3.3.4. Forming the drain hose and pipe

 

CAUTION

  In order to align the drain hose and drain cap, be sure to insert securely and vertically. 

Incline insertion will cause water leakage.

  When inserting, be sure not to attach any material besides water. If any other material 

is attached, it will cause deterioration and water leakage.

  After removing drain hose, be sure not to forget mounting drain cap.

  Be sure to 

fi

 x the drain hose with tape to the bottom of piping.

[Rear piping, Right piping, Bottom piping]

(1)  Install the indoor unit piping in the direction of the wall hole and bind the drain hose 

and pipe together with vinyl tape.

Bottom piping

Right piping

Bind with vinyl tape

Pipe (top) Rear piping

Indoor unit drain hose (bottom)

(2)  Install the piping so that the drain hose is at the bottom.

(3)  Wrap the pipes of the indoor unit that are visible from the outside with decorative 

tape.

[For Left rear piping, Left piping]

(1)  Interchange the drain cap, insulation and the drain hose.

Indoor unit 
drain hose

For left outlet piping, cut off the 
piping outlet cutting groove with 
a hacksaw.

Remove the drain cap by pulling 
at the projection at the end of the 
cap with pliers, etc.
And remove the insulation.

Drain cap

Insulation

(2)  Align the marks on the wall hook bracket and shape the connection pipe.

Connection pipe 
(Liquid pipe)

Bend (R70) with a 
pipe bender

Connection pipe (Gas pipe)

Align the marks.

(3)  Bend the connection piping at the bend radius of 70 mm or more and install no more 

than 35 mm from the wall.

3.3. Installing the unit

 

WARNING

  Install the air conditioner in a location which can withstand a load of at least 5 times the 

weight of the main unit and which will not amplify sound or vibration. If the installation 
location is not strong enough, the indoor unit may fall and cause injuries.

  If the job is done with the panel frame only, there is a risk that the unit will come loose. 

Please take care.

3.3.1. Determining the piping direction

The piping can be connected in the 5 directions indicated by 

1

2

3

4

, and 

5

 in (Fig. A).

When the piping is connected in direction 

2

 or 

5

, cut along the piping groove in the 

side of the front cover with a hacksaw.
When connecting the piping in direction 

3

, cut a notch in the thin wall at the front bot-

tom of the front cover.

Fig. A

5

 Left outlet

(Rear)

1

 Rear outlet

2

 Right outlet

3

 Bottom outlet

4

 Left rear outlet

3.3.2. Installing the wall hook bracket

 

CAUTION

  Install the wall hook bracket level, both horizontally and vertically.

(1)  Install the wall hook bracket so that it is correctly positioned horizontally and 

vertically. If the wall hook bracket is tiled, water will drip to the 

fl

 oor.

(2)  Install the wall hook bracket so that it is strong enough to withstand the weight of an 

adult.

• Fasten the wall hook bracket to the wall with 6 or more screws through the holes 

near the outer edge of the bracket.

• Check that there is no rattle at the wall hook bracket.

Tapping screw

Wall hook bracket

3.3.3. Cutting the hole in the wall for the connecting piping

 

WARNING

  If the wall pipe is not used, the cable interconnecting the indoor and outdoor units may 

touch metal and cause electric leakage.

(1)  Cut a 80 mm diameter hole in the wall at the position shown in Fig. B.

(2)  When cutting the wall hole at the inside of the wall hook bracket, cut the hole within 

the range of the left and right center marks 40 mm below the wall hook bracket.

 

When cutting the wall hole at the outside of the wall hook bracket, cut the hole at 
least 10 mm below over.

(3)  Cut the hole so that the outside end is lower (5 to 10 mm) than the inside end.

(4)  Always align the center of the wall hole. If misaligned, water leakage will occur.

(5)  Cut the wall pipe to match the wall thickness, stick it into the wall cap, fasten the cap 

with vinyl tape, and stick the pipe through the hole. (The connection pipe is supplied 
in the installation set.) (Fig. B)

(6)  For left piping and right piping, cut the hole a little lower so that drain water will 

fl

 ow 

freely. (Fig. B)

9373370192_IM.indb   Sec1:3

9373370192_IM.indb   Sec1:3

2/16/2013   11:13:07 AM

2/16/2013   11:13:07 AM

Summary of Contents for ASHA04GACH

Page 1: ...NSTALACI N APPAREIL INT RIEUR Type montage mural interne EEV UNIDAD INTERIOR Tipo montado en pared EEV interna Pour le personnel agr uniquement nicamente para personal de servicio autorizado MANUALE D...

Page 2: ...It is recommended to use a gauge manifold with a high pressure display range 0 1 to 5 3 MPa and a low pressure display range 0 1 to 3 8 MPa Charging hose To increase pressure resistance the hose mate...

Page 3: ...inlet and outlet ports should not be obstructed the air should be able to blow all over the room 3 Leave the space required to service the air conditioner 4 A place from where the air can be distribu...

Page 4: ...juries If the job is done with the panel frame only there is a risk that the unit will come loose Please take care 3 3 1 Determining the piping direction The piping can be connected in the 5 direction...

Page 5: ...raising the upper surface and a front panel is removed Front panel 4 Insert the spacer etc between the indoor unit and the wall hook bracket and separate the bottom of the indoor unit from the wall Wa...

Page 6: ...rque wrench using the specified tightening method Otherwise the flare nuts could break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into con...

Page 7: ...arate these cable by 50 mm or more Bundling these cables together will cause miss operation or breakdown When handling PCB static electricity charged in the body may cause malfunction of the PCB Follo...

Page 8: ...en the terminal screws Do not use a screwdriver that is too small otherwise the screw heads may be damaged and prevent the screws from being properly tightened 4 Do not tighten the terminal screws too...

Page 9: ...7 0 7 7 0 7 8 0 8 8 0 8 9 0 9 9 0 9 10 1 0 10 0 0 11 1 1 11 1 1 12 1 2 12 1 2 99 9 9 63 6 3 Do not set the indoor unit address IU AD SW at 64 to 99 It may result in failure 6 FIELD SETTING There are...

Page 10: ...to 6 1 Setting the address for indoor unit address and refrigerant circuit address settings Turn the power of the indoor unit ON before starting the setting Turning on the power to the indoor units in...

Page 11: ...ion number ones place 0 5s ON 0 5s OFF FILTER indicator lamp Red Setting number 0 to 9 0 5s ON 0 5s OFF Example Function 31 Setting number 2 OPERATION indicator lamp Green TIMER indicator lamp Orange...

Page 12: ...side the indoor unit using a pull box etc as shown on below example DC power supply 12 to 24V connected unit Load resistance P C B P C B CNA01 P C B Input device 1 Input device 2 Indoor unit Indoor un...

Page 13: ...cted device 1 Connected device 2 Connected device 3 connected unit Relay Field supply Operation behavior Connector Output voltage Status CNB01 External output1 Pins 1 2 0V Stop DC 12 V Operation Exter...

Page 14: ...ng cover Screw Piping cover Screw Cable clamp Piping cover Screw 7 FINISHING CAUTION After checking for gas leaks refer to the Installation Manual of the outdoor unit perform this section Install heat...

Page 15: ...No operation After installation is completed has the proper operation and handling been explained to the user 10 ERROR CODES If you use a wired type remote controller error codes will appear on the re...

Reviews: