En-13
7.3. Switching the upper limit of cooling
temperature
This setting can be raised the upper limit of the cooling temperature setting range.
This setting can be used when connecting to the following controllers.
• Wired remote controller (2-wire type)
• Central remote controller
• Touch panel controller
• System controller
• Service tool
• Web monitoring tool
DIP switch setting
Set the DIP switch SET 4 SW3 referring to the Table C.
DIP switch “SET4”
ON
OFF
SW
1
SW
2
SW
3
SW
4
Table C
DIP switch SET 4 SW3
Cooling temperature setting range
OFF (Factory setting)
Standard (18 to 30 °C)
ON
Extension (18 to 32 °C)
NOTE :
Please do not make a standard setup and an extension setup intermingled in remote
controller group.
7.4. Function setting
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
(Set IU AD, REF AD SW to 0)
• Refer to “7.1. Setting the address” for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air
tight test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
number
Setting number
Default
Details
Filter
indicator
interval
11
00
Default
○
Adjust the fi lter cleaning interval
notifi cation. If the notifi cation is too
early, change to setting 01. If the
notifi cation is too late, change to
setting 02.
01
Longer
02
Shorter
Filter
indicator
action
13
00
Enable
○
Enable or disable the fi lter indicator.
Setting 02 is for use with a central
remote controller.
01
Disable
02
Display
only on
central
remote
controller
Cool air
tem-
perature
trigger
30
00
Default
○
Adjust the cool air trigger
temperature. To lower the trigger
temperature, use setting 01. To
raise the trigger temperature, use
setting 02.
01
Adjust (1)
02
Adjust (2)
Heat air
tem-
perature
trigger
31
00
Default
○
Adjust the heat air trigger
temperature. To lower the trigger
temperature by 6 degrees C, use
setting 01. To lower the trigger
temperature by 4 degrees C, use
setting 02. To raise the trigger
temperature, use setting 03.
01
Adjust (1)
02
Adjust (2)
03
Adjust (3)
Auto
restart
40
00
Enable
Enable or disable automatic system
restart after a power outage.
01
Disable
○
Cool Air
Preven-
tion
43
00
Super low
○
Restrain the cold airfl ow with mak-
ing the airfl ow lower when starting
heating operation. To correspond to
the ventilation, set to 01.
01
Follow the
setting on
the remote
controller
External
control
46
00
Start/Stop
○
Allow an external controller to start
or stop the system, or to perform
an emergency stop.
* If an emergency stop is performed
from an external controller,
all refrigerant systems will be
disabled.
* If forced stop is set, indoor unit
stops by the input to the external
input terminals, and Start/Stop by
a remote controller is restricted.
01
Emergen-
cy stop
02
Forced
stop
Error re-
port target
47
00
All
○
Change the target for reporting er-
rors. Errors can either be reported
in all locations, or only on the wired
remote.
01
Display
only on
central
remote
controller
Fan set-
ting when
cooling
thermostat
OFF
49
00
Follow the
setting on
the remote
controller
○
When set to 01, the fan stops when
the thermostat is OFF in cooling
operation. Connection of the wired
remote controller (2-wire type
or 3-wire type) and switching its
thermistor are necessary.
01
Stop
8. TEST RUN
]1
8.1. Test run using Outdoor unit (PCB)
• Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to
be used for the test run.
8.2. Test run using remote controller
• Refer to the Installation Manual for the remote controller to perform the test run using
the remote controller.
• When the air conditioner is being test run, the OPERATION and TIMER indicator lamps
fl
ash slowly at the same time.
For details, please refer to the Manual of “IR Receiver Unit” or “Wired Remote Controller”.
9. CHECK LIST
]1
Pay special attention to the check items below when installing the indoor unit(s). After
installation is complete, be sure to check the following check items again.
Check items
If not performed correctly
Check
box
Has the indoor unit been installed cor-
rectly?
Vibration, noise, indoor unit may drop
Has there been a check for gas leaks
(refrigerant pipes)?
No cooling, No heating
Has heat insulation work been com-
pleted?
Water leakage
Does water drain easily from the
indoor units?
Water leakage
Is the voltage of the power source the
same as that indicated on the label on
the indoor unit?
No operation, heat or burn damage
Are the wires and pipes all connected
completely?
No operation, heat or burn damage
Is the indoor unit earthed (grounded)?
Short circuit
Is the connection cable the speci
fi
ed
thickness?
No operation, heat or burn damage
Are the inlets and outlets free of any
obstacles?
No cooling, No heating
Does start and stop air conditioner
operation by remote controller or
external device?
No operation
After installation is completed, has the
proper operation and handling been
explained to the user?