background image

En-18

8. 2.  Vacuum process

CAUTION

Do not turn on the power unless all operations are complete.

If the system is not evacuated suf

fi

 ciently, its performance will drop.

Be sure to evacuate the refrigerant system using a vacuum pump.

The refrigerant pressure may sometimes not rise when a closed valve is opened after 
the system is evacuated using a vacuum pump. This is caused by the closure of the 
refrigerant system of the outdoor unit by the electronic expansion valve. This will not 
affect the operation of the unit.
Use a clean gauge manifold and charging hose that were designed speci

fi

 cally for 

use with R410A. Using the same vacuum equipment for different refrigerants may 
damage the vacuum pump or the unit.

Do not purge the air with refrigerants, but use a vacuum pump to evacuate the system.

•  If moisture might enter the piping, follow below. (i.e., if doing work during the rainy 

season, if the actual work takes long enough that condensation may form on the 
inside of the pipes, if rain might enter the pipes during work, etc.)

•  After operating the vacuum pump for 2 hours, pressurize to 0.05 MPa (i.e., vacuum 

breakdown) with nitrogen gas, then depressurize down to -100.7kPa (-755mmHg) 
for an hour using the vacuum pump (vacuum process).

•  If the pressure does not reach -100.7kPa (-755mmHg) even after depressurizing 

for at least 2 hours, repeat the vacuum breakdown - vacuum process.

After vacuum process, maintain the vacuum for an hour and make sure the pressure 
does not rise by monitoring with a vacuum gauge.

Evacuation procedure

(1)  Remove the blank caps of the gas pipe and liquid pipe and check that the valves 

are closed.

(2)  Remove the charging port cap.
(3)  Connect a vacuum pump and a pressure gauge to a charging hose and connect it 

to the charging port.

(4)  Activate the vacuum pump and vacuum the indoor unit and connection piping until 

the pressure gauge becomes -100.7kPa (-755mmHg).
Evacuate from both the gas pipe and the liquid pipe.

(5) Continue 

evacuating 

the 

system 

for 

1 hour after the pressure gauge reads 

-100.7kPa (-755mmHg).

(6) Remove 

the 

charging 

hose 

and 

reinstall the charging port cap.

8. 3.  Additional charging

CAUTION

Do not turn on the power unless all operations are complete.

After evacuating the system, add refrigerant.

Do not charge the system with a refrigerant other than R410A.

Always keep to the limit on the total amount of refrigerant. Exceeding the limit on the 
total amount of refrigerant will lead to malfunction during charging of refrigerant.

Do not reuse recovered refrigerant.

Use an electronic scale to measure the charging amount of refrigerant. 
Adding more refrigerant than the speci

fi

 ed amount will cause a malfunction.

Charge refrigerant using the liquid pipe.
Adding refrigerant through the gas pipe will cause a malfunction.
Add refrigerant by charging the system with the refrigerant in the liquid state. If the 
refrigerant cylinder is equipped with a siphon, it is not necessary to place the cylinder 
upright.
Check if the steel cylinder has a siphon installed or not before 

fi

lling. (There is an 

indication “with siphon for 

fi

lling liquid” on the steel cylinder.)

Filling method for cylinder with siphon

Set the cylinder vertical and 

fi

ll with the 

liquid.
(Liquid can be 

fi

lled without turning bot-

tom up with the siphon inside.)

Liquid

Gas

R410A

Filling method for other cylinders

Turn bottom up and 

fi

ll with liquid.

(Be careful to avoid turning over the 
cylinder.)

Liquid

Gas

R410A

Be sure to use the special tools for R410A for pressure resistance and to avoid mixing 
of impure substances.
If the units are further apart than the maximum pipe length, correct operation can not 
be guaranteed.
Make sure to back closing valve after refrigerant charging. Otherwise, the compressor 
may fail.
Minimize refrigerant release to the air. Excessive release is prohibited under the 
Freon Collection and Destruction Law.

8. 3. 1.  Procedure for charging the system with refrigerant

(1) Remove 

the 

charging 

port 

cap from the liquid pipe.

(2)  Attach a charging hose to the refrigerant cylinder, and connect it to the charging port.
(3) Add 

refrigerant 

by 

calculating 

the 

additional refrigerant volume in accordance with 

the calculation formula indicated below.

(4) Remove 

the 

charging 

hose 

and install the charging port cap.

(5)  Remove the blank caps (gas pipe and liquid pipe) and open the valves.
(6) Close 

the 

blank 

caps.

(7)  After adding refrigerant, indicate the added charging volume on the unit.

*  Tighten the blank caps and charging port caps to the torque values speci

fi

 ed in the 

Table A. 
To open and close the valves,
Use an M4 hexagon wrench.

8. 3. 2.   Checking total amount of refrigerant and calculating 

the amount of refrigerant charge to be added

•  The amount of refrigerant charge to be added is the total value of the basic refriger-

ant charge amount and the value calculated from the length of the liquid pipe.

•  Round up the value to 2 decimal places.

Model

B

Factory charged amount (kg)

 AJY040LCLAH

4.0

 AJY045LCLAH

4.0

 AJY054LCLAH

4.0

Diameter of liquid pipe (mm)

a

Additional amount for pipe length (kg/m)

Ø6.35

0.021

Ø9.52

0.058

(1)  Calculation of additional amount for pipe length

A = 

Total length of 
ø9.52 mm liquid 
pipe

a

× 0.058
(kg/m)

m

kg

 + 

Total length of 
ø6.35 mm liquid 
pipe

× 0.021
(kg/m)

m

kg

 = 

Total

kg

   (Round up A to 2 decimal place)

(2) Calculation 

of 

total 

refrigerant 

amount

C = A + B =  

kg

  (B : Factory charged amount)

Note: Check the total refrigerant amount under the following conditions

Condition

Computational formula

Total amount of refrigerant

 6.83kg

<Calculation>

Outdoor unit: AJY054LCLAH

(1)  Calculation of additional amount for outdoor unit

 

If liquid pipe piping length is the following

 

Φ

9.52 : 20m , 

Φ

6.35 : 10m

Additional charge volume: 
 

A = 20 (m) × 0.058 (kg/m) + 10 (m) × 0.021 (kg/m)

  

1.37 

kg

(2)  Check the total amount of refrigerant

 

C = A + B = 1.37 kg + 4.0 kg = 5.37 kg 

 6.83 kg

    

 No problem if the above condition is satis

fi

 ed

8. 4.  Installing insulation

•  Install insulation material after conducting the “8.1 Sealing Test”.
• To 

prevent 

condensation 

and 

water 

droplets, 

install insulation material on the refriger-

ant pipe.

•  Refer to the table to determine the thickness of the insulation material.
•  If the outdoor unit is installed at a level that is higher than the indoor unit, the water that 

has condensed in the 3-way valve of the outdoor unit could travel to the indoor unit. 
Therefore, use putty in the space between the pipe and the insulation to prevent the 
entry of water.

Table. Selection  of  insulation
(for using an insulation material with equal heat transmission rate or below 0.040W/(m·k))

9380545057_IM.indb   18

9380545057_IM.indb   18

2014/9/15   11:27:06

2014/9/15   11:27:06

Summary of Contents for AJY040LCLAH

Page 1: ...AL For authorized service personnel only INSTALLATIONSANLEITUNG Nur f r autorisiertes Fachpersonal MANUEL D INSTALLATION MANUAL DE INSTALACI N Pour le personnel agr uniquement nicamente para personal...

Page 2: ...y performed electrical work can cause serious accidents such as electric shock or fire For wiring use the prescribed type of cables connect them securely making sure that there are no external forces...

Page 3: ...one ground cable Improper grounding may cause electric shock Perform draining for the unit according to the Installation manual Check that the water is properly drained If the drain processing is impr...

Page 4: ...this is to prevent TV reception interference or radio noise Even if they are installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping...

Page 5: ...ace as shown in the following example when an obstruction is present also in the upward area When the upward area is open Unit mm 1 Obstacles at rear only 300 2 Obstacles at front only 1500 or more 3...

Page 6: ...s in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base such as concrete blocks The foundation shall support the legs of the unit and have a widt...

Page 7: ...e model Model code of indoor unit Capacity kW 04 1 1 07 2 2 09 2 8 12 3 6 14 4 5 18 5 6 24 7 1 30 9 0 34 10 0 36 11 2 45 12 5 54 14 0 In the case of ARXD07GALH equivalent to model code of indoor unit...

Page 8: ...Front connection Bottom connection Lateral connection Rear connection 5 2 Indoor unit pipe connections CAUTION For details refer to the Installation Instruction Sheet of each part Separation tube A B...

Page 9: ...indoor unit and the outdoor unit cor rectly If the centering is improper the flare nut cannot be tightened smoothly If the flare nut is forced to turn the threads will be damaged Do not remove the fl...

Page 10: ...to dust or water CAUTION The primary power supply capacity is for the air conditioner itself and does not include the concurrent use of other devices Do not use crossover power supply wiring for the...

Page 11: ...rror Pay attention to the following points while attaching wires on the terminal board Do not attach 2 wires on one side Do not twist wires Do not cross the wires Do not shorted at edge at root PROHIB...

Page 12: ...a screwdriver that is too small otherwise the screw heads may be damaged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may bre...

Page 13: ...onnected unit connected unit connected unit connected unit connected unit Input1 CN131 Yellow Input2 CN132 Green Input3 CN133 White Input4 CN134 Red Input5 CN135 Orange P C B Operation behavior Each i...

Page 14: ...output signal for base heater Output signal ON when the outdoor tempera ture goes down below 2 C and signal OFF at the outdoor temperature 4 C 1 2 3 4 Voltage power supply input voltage cable 0 82mm2...

Page 15: ...0 0 Factory setting 11 Cooling capacity shift Normal mode 1 1 0 0 Save energy mode 0 1 High power mode 1 0 2 High power mode 2 0 3 Forbidden 0 4 Set this item when necessary 12 Heating capacity shift...

Page 16: ...ter pulse setting 2 Setting number 00xx 7 3 0 0 Setting number 01xx 0 1 Setting number 98xx 9 8 Setting number 99xx 9 9 Set the hundreds digit and thousands digit of the electricity meter pulse settin...

Page 17: ...address setting Address must be set for the indoor unit Manual setting When setting with the switch inside the indoor unit refer to the indoor unit operating manual When setting with a remote control...

Page 18: ...the pressure of nitrogen gas before blazing After completing the sealing test release the nitrogen gas from both valves Release the nitrogen gas slowly It may take about 10 minutes for completing the...

Page 19: ...Set the cylinder vertical and fill with the liquid Liquid can be filled without turning bot tom up with the siphon inside Liquid Gas R410A Filling method for other cylinders Turn bottom up and fill wi...

Page 20: ...ry indoor units 3 Are the cables connected to the terminals without loose ness and in accordance with the specifications 4 Are all the indoor units stopped Indoor unit connection check can not be perf...

Page 21: ...d to test operation the unit If there are problems adjust immediately and recheck 9 3 Test run method Be sure to configure test run settings only when the outdoor unit has stopped operating Depending...

Page 22: ...error E 7 4 1 Outside air temp thermistor error E 7 5 1 Outdoor unit suction gas temp thermistor error E 7 7 1 Outdoor unit heat sink temp thermistor error E 8 4 1 Outdoor unit current sensor 1 error...

Page 23: ...ition is max cooling condition refer to item 16 9 Air circulation Air circulation 10 Noise level Noise level 11 Refrigerant Refrigerant type and initial charging amount 12 Max pressure HP LP Means pre...

Reviews: