5. INSTALLING DRAIN HOSE
]
CAUTION
Install the drain hose in accordance with the instructions in this Installation Manual
and keep the area warm enough to prevent condensation. Problems with the piping
may lead to water leaks.
Use general hard polyvinyl chloride pipe and connect it with adhesive (polyvinyl chloride)
so that there is no leakage.
Always heat insulate the indoor side of the drain hose.
Use a drain pipe that matches the size of the drain hose.
• Do not perform a rise, trap and air bleeding.
• Provide a downward gradient (1/100 or more).
• Provide supporters when long pipes are installed.
• Use an insulation material as needed, to prevent the pipes from freezing.
• Install the pipes in a way that allows for the removal of the control box.
Pipe size
Drain pipe
Φ
3/4 in. (19 mm) [I.D.],
Φ
1-1/16 in. (27 mm) [O.D.]
When using the drain port on the left side of the unit, remove the drain cap and install it to
the right side drain port.
(Only when suspended from the ceiling)
Drain cap
Unit
INSTALL THE DRAIN HOSE
Working procedure
1) Install the attached drain hose to the drain port of the body. Install the hose band
from the top of the hose within the graphic display area. Secure
fi
rmly with the hose
band.
2) Use vinyl adhesive agent to glue the drain piping (PVC pipe) / [
Φ
3/4 in. (19 mm) I.D.
Φ
1-1/16 in. (27 mm) O.D.] which is prepared on site or piping socket. (Apply color
adhesive agent evenly until the gauge line and seal)
3) Check the drainage.
4) Install the heat insulation.
5) Use the attached heat insulation to insulate the drain port and band parts of the body.
Top view
Drain hose
(Accessories)
13/32 to 19/32 in. (10 to 15 mm)
Hose Band
(Accessories)
Soft PVC side
Ensure there is no space
Drain pan
Side view
Applying
area of
adhesive
Hard PVC side
Joint pipe
(Field supply)
Drain pipe (Field supply)
Φ
3/4 in. (19 mm) [I.D.],
Φ
1-1/16 in. (27 mm) [O.D.]
5/32 in. (4 mm) or less
Wrap the Drain hose insulation around the drain hose connection.
Top view
Drain pan
Drain hose
3-15/16 in.
(100mm)
Drain hose insulation
(Accessories)
Hose opening view
Wind the attached heat insulation
around the hose band. Make sure
the alignment is on top.
A. Floor console type
Be sure to arrange the drain hose so that it is leveled lower than the drain hose connect-
ing port of the indoor unit.
Drain hose
GOOD
Prohibited
Prohibited
Arrange the drain
hose lower than
this portion.
CAUTION
Do not install the unit so that the drain hose side is too high. Height A should be less
than 3/16 in. (5 mm).
Drain hose
Prohibited
Prohibited
B. Under ceiling type
Be sure to arrange the drain hose so that it is leveled lower than the drain hose connect-
ing port of the indoor unit.
Drain
hose
Arrange the drain hose
lower than this portion.
GOOD
Prohibited
When drain hose is arranged backward.
Secure the drain hose with the VT wire.
Drain hose
VT wire
hole
VT wire
Pass the drain hose
through here.
Cut the grille
Intake grille
Base (Bottom)
6. ELECTRICAL WIRING
]
WARNING
Electrical work must be performed in accordance with this Manual by a person
certi
fi
ed under the national or regional regulations. Be sure to use a dedicated circuit
for the unit.
An insuf
fi
cient power supply circuit or improperly performed electrical work can cause
serious accidents such as electric shock or
fi
re.
Before starting work, check that power is not being supplied to the indoor unit and
outdoor unit.
Use the included connection cables and power cables or ones speci
fi
ed by the
manufacturer. Improper connections, insuf
fi
cient insulation, or exceeding the allowable
current can cause electric shock or
fi
re.