En-16

Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons to con

fi

 gure settings according 

to the procedures below.

(If no setting is made, the factory setting setting will be displayed.)

: Press the “MODE/EXIT” button.

: Press the “SELECT” button.

: Press the “ENTER” button.

: Press the “ENTER” button for more than 3 seconds.

MODE/EXIT

SELECT

ENTER

ENTER

7. 5.  Address setting for signal ampli

fi

 ers

7. 5. 1.  Address setting for signal ampli

fi

 ers

When using signal ampli

fi

 ers, the address for signal ampli

fi

 ers must be set.

The address for signal ampli

fi

 ers can be set automatically from 1 outdoor unit (master 

unit) on the network.
Refer to “Fig. Wiring example for automatic address setting” (7.6.1 chapter) for the wir-
ing example.
(For manual setting of address, refer to the signal ampli

fi

 er installation manual.)

7. 5. 2.  Automatic address setting for signal ampli

fi

 ers

When setting the address of the signal ampli

fi

 er, please use the factory setting. (See the 

installation manual of the signal ampli

fi

 er)

When the system is normal, nothing will be displayed on the 7 segment display.
When ERROR is displayed, inspect the units. 

Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the outdoor unit PC board 
to con

fi

 gure settings according to the procedures below.

1: FUNCTION Setting

First 2 digits Last 2 digits

(the display when the main 

power is turned on)

(When [F4] to [F9] are displayed, 

continue to press the “SELECT” 

button until [F3] is displayed.)

MODE/EXIT

SELECT

SELECT

ENTER

SELECT

ENTER

Automatic address setting for 

signal ampli

fi

 ers

Press the “SELECT” button until 

“10” is displayed.

Press the “ENTER” button for 

more than 3 seconds.

Setting is complete when the 

number of units is displayed

End

ENTER

MODE/EXIT

7. 6.  Indoor unit address setting

7. 6. 1.  Indoor unit address setting

Address must be set for the indoor unit.
Manual setting 

 • 

When setting with the switch inside the indoor unit, refer to 
the indoor unit operating manual.

  

• 

When setting with a remote control, refer to the remote 
control operating manual.

Automatic setting 

 • 

Check that the wiring is as shown in the 

fi

 gure below. 

Operate using the outdoor master unit of each refrigerant 
system.

Fig. Wiring example for automatic address setting

(1) Signal ampli

fi

 er wiring example

(2)(3)(4) Indoor unit wiring example

 (Connect  the  indoor  and  outdoor  units  of the same refrigerant system as shown 
below.)

Refrigerant system1

Refrigerant system2

Refrigerant system3

Master unit

Master unit

Master unit

Signal ampli

fi

 er

Signal ampli

fi

 er

NOTE) • 

 

The automatic address function can be used for a maximum of 8 indoor units 

 installed to the same refrigerant system. When network is connected to other 
 refrigerant systems, the automatic address function cannot be used.

•  The addresses of indoor units that have been configured automatically 

 cannot be assigned in the order when they are installed. (Refer to the indoor 
 unit installation manual for the procedures to check the addresses.)

7. 6. 2.   Procedures to enable automatic address setting on 

indoor units 

Check that the rotary switch IU AD on the indoor unit PC board is set to “00”.If it is not 
set to “00”, it means the address of that device is not set. (Factory setting is “00”).

Turn on the power of the indoor and outdoor units.

When the system is normal, nothing will be displayed on the 7 segment display.
When ERROR is displayed, inspect the units. 

Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the outdoor unit PC board 
to con

fi

 gure settings according to the procedures below.

1

1: FUNCTION Setting

First 2 digits Last 2 digits

(the display when the 

main power is turned on)

(When [F4] to [F9] are displayed, 

continue to press the “SELECT” 

button until [F3] is displayed.)

MODE/EXIT

SELECT

SELECT

ENTER

9380545057_IM.indb   16

9380545057_IM.indb   16

2014/9/15   11:27:06

2014/9/15   11:27:06

Summary of Contents for AJY040LCLAH

Page 1: ...AL For authorized service personnel only INSTALLATIONSANLEITUNG Nur f r autorisiertes Fachpersonal MANUEL D INSTALLATION MANUAL DE INSTALACI N Pour le personnel agr uniquement nicamente para personal...

Page 2: ...y performed electrical work can cause serious accidents such as electric shock or fire For wiring use the prescribed type of cables connect them securely making sure that there are no external forces...

Page 3: ...one ground cable Improper grounding may cause electric shock Perform draining for the unit according to the Installation manual Check that the water is properly drained If the drain processing is impr...

Page 4: ...this is to prevent TV reception interference or radio noise Even if they are installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping...

Page 5: ...ace as shown in the following example when an obstruction is present also in the upward area When the upward area is open Unit mm 1 Obstacles at rear only 300 2 Obstacles at front only 1500 or more 3...

Page 6: ...s in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base such as concrete blocks The foundation shall support the legs of the unit and have a widt...

Page 7: ...e model Model code of indoor unit Capacity kW 04 1 1 07 2 2 09 2 8 12 3 6 14 4 5 18 5 6 24 7 1 30 9 0 34 10 0 36 11 2 45 12 5 54 14 0 In the case of ARXD07GALH equivalent to model code of indoor unit...

Page 8: ...Front connection Bottom connection Lateral connection Rear connection 5 2 Indoor unit pipe connections CAUTION For details refer to the Installation Instruction Sheet of each part Separation tube A B...

Page 9: ...indoor unit and the outdoor unit cor rectly If the centering is improper the flare nut cannot be tightened smoothly If the flare nut is forced to turn the threads will be damaged Do not remove the fl...

Page 10: ...to dust or water CAUTION The primary power supply capacity is for the air conditioner itself and does not include the concurrent use of other devices Do not use crossover power supply wiring for the...

Page 11: ...rror Pay attention to the following points while attaching wires on the terminal board Do not attach 2 wires on one side Do not twist wires Do not cross the wires Do not shorted at edge at root PROHIB...

Page 12: ...a screwdriver that is too small otherwise the screw heads may be damaged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may bre...

Page 13: ...onnected unit connected unit connected unit connected unit connected unit Input1 CN131 Yellow Input2 CN132 Green Input3 CN133 White Input4 CN134 Red Input5 CN135 Orange P C B Operation behavior Each i...

Page 14: ...output signal for base heater Output signal ON when the outdoor tempera ture goes down below 2 C and signal OFF at the outdoor temperature 4 C 1 2 3 4 Voltage power supply input voltage cable 0 82mm2...

Page 15: ...0 0 Factory setting 11 Cooling capacity shift Normal mode 1 1 0 0 Save energy mode 0 1 High power mode 1 0 2 High power mode 2 0 3 Forbidden 0 4 Set this item when necessary 12 Heating capacity shift...

Page 16: ...ter pulse setting 2 Setting number 00xx 7 3 0 0 Setting number 01xx 0 1 Setting number 98xx 9 8 Setting number 99xx 9 9 Set the hundreds digit and thousands digit of the electricity meter pulse settin...

Page 17: ...address setting Address must be set for the indoor unit Manual setting When setting with the switch inside the indoor unit refer to the indoor unit operating manual When setting with a remote control...

Page 18: ...the pressure of nitrogen gas before blazing After completing the sealing test release the nitrogen gas from both valves Release the nitrogen gas slowly It may take about 10 minutes for completing the...

Page 19: ...Set the cylinder vertical and fill with the liquid Liquid can be filled without turning bot tom up with the siphon inside Liquid Gas R410A Filling method for other cylinders Turn bottom up and fill wi...

Page 20: ...ry indoor units 3 Are the cables connected to the terminals without loose ness and in accordance with the specifications 4 Are all the indoor units stopped Indoor unit connection check can not be perf...

Page 21: ...d to test operation the unit If there are problems adjust immediately and recheck 9 3 Test run method Be sure to configure test run settings only when the outdoor unit has stopped operating Depending...

Page 22: ...error E 7 4 1 Outside air temp thermistor error E 7 5 1 Outdoor unit suction gas temp thermistor error E 7 7 1 Outdoor unit heat sink temp thermistor error E 8 4 1 Outdoor unit current sensor 1 error...

Page 23: ...ition is max cooling condition refer to item 16 9 Air circulation Air circulation 10 Noise level Noise level 11 Refrigerant Refrigerant type and initial charging amount 12 Max pressure HP LP Means pre...

Reviews: