background image

En-8

 

CAUTION

Earth (Ground) the unit.
Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a 
telephone earth (ground) cable. 
Improper earthing (grounding) may cause electric shock.

Do not connect power supply cables to the transmission or remote controller terminals, 
as this will damage the product.

Never bundle the power supply cable and transmission cable, remote controller cable 
together.
Separate these cable by 2 in. (50 mm) or more.
Bundling these cables together will cause miss operation or breakdown.

When handling PCB, static electricity charged in the body may cause malfunction of 
the PCB. Follow the cautions below:

•  Establish an earth (ground) for the indoor and outdoor units and peripheral 

devices.

•  Cut power (breaker) off.
•  Touch metal part of the indoor unit for more than 10 seconds to discharge static 

electricity charged in the body.

•  Do not touch terminals of parts and patterns implemented on PCB.

]1

6.1. Electrical requirement

Voltage rating

208/230 V

Operating range

187 to 253 V

•  Select the power cable type and size in accordance with relevant local and national 

regulations.

• Speci

fi

 cations for local wiring power cord and branch wiring are in compliance with local 

code.

•  Select the correct cable type and size according to the country or region’s regulations.
•  Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the wire 

diameter when the wire length is long.

Refer to the table for the breaker speci

fi

 cations of each installation condition. Perform the 

power crossover wiring within the range of the same refrigerant system. When the crossover 
wiring is done, make a connection for indoor units to satisfy conditions A and B below.

A. Current breaker requirements

Model

MCA

MAX. CKT. BKR (Fuse capacity)

ABUA12TLAV

0.40 A

15 A

ABUA14TLAV

0.43 A

ABUA18TLAV

0.71 A

ABUA24TLAV

0.93 A

MCA: Minimum Circuit Ampacity
MAX. CKT. BKR : Maximum Circuit Breaker
When the power crossover wiring is done, make it so that the total of the MCA of the 
connected RB units and indoor units does not exceed the 11 A. For RB unit MCA, refer to 
the RB unit installation manual.
If the capacity of connected RB units and indoor units exceeds the upper limit, either add 
breakers or use a breaker with a greater capacity.

B. Ground Fault Equipment Breaker requirements

Breaker capacity

* Maximum connectable  “indoor units” 

or “indoor units + RB units”

30 mA, 0.1 sec or less

36 or less **

100 mA, 0.1 sec or less

37 to 90

* Heat pump type: indoor units, Heat recovery type: indoor units and RB units.
**  If the total number of units connected to the breaker exceeds 36, either add a 30mA 

breaker, or use breakers with a greater capacity.

6.1.1. Cable  speci

fi

 cations

Follow the speci

fi

 cations below for the power supply, transmission and remote controller 

cable.

Recommended 

cable size

Cable type

Remark

Transmission cable

22 AWG 

(0.33 mm²)

LONWORKS 

compatible cable

22 AWG LEVEL 4 

(NEMA) non-polar 

2 core, twisted pair 
solid core diameter 

0.026 in. (0.65 mm)

Remote controller cable

(2-wire type)

22 AWG 

(0.33 mm²) to 16 

AWG (1.25mm²)

Sheathed 

PVC cable

Non polar 2 core

Remote controller cable

(3-wire type)

22 AWG 

(0.33 mm²)

Sheathed 

PVC cable

Polar 3 core

]1

6.2. Wiring method

EXAMPLE

Outdoor unit or RB unit *1

Transmission

Transmission

Power supply

Breaker2

Breaker2

Breaker2

Breaker1

Breaker1

Breaker1

Power supply

Remote controller

(Master)

Remote controller

(Slave)

Remote controller

Indoor unit

Remote 

control

*2

*2

*2

Indoor unit

Indoor unit

Breaker 1:  Ground Fault Equipment

Breaker (GFEB)

Breaker 2:  Maximum Circuit Breaker

(MAX. CKT. BKR)

Breaker shall be located in sight from and readily accessible from all indoor units.
*1: When connecting to the Heat Recovery System, refer to the installation manual of the 

RB unit. 

*2: When connecting the 2-wire type remote controller, Y3 is not used.

Indoor unit

Power supply

Pull box

Pull box

Breaker2

Breaker1

Power supply

Power supply

Power supply

: Disconnect switch

Indoor unit

Indoor unit

(Crossover wiring of power supply)

Disconnect switch shall be installed between indoor unit and pull box.

1

6.3. Unit wiring

Before attaching the cable to terminal block.

6.3.1. Power supply cable

Adjust the length of power supply cable to avoid excessive tension with referring 

fi

 gure 

below.

3-1/8 in. 

(80mm)

3-1/8 in. 

(80mm)

Earth 
(Ground) 
wire

Conduit 
connector

A. For solid core wiring

(1)  To connect the electrical terminal, follow the below diagram and connect after looping 

it around the end of the cable.

(2)  Use the speci

fi

 ed cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(3)  Use an appropriate screwdriver to tighten the terminal screws. Do not use a 

screwdriver that is too small, otherwise, the screw heads may be damaged and 
prevent the screws from being properly tightened.

(4)  Do not tighten the terminal screws too much, otherwise, the screws may break.
(5)  See the table for the terminal screw tightening torques.
(6)  Please do not 

fi

 x 2 power supply cables with 1 screw.

 Loop

Screw with 
special washer

Screw with 
special washer

Cable end (Loop)

Cable end (Loop)

Cable

Cable

Terminal block

Strip 1 in. 
(25 mm)

9367701124-03_IM.indb   Sec1:8

9367701124-03_IM.indb   Sec1:8

2013-10-25   13:00:43

2013-10-25   13:00:43

Summary of Contents for ABUA12TLAV

Page 1: ...nel only PART NO 9367701124 03 ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV Fran ais MANUEL D INSTALLATION APPAREIL INT RIEUR type sol plafonnier Pour le personnel agr uniquement Espa ol MANUAL DE INST...

Page 2: ...the outdoor unit down with bolts and a metal frame Provide a suitable air baffle In a Snowy Area for Heat Pump type Systems Install the outdoor unit on a raised platform that is higher than drifting...

Page 3: ...dedicated tools and piping materials that have been manufactured specifically for R410A use Because the pressure of R410A refrigerant is approximately 1 6 times higher than the R22 failure to use ded...

Page 4: ...use refrigerant leakage Area that can cause combustible gas to leak contains suspended carbon fibers or flammable dust or volatile inflammables such as paint thinner or gasoline If gas leaks and settl...

Page 5: ...ccessories Special nut A Accessories Ceiling panel Spring washer Field supply M10 Nut Field supply M10 Nut Field supply 1 3 3 Installation the unit WARNING Install the air conditioner in a location wh...

Page 6: ...48 F 120 C Reverse cycle model only In addition if the humidity level at the installation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant pip...

Page 7: ...iquid pipes Failure to do so may cause water leaks After checking for gas leaks insulate by wrapping insulation around the 2 parts Gas and Liquid of the indoor unit coupling using the coupler heat ins...

Page 8: ...ctric shock or fire Before starting work check that power is not being supplied to the all units Use the included connection cables and power cables or ones specified by the manufacturer Improper conn...

Page 9: ...37 to 90 Heat pump type indoor units Heat recovery type indoor units and RB units If the total number of units connected to the breaker exceeds 36 either add a 30mA breaker or use breakers with a grea...

Page 10: ...emote controller cable Shielded wire no film 1 3 16 in 30 mm 1 15 16 in 50 mm Transmission cable Remote controller cable For 3 wire type For 2 wire type 1 3 16 in 30 mm 1 3 16 in 30 mm When the 2 cabl...

Page 11: ...nd output cable with appropriate external dimension depending on the number of cables to be installed The wire connection should be separate from the power cable line Input select Use either one of th...

Page 12: ...rning ON output to the connected external heater can be set by changing Dip switch on PC board Dip switch SET2 SW3 Fan setting when ON is output to the external heater Explanation OFF Factory setting...

Page 13: ...s and the refrigerant circuit address can also be set up through the wireless remote controller Set it according to the following procedures when setting manually It can be set manually if the cover s...

Page 14: ...er 02 Shorter Filter indicator action 13 00 Enable Enable or disable the filter indicator Setting 02 is for use with a central remote controller 01 Disable 02 Display only on central remote controller...

Page 15: ...r lamp Orange FILTER indicator lamp Red MANUAL AUTO button 7 3 2 Checking the function settings Press and hold the MANUAL AUTO button on the indoor unit for 3 seconds to check the function settings It...

Page 16: ...r plate Left 1 Join the cover plates left and mount with screws Tapping screw M4 10 mm Accessories Cover plate Left Accessories 8 4 Mount the intake grille 1 Cut the right side of the intake grille Th...

Page 17: ...remote controller display If you use a wireless remote controller the lamp on the photodetector unit will output error codes by way of blinking patterns See the lamp blinking patterns and error codes...

Reviews: