Airstream EXPERT PN110 User Manual Download Page 27

22

EXPERT PN110   rev.23

EXPERT PN110

6.3.4. Inlet Calibration

[For potentiometer-based inlets only]

If the inlet uses a potentiometer, the actuator 
of the inlet must be calibrated. This calibra-
tion tells the controller what are the minimum 
and maximum positions of the actuator: 

Minimum calibrated position = opening of 0%
Max. calibrated position = opening of 100% 

1. Select:

»

INLET

»

  1. Stage Opening*

* This menu is accessible if the inlet is enabled 
(section 4.5).

Inlet 
Status :      Auto
Position     

 0%

Calibration?    Yes
Minimum      

   Save

Maximum        

  Set

2. Minimum — 

To calibrate the minimum 

position, use the 

“Close” 

switch to close the 

inlet to its minimum position. Once the inlet 
is closed, set the manual control switch to 

“O

 ”

 to stop the actuator. 

*This parameter is 

accessible if the inlet uses a potentiometer.

Now that the actuator is closed, answer 

“Yes”

to the 

“Minimum” 

parameter on screen. Once 

the 

“Yes”

 answer is posted, the controller 

shows the word 

"Save"

 for 5 seconds and then 

displays 

"No"

 again; the minimum position has  

now been saved.

3.  Save maximum posi-
tion? — 

To calibrate the 

maximum position, use 
the 

“Open” 

manual control 

switch to fully open the inlet. Once the maxi-
mum inlet opening is reached, set the manual 
control switch to 

“O

 ”

 to stop the actuator. 

Now that the actuator is closed, answer 

“Yes”

to the 

“Minimum” 

parameter on screen. Once 

the 

“Yes”

 answer is posted, the controller 

shows the word 

"Save"

 for 5 seconds and then 

displays 

"No"

 again; the maximum position 

has now been saved.

4.  Once the calibration is 

completed, set the manual control switch 
back to the 

“Auto”

 position to enable the au-

tomatic control of the inlet.

For best results, make sure at least 
12 inches (30 cm) separates the minimum 
actuator’s position from its maximum 
position.

6.3.5. Opening Compensations

• Temperature Compensation:

The inlet temperature compensation is ex-
pressed as a percentage per degree difference 
between the average controller temperature 
and the average reading of the probes as-
signed to the inlet. It determines by how much 
the inlet must open or close to help reduce 
the temperature differences in the building. 
For each degree above or below the average 
temperature, the inlet will open or close us-
ing the compensation value assigned by the 
user. For example, if the compensation value 
is set to 2%/°F and the inlet's probes read 
3°F above the average controller tempera-
ture, the inlet will open 6% to help decrease 
the temperature in that zone. The maximum 
temperature compensation value is 10%.

• Static Pressure Compensation

The  static  pressure  compensation  is  ex-
pressed as a percentage per 0.01inch of water 
(%/0.01"WC).  It  determines  by  how  much 
the inlet must open or close to help reduce 
or enhance the static pressure in the building 
according to set points. For each .01"WC 
above the high static pressure set point or 
below the low static pressure set point, the 
inlet will open or close using the compensa-
tion value assigned by the user. For example, 
if the compensation value is set to 1%/"WC 
and the static pressure is 0.05"WC above 
the high static pressure set point, the inlet 
will open of 5% to help decrease the static 
pressure in the building. The maximum static 
pressure compensation value is 10%.

1. Select:

»

INLET

»

2. Compensation*

»

  1. Temp & Static

* This menu is accessible if the inlet is enabled 
(section 4.5).

Inlet Compensation
Temp Comp     5%/°F
Stat Press    3%/WC

2.  Set the following parameters:

Temp Comp —

 Set the temperature compen-

sation to the desired value.

Stat Press —

 Set the static pressure compen-

sation to the desired value. *

This parameter 

is  accessible  if  the  static  pressure  sensor  is  used 
(sec. 4.7.1).

• Static Pressure Comp. Stages

The procedure below shows how to select 
the fan stages on which the static pressure 
compensation will be applied. 

1. Select:

»

INLET

»

2. Compensation*

»

  2. Static Stages**

* This menu is accessible if the inlet is enabled 
(section 4.5).
** This menu is accessible if the static pressure sen-
sor is enabled (section 4.7.1).

Comp. Static Stages                   

12345678

2.  Put check marks to identify the fan 
stage(s) on which the static pressure com-
pensation is applied.

27

EXPERT PN110   rev.23

EXPERT PN110

6.6. Misting 

Output

To operate the misting output, the controller 
refers to the average reading of the tempera-
ture probes assigned to the output.

The controller can control one misting out-
put. When the temperature reaches the start 
temperature of the output, mist units are 
activated and run in timer mode according to 
their minimum timer (Min On Time & Min Off 
Time). Then, as temperature rises, a gradual 
transition is made from the minimum timer 
towards the maximum timer (Max On Time  
& Max Off Time). The second mist timer is 
fully used when the temperature reaches the 
Maximum Temperature  parameter setting. 
The misting output is disabled when the 
temperature falls below a user-de

fi

 ned value. 

It can also stop when humidity levels are too 
high (see RH Compensation in chapter 10).

Max On 

Time

Min On 

Time

OFF

Mist 

Timer

Misting

Output

ON T°

Max T°

OFF T°

1. Select:

»

START / STOP TEMPS

»

7. Cooling*

*This parameter is acessible if the cooling output is 
enabled (see sec. 4.5).

Cooling
On Temp         85.0
Off Temp        83.0
Min.OnTime     15sec
Off Time      900sec
Max.Temperature 87.0
Max.OnTime    180sec

2.   Set the following parameters:

On Temp. / Off Temp —

 Select the tempera-

ture at which the cooling output starts and 
stops.

Min/Max On Time —

 Set the minimum and 

maximum On Time of the cooling timer. 

Max Temperature —

 Set the temperature at 

which the cooling output uses its maximum 
timer settings. The maximum temperature 
must be at least 0.5°F (0.3°C) greater than 
the ON TEMP.

6.7. Soaking

The soaking output is used to clean the room 
when it is empty. This output runs in timer 
mode when the controller is in clean mode. 

1. Select:

»

START / STOP TEMPS

»

9. Soaking*

*This parameter is acessible if the soaking output is 
enabled (see sec. 4.5).

On Time:     60sec
Off Time:    60min
#Soaking Cycle: None

2.  Set the following parameters:

On/Off Time — 

Set the timer used by the 

soaking output. 

# Soaking Cycles — 

Select how many soak-

ing cycles must be performed from the mo-
ment the controller enters in clean mode (1 
to 100 cycles). 

Summary of Contents for EXPERT PN110

Page 1: ...M 890 00001 rev 23 REV 17 EXPERT PN110 Temperature controller User s Manual...

Page 2: ...used in a manner not specified by the manu facturer Every effort has been made to ensure that this manual is complete accurate and up to date The information contained in it is however subject to chan...

Page 3: ...6 2 3 0 10V Ventilation Outputs 19 6 3 Air Inlets 20 6 3 1 Principle of Operation 20 6 3 2 Settings 20 6 3 3 Actuator Reset 21 6 3 4 Inlet Calibration 22 6 3 5 Opening Compensations 22 6 3 6 Static P...

Page 4: ...he alarm system and keep this information for future reference Model EXPERT PN110 Serial number Date installed 45 EXPERT PN110 rev 23 EXPERT PN110 M Marketed animals 37 Measuring units 7 Memory card T...

Page 5: ...e sensors 7 days Outside temperature sensor 7 days Humidity sensor 7 days Static pressure sensor 7 days Daily water consumption 60 days Run time of each heater 75 days Run time of each feeder 75 days...

Page 6: ...r fan output is ON DE ICING PURGE Turns on when a curtain is operaing in de icing purge mode CLOCK OUTPUT 1 2 Turns on when clock output 1 2 is active 0 10V OUTPUT 1 2 Turns on when 0 10V output 1 2 i...

Page 7: ...notification appears fol low the steps outlined in section 4 1 Setting the Time Date Once the time and date have been adjusted the notification message disappears the sys tem clock is set and accurate...

Page 8: ...er opening stage is used to direct the airflow more efficiently during periods of warm weather Select Yes to enable the inlet over opening function or select No to disable it This parameter is accessi...

Page 9: ...Allow purge By default the controller automatically disables the curtain purge when using the interlock function Select Yes if you purge cycles to continue within that mode Use Cooling The controller...

Page 10: ...his rate can be adjusted from 1 to 100 liters or gallons per pulse 1 Select WATER 1 Water history Water Consumption Calib 1gal p Min 1 Max 100 2 Press the UP arrow key The water flow per pulse is disp...

Page 11: ...he desired fan stage A password is required to access this menu sec 4 2 Stage 1 Relays Variable 1 On 1 Variable 2 Var 1 Relay 1 On 1 Relay 2 Off 1 Relay 3 Timer 1 Relay 13 Off 1 Relay 14 Off 1 On Time...

Page 12: ...the down arrow key to scroll down the water consumption history Water Consumption Previous P and Last L 24 Hours 1 Select WATER 2 Last 48Hr Water Consumption L 24Hr 0Gal P 24Hr 0Gal Water Consumption...

Page 13: ...SetPoint Yes Night Min Vent Yes DayTime 6 00 NightTime 18 00 Transition 60min Min V1 10 Min V2 25 2 Set the following parameters Night Set Point Select Yes to use a differ ent target temperature at n...

Page 14: ...temperatures are not allowed 4 All ten steps must be specified If you don t need ten different steps repeat the last temperature for each unnecessary step Note that the temperature curve must be turne...

Page 15: ...ontroller will set off an alarm Last 24h Previous 24h x 100 Hi Alarm Previous 24h Case 2 If less water was consumed in the last 24 hours than in the 24 hours that precede the controller will determine...

Page 16: ...this cycle increases as the RH level increases ON OFF Output Status RH Heat Timer Time ON Time Cycle Time 2 High RH Comp on the Min Vent Speed The controller can compensate for a high hu midity level...

Page 17: ...atures of fan stages are defined with respect to the set point and with respect to each other This means that when one of these values is adjusted all the consecutive values are adjusted by the same a...

Page 18: ...110 rev 23 EXPERT PN110 intensity This parameter is accessible if the brooder mode is set to 0 10V in the installation menu see section 3 Min Output Set the minimum intensity of the brooder heater in...

Page 19: ...f the Hi fire option is used set this temperature separately for the regular and Hi Fire brooder steps 8 3 2 0 10V Brooder Heater The 0 10V brooder heater starts heating at minimum intensity when the...

Page 20: ...ir Inlet Min Vent Stage 1 ON T Stage 2 ON T Stage 3 Off T Stage 3 ON T Room T Last Stage starts Over opening bandwidth optional Inlet Opening Closed Min vent opening Stage 1 min opening Stage1 opening...

Page 21: ...if the over opening function is enabled in the Installation Setup see section 4 5 Total open Enter the exact time that is required to reach the actuator s maximum limit switch The controller will lim...

Page 22: ...e if the compensation value is set to 1 WC and the static pressure is 0 05 WC above the high static pressure set point the inlet will open of 5 to help decrease the static pressure in the building The...

Page 23: ...e output s start temperature The output is disabled when the temperature falls below its stop temperature see graph on the right 2 Stir fans in cold temperature conditions When the room temperature is...

Page 24: ...utside temperature to adjust the opening and clos ing times of the curtains As the outside temperature increases the curtains Opening ON Time is increased causing the curtains to open faster As the ou...

Page 25: ...utside temperature to adjust the opening and clos ing times of the curtains As the outside temperature increases the curtains Opening ON Time is increased causing the curtains to open faster As the ou...

Page 26: ...e output s start temperature The output is disabled when the temperature falls below its stop temperature see graph on the right 2 Stir fans in cold temperature conditions When the room temperature is...

Page 27: ...e if the compensation value is set to 1 WC and the static pressure is 0 05 WC above the high static pressure set point the inlet will open of 5 to help decrease the static pressure in the building The...

Page 28: ...if the over opening function is enabled in the Installation Setup see section 4 5 Total open Enter the exact time that is required to reach the actuator s maximum limit switch The controller will lim...

Page 29: ...ir Inlet Min Vent Stage 1 ON T Stage 2 ON T Stage 3 Off T Stage 3 ON T Room T Last Stage starts Over opening bandwidth optional Inlet Opening Closed Min vent opening Stage 1 min opening Stage1 opening...

Page 30: ...f the Hi fire option is used set this temperature separately for the regular and Hi Fire brooder steps 8 3 2 0 10V Brooder Heater The 0 10V brooder heater starts heating at minimum intensity when the...

Page 31: ...110 rev 23 EXPERT PN110 intensity This parameter is accessible if the brooder mode is set to 0 10V in the installation menu see section 3 Min Output Set the minimum intensity of the brooder heater in...

Page 32: ...atures of fan stages are defined with respect to the set point and with respect to each other This means that when one of these values is adjusted all the consecutive values are adjusted by the same a...

Page 33: ...this cycle increases as the RH level increases ON OFF Output Status RH Heat Timer Time ON Time Cycle Time 2 High RH Comp on the Min Vent Speed The controller can compensate for a high hu midity level...

Page 34: ...ontroller will set off an alarm Last 24h Previous 24h x 100 Hi Alarm Previous 24h Case 2 If less water was consumed in the last 24 hours than in the 24 hours that precede the controller will determine...

Page 35: ...temperatures are not allowed 4 All ten steps must be specified If you don t need ten different steps repeat the last temperature for each unnecessary step Note that the temperature curve must be turne...

Page 36: ...SetPoint Yes Night Min Vent Yes DayTime 6 00 NightTime 18 00 Transition 60min Min V1 10 Min V2 25 2 Set the following parameters Night Set Point Select Yes to use a differ ent target temperature at n...

Page 37: ...the down arrow key to scroll down the water consumption history Water Consumption Previous P and Last L 24 Hours 1 Select WATER 2 Last 48Hr Water Consumption L 24Hr 0Gal P 24Hr 0Gal Water Consumption...

Page 38: ...he desired fan stage A password is required to access this menu sec 4 2 Stage 1 Relays Variable 1 On 1 Variable 2 Var 1 Relay 1 On 1 Relay 2 Off 1 Relay 3 Timer 1 Relay 13 Off 1 Relay 14 Off 1 On Time...

Page 39: ...his rate can be adjusted from 1 to 100 liters or gallons per pulse 1 Select WATER 1 Water history Water Consumption Calib 1gal p Min 1 Max 100 2 Press the UP arrow key The water flow per pulse is disp...

Page 40: ...Allow purge By default the controller automatically disables the curtain purge when using the interlock function Select Yes if you purge cycles to continue within that mode Use Cooling The controller...

Page 41: ...er opening stage is used to direct the airflow more efficiently during periods of warm weather Select Yes to enable the inlet over opening function or select No to disable it This parameter is accessi...

Page 42: ...notification appears fol low the steps outlined in section 4 1 Setting the Time Date Once the time and date have been adjusted the notification message disappears the sys tem clock is set and accurate...

Page 43: ...r fan output is ON DE ICING PURGE Turns on when a curtain is operaing in de icing purge mode CLOCK OUTPUT 1 2 Turns on when clock output 1 2 is active 0 10V OUTPUT 1 2 Turns on when 0 10V output 1 2 i...

Page 44: ...e sensors 7 days Outside temperature sensor 7 days Humidity sensor 7 days Static pressure sensor 7 days Daily water consumption 60 days Run time of each heater 75 days Run time of each feeder 75 days...

Page 45: ...he alarm system and keep this information for future reference Model EXPERT PN110 Serial number Date installed 45 EXPERT PN110 rev 23 EXPERT PN110 M Marketed animals 37 Measuring units 7 Memory card T...

Page 46: ...6 2 3 0 10V Ventilation Outputs 19 6 3 Air Inlets 20 6 3 1 Principle of Operation 20 6 3 2 Settings 20 6 3 3 Actuator Reset 21 6 3 4 Inlet Calibration 22 6 3 5 Opening Compensations 22 6 3 6 Static P...

Page 47: ...used in a manner not specified by the manu facturer Every effort has been made to ensure that this manual is complete accurate and up to date The information contained in it is however subject to chan...

Page 48: ...M 890 00001 rev 23 REV 17 EXPERT PN110 Temperature controller User s Manual...

Reviews: