En-9
3
Remote controller address
i) 3-wire
type
Rotary switch (RC AD SW)...Factory setting “0”
When connecting multiple indoor units to 1 standard wired remote controller, set
the address at RC AD SW in sequence from 0.
Setting
Setting range
Type of switch
Remote controller
address
0 to 15
Setting
example
0
RC-AD
Example
If 4 indoor units are connected.
RC AD SW
RC AD SW
RC AD SW
RC AD SW
0
1
2
3
Indoor unit
Remote
controller
Indoor unit
Indoor unit
Indoor unit
RC AD SW
0
1
2
3
4
5
6
7
Address
0
1
2
3
4
5
6
7
RC AD SW
8
9
A
B
C
D
E
F
Address
8
9
10
11
12
13
14
15
ii) 2-wire
type
Rotary switch (RC AD SW)...Factory setting “0”
Since the remote controller address settings are automatically con
fi
gured, you do
not need to con
fi
gure them.
If
con
fi
guring manually, it is necessary to con
fi
gure both the indoor unit and the
remote controller. For details, please refer to the remote controller manual.
6.2. Custom code setting
Selecting the custom code prevents the indoor unit mix-up.
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
A B C D
A B C D
Indoor
unit
Remote
controller
Confusion
Code change
Custom code setting for indoor unit
Set the DIP switch SET 3 SW1, SW2 referring to the Table B.
DIP switch (SET 3)
OFF
ON
Controller PCB
SW1
SW2
SW3
SW4
SET 3
Table B
Custom code
A (Factory setting)
B
C
D
DIP switch
SET 3 SW1
OFF
ON
OFF
ON
DIP switch
SET 3 SW2
OFF
OFF
ON
ON
6.3. Switching the upper limit of cooling
temperature
This setting can be raised the upper limit of the cooling temperature setting range.
This setting can be used when connecting to the following controllers.
• Wired remote controller (2-wire type)
• Central remote controller
• Touch panel controller
• System controller
• Service tool
• Web monitoring tool
DIP switch setting
Set the DIP switch SET 4 SW3 referring to the Table C.
DIP switch (SET 4)
OFF
ON
SW1
SW2
SW3
SW4
SET 4
Controller PCB
Table C
DIP switch SET 4 SW3
Cooling temperature setting range
OFF (Factory setting)
Standard (18 to 30 °C)
ON
Extension (18 to 32 °C)
NOTE:
Please do not make a standard setup and an extension setup intermingled in remote
controller group.
6.4. Function Setting
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
(Set IU AD, REF AD SW to 0)
• Refer to “6.1. Setting the address.” for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air
tight test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
number
Setting number
Default
Details
Filter
indicator
interval
11
00
Default
○
Adjust the
fi
lter cleaning interval noti-
fi
cation. If the noti
fi
cation is too early,
change to setting 01. If the noti
fi
cation
is too late, change to setting 02.
01
Longer
02
Shorter
Filter
indicator
action
13
00
Enable
○
Enable or disable the
fi
lter indica-
tor. Setting 02 is for use with a
central remote controller.
01
Disable
02
Display only on
central remote
controller
Cool air
temperature
trigger
30
00
Default
○
Adjust the cool air trigger temperature.
To lower the trigger temperature,
use setting 01. To raise the trigger
temperature, use setting 02.
01
Adjust (1)
02
Adjust (2)
Heat air
temperature
trigger
31
00
Default
○
Adjust the heat air trigger temperature.
To lower the trigger temperature by 6
degrees C, use setting 01. To lower the
trigger temperature by 4 degrees C, use
setting 02. To raise the trigger tempera-
ture, use setting 03.
01
Adjust (1)
02
Adjust (2)
03
Adjust (3)
Auto restart
40
00
Enable
Enable or disable automatic sys-
tem restart after a power outage.
01
Disable
○
Cool Air
Prevention
43
00
Super low
○
Restrain the cold air
fl
ow with mak-
ing the air
fl
ow lower when starting
heating operation. To correspond
to the ventilation, set to 01.
01
Follow the
setting on the
remote controller
External
control
46
00
Start/Stop
○
Allow an external controller to start
or stop the system, or to perform an
emergency stop.
* If an emergency stop is performed
from an external controller, all refriger-
ant systems will be disabled.
* If forced stop is set, indoor unit stops
by the input to the external input
terminals, and Start/Stop by a remote
controller is restricted.
01
Emergency
stop
02
Forced stop
Error report
target
47
00
All
○
Change the target for reporting errors.
Errors can either be reported in all
locations, or only on the wired remote.
01
Display only on
central remote
controller
Fan setting
when cooling
thermostat
OFF
49
00
Follow the setting
on the remote
controller
○
When set to 01, the fan stops when
the thermostat is OFF in cooling
operation. Connection of the wired
remote controller (2-wire type or 3-wire
type) and switching its thermistor are
necessary.
01
Stop
9373370192_IM.indb Sec1:9
9373370192_IM.indb Sec1:9
2/16/2013 11:13:09 AM
2/16/2013 11:13:09 AM