background image

En-13

 

Example

  If 4 indoor units are connected.

RC AD SW

0

RC AD SW

1

RC AD SW

2

RC AD SW

3

Indoor unit

Remote 

controller

Indoor unit

Indoor unit

Indoor unit

RC AD SW

0

1

2

3

4

5

6

7

Address

0

1

2

3

4

5

6

7

RC AD SW

8

9

A

B

C

D

E

F

Address

8

9

10

11

12

13

14

15

ii) 2-wire type
  Rotary switch (RC AD SW)...Factory setting “0”
  Since the remote controller address settings are automatically con

fi

 gured, you do not 

need to con

fi

 gure them.

 If 

con

fi

 guring manually, it is necessary to con

fi

 gure both the indoor unit and the remote 

controller. 

  For details, please refer to the remote controller manual.

]1

7.2. Custom code setting

 

CAUTION

Use an insulated screwdriver to set the DIP switches.

Selecting the custom code prevents the indoor unit mix-up. (Fig. B)
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.

Fig. B

Code change

Indoor unit

Remote 
controller

Confusion

A            B              C           D

A           B            C             D

Custom code setting for indoor unit

Set the DIP switch SET 3 SW1, SW2, referring to the Table B.

sw

1

sw

2

sw

3

sw

4

Dip switch “SET 3”

ON

OFF

 

Table B

Custom code

A (Factory setting)

B

C

D

DIP switch SET 3 SW1

OFF

ON

OFF

ON

DIP switch SET 3 SW2

OFF

OFF

ON

ON

]

]1

7.3. Function setting

•  FUNCTION SETTING can be performed with the wired or wireless remote controller.
  (The remote controller is optional equipment)
•  Refer to the wired or wireless remote controller manual for detailed setting information. 

(Set IU AD, REF AD SW to 0)

•  Refer to “7.1. Setting the address” for indoor unit address and refrigerant circuit address 

settings.

•  Turn the power of the indoor unit ON before starting the setting.

*  Turning on the power to the indoor units initializes EEV, so make sure the piping air 

tight test and vacuuming have been conducted before turning on the power.

*  Also check again to make sure no wiring mistakes were made before turning on the 

power.

Function details

Function

Function 

number

Setting number

Default

Details

Filter indicator 

interval

11

00

Standard

Adjust the 

fi

 lter cleaning interval 

noti

fi

 cation. If the noti

fi

 cation is too 

early, change to setting 01. If the 
noti

fi

 cation is too late, change to 

setting 02.

01

Longer

02

Shorter

Filter indicator 

action

13

00

Enable

Enable or disable the 

fi

 lter indicator. 

Setting 02 is for use with a central 
remote controller.

01

Disable

02

Display only 

on central 

remote 

controller

Horizontal swing 

air

fl

 ow direction

24

00

Standard

Adjust the horizontal swing air

fl

 ow 

direction.
(For horizontal swing equipped 
models)

01

Left half

02

Right half

Cool air 

temperature 

trigger

30

00

Standard

Adjust the cool air trigger temperature. 
To lower the trigger temperature, 
use setting 01. To raise the trigger 
temperature, use setting 02.

01

Adjust (1)

02

Adjust (2)

Heat air 

temperature 

trigger

31

00

Standard

Adjust the heat air trigger temperature. 
To lower the trigger temperature by 11 
degrees F (6 degrees C), use setting 
01. To lower the trigger temperature 
by 7 degrees F (4 degrees C), 
use setting 02. To raise the trigger 
temperature, use setting 03.

01

Adjust (1)

02

Adjust (2)

03

Adjust (3)

Auto restart

40

00

Enable

Enable or disable automatic system 
restart after a power outage.
*  Auto restart is an emergency function 

such as for power failure etc. Do not 
start and stop the indoor unit by this 
function in normal operation.
Be sure to operate by the control unit, 
converter or external input device.

01

Disable

Cool Air 

Prevention

43

00

Super low

Restrain the cold air

fl

 ow with making 

the air

fl

 ow lower when starting heating 

operation. To correspond to the 
ventilation, set to 01.

01

Follow the 

setting on 

the remote 

controller

External control

46

00

Start/Stop

Allow an external controller to start 
or stop the system, or to perform an 
emergency stop.
*  If an emergency stop is performed 

from an external controller, all 
refrigerant systems will be disabled. 

*  If forced stop is set, indoor unit stops 

by the input to the external input 
terminals, and Start/Stop by a remote 
controller is restricted. 

01

Emergency 

stop

02

Forced stop

Error report 

target

47

00

All

Change the target for reporting 
errors. Errors can either be reported 
in all locations, or only on the central 
remote controller.

01

Display only on 

central remote 

controller

Fan setting 

when cooling 

thermostat OFF

49

00

Follow the 

setting on 

the remote 

controller

When set to 01, the fan stops when 
the thermostat is OFF in cooling 
operation. Connection of the wired 
remote controller (2-wire type 
or 3-wire type) and switching its 
thermistor are necessary.

01

Stop

9367701124-03_IM.indb   Sec1:13

9367701124-03_IM.indb   Sec1:13

2013-10-25   13:00:50

2013-10-25   13:00:50

Summary of Contents for ABUA12TLAV

Page 1: ...nel only PART NO 9367701124 03 ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV Fran ais MANUEL D INSTALLATION APPAREIL INT RIEUR type sol plafonnier Pour le personnel agr uniquement Espa ol MANUAL DE INST...

Page 2: ...the outdoor unit down with bolts and a metal frame Provide a suitable air baffle In a Snowy Area for Heat Pump type Systems Install the outdoor unit on a raised platform that is higher than drifting...

Page 3: ...dedicated tools and piping materials that have been manufactured specifically for R410A use Because the pressure of R410A refrigerant is approximately 1 6 times higher than the R22 failure to use ded...

Page 4: ...use refrigerant leakage Area that can cause combustible gas to leak contains suspended carbon fibers or flammable dust or volatile inflammables such as paint thinner or gasoline If gas leaks and settl...

Page 5: ...ccessories Special nut A Accessories Ceiling panel Spring washer Field supply M10 Nut Field supply M10 Nut Field supply 1 3 3 Installation the unit WARNING Install the air conditioner in a location wh...

Page 6: ...48 F 120 C Reverse cycle model only In addition if the humidity level at the installation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant pip...

Page 7: ...iquid pipes Failure to do so may cause water leaks After checking for gas leaks insulate by wrapping insulation around the 2 parts Gas and Liquid of the indoor unit coupling using the coupler heat ins...

Page 8: ...ctric shock or fire Before starting work check that power is not being supplied to the all units Use the included connection cables and power cables or ones specified by the manufacturer Improper conn...

Page 9: ...37 to 90 Heat pump type indoor units Heat recovery type indoor units and RB units If the total number of units connected to the breaker exceeds 36 either add a 30mA breaker or use breakers with a grea...

Page 10: ...emote controller cable Shielded wire no film 1 3 16 in 30 mm 1 15 16 in 50 mm Transmission cable Remote controller cable For 3 wire type For 2 wire type 1 3 16 in 30 mm 1 3 16 in 30 mm When the 2 cabl...

Page 11: ...nd output cable with appropriate external dimension depending on the number of cables to be installed The wire connection should be separate from the power cable line Input select Use either one of th...

Page 12: ...rning ON output to the connected external heater can be set by changing Dip switch on PC board Dip switch SET2 SW3 Fan setting when ON is output to the external heater Explanation OFF Factory setting...

Page 13: ...s and the refrigerant circuit address can also be set up through the wireless remote controller Set it according to the following procedures when setting manually It can be set manually if the cover s...

Page 14: ...er 02 Shorter Filter indicator action 13 00 Enable Enable or disable the filter indicator Setting 02 is for use with a central remote controller 01 Disable 02 Display only on central remote controller...

Page 15: ...r lamp Orange FILTER indicator lamp Red MANUAL AUTO button 7 3 2 Checking the function settings Press and hold the MANUAL AUTO button on the indoor unit for 3 seconds to check the function settings It...

Page 16: ...r plate Left 1 Join the cover plates left and mount with screws Tapping screw M4 10 mm Accessories Cover plate Left Accessories 8 4 Mount the intake grille 1 Cut the right side of the intake grille Th...

Page 17: ...remote controller display If you use a wireless remote controller the lamp on the photodetector unit will output error codes by way of blinking patterns See the lamp blinking patterns and error codes...

Reviews: