This parameter is accessible if the brooder mode is set to 0 10V in the installation menu see section 3 Min Output Set the minimum intensity of the brooder heater in...

Page 19: ...f the Hi fire option is used set this temperature separately for the regular and Hi Fire brooder steps 8 3 2 0 10V Brooder Heater The 0 10V brooder heater starts heating at minimum intensity when the...

Page 20: ...ir Inlet Min Vent Stage 1 ON T Stage 2 ON T Stage 3 Off T Stage 3 ON T Room T Last Stage starts Over opening bandwidth optional Inlet Opening Closed Min vent opening Stage 1 min opening Stage1 opening...

Page 21: ...if the over opening function is enabled in the Installation Setup see section 4 5 Total open Enter the exact time that is required to reach the actuator s maximum limit switch The controller will lim...

Page 22: ...e if the compensation value is set to 1 WC and the static pressure is 0 05 WC above the high static pressure set point the inlet will open of 5 to help decrease the static pressure in the building The...

Page 23: ...e output s start temperature The output is disabled when the temperature falls below its stop temperature see graph on the right 2 Stir fans in cold temperature conditions When the room temperature is...

Page 24: ...utside temperature to adjust the opening and clos ing times of the curtains As the outside temperature increases the curtains Opening ON Time is increased causing the curtains to open faster As the ou...

Page 25: ...utside temperature to adjust the opening and clos ing times of the curtains As the outside temperature increases the curtains Opening ON Time is increased causing the curtains to open faster As the ou...

Page 26: ...e output s start temperature The output is disabled when the temperature falls below its stop temperature see graph on the right 2 Stir fans in cold temperature conditions When the room temperature is...

Page 27: ...e if the compensation value is set to 1 WC and the static pressure is 0 05 WC above the high static pressure set point the inlet will open of 5 to help decrease the static pressure in the building The...

Page 28: ...if the over opening function is enabled in the Installation Setup see section 4 5 Total open Enter the exact time that is required to reach the actuator s maximum limit switch The controller will lim...

Page 29: ...ir Inlet Min Vent Stage 1 ON T Stage 2 ON T Stage 3 Off T Stage 3 ON T Room T Last Stage starts Over opening bandwidth optional Inlet Opening Closed Min vent opening Stage 1 min opening Stage1 opening...

Page 30: ...f the Hi fire option is used set this temperature separately for the regular and Hi Fire brooder steps 8 3 2 0 10V Brooder Heater The 0 10V brooder heater starts heating at minimum intensity when the...

Page 31: ...110 rev 23 EXPERT PN110 intensity This parameter is accessible if the brooder mode is set to 0 10V in the installation menu see section 3 Min Output Set the minimum intensity of the brooder heater in...

Page 32: ...atures of fan stages are defined with respect to the set point and with respect to each other This means that when one of these values is adjusted all the consecutive values are adjusted by the same a...

Page 33: ...this cycle increases as the RH level increases ON OFF Output Status RH Heat Timer Time ON Time Cycle Time 2 High RH Comp on the Min Vent Speed The controller can compensate for a high hu midity level...

Page 34: ...ontroller will set off an alarm Last 24h Previous 24h x 100 Hi Alarm Previous 24h Case 2 If less water was consumed in the last 24 hours than in the 24 hours that precede the controller will determine...

Page 35: ...temperatures are not allowed 4 All ten steps must be specified If you don t need ten different steps repeat the last temperature for each unnecessary step Note that the temperature curve must be turne...

Page 36: ...SetPoint Yes Night Min Vent Yes DayTime 6 00 NightTime 18 00 Transition 60min Min V1 10 Min V2 25 2 Set the following parameters Night Set Point Select Yes to use a differ ent target temperature at n...

Page 37: ...the down arrow key to scroll down the water consumption history Water Consumption Previous P and Last L 24 Hours 1 Select WATER 2 Last 48Hr Water Consumption L 24Hr 0Gal P 24Hr 0Gal Water Consumption...

Page 38: ...he desired fan stage A password is required to access this menu sec 4 2 Stage 1 Relays Variable 1 On 1 Variable 2 Var 1 Relay 1 On 1 Relay 2 Off 1 Relay 3 Timer 1 Relay 13 Off 1 Relay 14 Off 1 On Time...

Page 39: ...his rate can be adjusted from 1 to 100 liters or gallons per pulse 1 Select WATER 1 Water history Water Consumption Calib 1gal p Min 1 Max 100 2 Press the UP arrow key The water flow per pulse is disp...

Page 40: ...Allow purge By default the controller automatically disables the curtain purge when using the interlock function Select Yes if you purge cycles to continue within that mode Use Cooling The controller...

Page 41: ...er opening stage is used to direct the airflow more efficiently during periods of warm weather Select Yes to enable the inlet over opening function or select No to disable it This parameter is accessi...

Page 42: ...notification appears fol low the steps outlined in section 4 1 Setting the Time Date Once the time and date have been adjusted the notification message disappears the sys tem clock is set and accurate...

Page 43: ...r fan output is ON DE ICING PURGE Turns on when a curtain is operaing in de icing purge mode CLOCK OUTPUT 1 2 Turns on when clock output 1 2 is active 0 10V OUTPUT 1 2 Turns on when 0 10V output 1 2 i...

Page 44: ...e sensors 7 days Outside temperature sensor 7 days Humidity sensor 7 days Static pressure sensor 7 days Daily water consumption 60 days Run time of each heater 75 days Run time of each feeder 75 days...

Page 45: ...he alarm system and keep this information for future reference Model EXPERT PN110 Serial number Date installed 45 EXPERT PN110 rev 23 EXPERT PN110 M Marketed animals 37 Measuring units 7 Memory card T...

Page 46: ...6 2 3 0 10V Ventilation Outputs 19 6 3 Air Inlets 20 6 3 1 Principle of Operation 20 6 3 2 Settings 20 6 3 3 Actuator Reset 21 6 3 4 Inlet Calibration 22 6 3 5 Opening Compensations 22 6 3 6 Static P...

Page 47: ...used in a manner not specified by the manu facturer Every effort has been made to ensure that this manual is complete accurate and up to date The information contained in it is however subject to chan...

Page 48: ...M 890 00001 rev 23 REV 17 EXPERT PN110 Temperature controller User s Manual...

Reviews: