6. 5. 2.  Wiring procedure

• Remove 

the 

service 

panel. 

And connect the cable to the terminal in accordance with 

the terminal name plate.

•  Use a ring terminal to connect the electric cables to the power supply terminal board.
• Keep 

the 

earth 

cable 

longer than the other cables.

•  After connecting the electric cable, secure them with a cable clamp.
• Connect 

the 

cable 

without 

applying excessive tension.

• Use 

the 

speci

fi

 ed cable type and connect the cable securely.

Secure with a cable clamp as shown in the 

fi

 gure below.

Tightening torque

M3 screw

0.5 to 0.6 N·m (5 to 6 kgf·cm)

M5 screw

2.0 to 3.0 N·m (20 to 30 kgf·cm)

Power supply cable

Power supply terminal

Transmission terminal (M3)

Ring terminal (M5)

Cable clamp

Cable clamp

earth cable

Cable tie (accessory)

Transmission cable

8~1

0 mm

45~50mm

25~30mm

25~40mm

Cable tie (accessory)

Sealing transmission cable

Connect both ends of the sealed wires of the transmission cable to the earth terminal of 
the equipment or to the earth screw near the terminal.
Be very careful that the screws are not overly tightened as the cables may snap and the 
terminal may be damaged.

How to connect wiring to the terminal

Caution when wiring cable 
(1)  

Use ring terminals with insulating sleeves as shown in the 

fi

 gure below to 

connect to the terminal block.

(2)  

Securely clamp the ring terminals to the cables using an appropriate tool so that 
the cables do not come loose.

(3)  

Use the speci

fi

 ed cables, connect them securely, and fasten them so that there 

is no stress placed on the terminals.

(4)  

Use an appropriate screwdriver to tighten the terminal screws. Do not use a 
screwdriver that is too small, otherwise, the screw heads may be damaged and 
prevent the screws from being properly tightened.

(5)  

Do not tighten the terminal screws too much, otherwise, the screws may break.

(6)  See the table below for the terminal screw tightening torques.

Sleeve

Strip : 10mm

Ring terminal

Cable

Screw with special washer

Ring terminal

Terminal blocks

Screw with special washer 

Cable

Ring terminal

6. 4. 3.  Enabling/Disabling automatic address setting

You can enable/disable automatic address setting for the indoor unit and the signal 
ampli

fi

 er.

To enable automatic address setting for the indoor unit, connect the indoor unit to out-
door units under the same refrigerant system.(Fig.4)

Example: Disable Automatic Address setting

Refrigerant 

system 1

Refrigerant 

system 2

Refrigerant 

system 3

Transmission line

Transmission line

Transmission line

Example: Enable Automatic Address setting

Refrigerant 

system 1

Refrigerant 

system 2

Refrigerant 

system 3

Transmission line

Transmission line

Transmission line

6. 5.  Wiring method

6. 5. 1.  Connection diagrams

Breaker :  (1) Earth leakage circuit breaker

(2) Current breaker (over current)

To other refrigerant circuit Outdoor unit

Power supply

Outdoor unit

Breaker

Indoor unit

Indoor unit

Indoor unit

Power supply

Remote

control

Transmission

Transmission

Remote 

controller

Transmission

Power supply

Power supply

Power supply

Power supply

Power supply

Remote

control

Remote

control

Transmission

Breaker

Breaker

Breaker

Remote 

controller

Remote 

controller

*1:  The number of power supply terminals is different depending on the indoor unit 

 model. For the wiring, refer to the indoor unit installation manual.

*2:  Ground the remote controller if it has a ground cable.

*1

*1

*2

*2

*2

*1

The wiring example for outdoor and indoor units is shown in 

fi

 gure.

9380545057_IM.indb   11

9380545057_IM.indb   11

2014/9/15   11:27:05

2014/9/15   11:27:05

Summary of Contents for AJY040LCLAH

Page 1: ...AL For authorized service personnel only INSTALLATIONSANLEITUNG Nur f r autorisiertes Fachpersonal MANUEL D INSTALLATION MANUAL DE INSTALACI N Pour le personnel agr uniquement nicamente para personal...

Page 2: ...y performed electrical work can cause serious accidents such as electric shock or fire For wiring use the prescribed type of cables connect them securely making sure that there are no external forces...

Page 3: ...one ground cable Improper grounding may cause electric shock Perform draining for the unit according to the Installation manual Check that the water is properly drained If the drain processing is impr...

Page 4: ...this is to prevent TV reception interference or radio noise Even if they are installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping...

Page 5: ...ace as shown in the following example when an obstruction is present also in the upward area When the upward area is open Unit mm 1 Obstacles at rear only 300 2 Obstacles at front only 1500 or more 3...

Page 6: ...s in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base such as concrete blocks The foundation shall support the legs of the unit and have a widt...

Page 7: ...e model Model code of indoor unit Capacity kW 04 1 1 07 2 2 09 2 8 12 3 6 14 4 5 18 5 6 24 7 1 30 9 0 34 10 0 36 11 2 45 12 5 54 14 0 In the case of ARXD07GALH equivalent to model code of indoor unit...

Page 8: ...Front connection Bottom connection Lateral connection Rear connection 5 2 Indoor unit pipe connections CAUTION For details refer to the Installation Instruction Sheet of each part Separation tube A B...

Page 9: ...indoor unit and the outdoor unit cor rectly If the centering is improper the flare nut cannot be tightened smoothly If the flare nut is forced to turn the threads will be damaged Do not remove the fl...

Page 10: ...to dust or water CAUTION The primary power supply capacity is for the air conditioner itself and does not include the concurrent use of other devices Do not use crossover power supply wiring for the...

Page 11: ...rror Pay attention to the following points while attaching wires on the terminal board Do not attach 2 wires on one side Do not twist wires Do not cross the wires Do not shorted at edge at root PROHIB...

Page 12: ...a screwdriver that is too small otherwise the screw heads may be damaged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may bre...

Page 13: ...onnected unit connected unit connected unit connected unit connected unit Input1 CN131 Yellow Input2 CN132 Green Input3 CN133 White Input4 CN134 Red Input5 CN135 Orange P C B Operation behavior Each i...

Page 14: ...output signal for base heater Output signal ON when the outdoor tempera ture goes down below 2 C and signal OFF at the outdoor temperature 4 C 1 2 3 4 Voltage power supply input voltage cable 0 82mm2...

Page 15: ...0 0 Factory setting 11 Cooling capacity shift Normal mode 1 1 0 0 Save energy mode 0 1 High power mode 1 0 2 High power mode 2 0 3 Forbidden 0 4 Set this item when necessary 12 Heating capacity shift...

Page 16: ...ter pulse setting 2 Setting number 00xx 7 3 0 0 Setting number 01xx 0 1 Setting number 98xx 9 8 Setting number 99xx 9 9 Set the hundreds digit and thousands digit of the electricity meter pulse settin...

Page 17: ...address setting Address must be set for the indoor unit Manual setting When setting with the switch inside the indoor unit refer to the indoor unit operating manual When setting with a remote control...

Page 18: ...the pressure of nitrogen gas before blazing After completing the sealing test release the nitrogen gas from both valves Release the nitrogen gas slowly It may take about 10 minutes for completing the...

Page 19: ...Set the cylinder vertical and fill with the liquid Liquid can be filled without turning bot tom up with the siphon inside Liquid Gas R410A Filling method for other cylinders Turn bottom up and fill wi...

Page 20: ...ry indoor units 3 Are the cables connected to the terminals without loose ness and in accordance with the specifications 4 Are all the indoor units stopped Indoor unit connection check can not be perf...

Page 21: ...d to test operation the unit If there are problems adjust immediately and recheck 9 3 Test run method Be sure to configure test run settings only when the outdoor unit has stopped operating Depending...

Page 22: ...error E 7 4 1 Outside air temp thermistor error E 7 5 1 Outdoor unit suction gas temp thermistor error E 7 7 1 Outdoor unit heat sink temp thermistor error E 8 4 1 Outdoor unit current sensor 1 error...

Page 23: ...ition is max cooling condition refer to item 16 9 Air circulation Air circulation 10 Noise level Noise level 11 Refrigerant Refrigerant type and initial charging amount 12 Max pressure HP LP Means pre...