AirStage ABUA12RLAV Installation Manual Download Page 8

En-7

5.  INSTALLING DRAIN HOSE

]

 

CAUTION

Install the drain hose in accordance with the instructions in this Installation Manual 
and keep the area warm enough to prevent condensation. Problems with the piping 
may lead to water leaks.

Use general hard polyvinyl chloride pipe and connect it with adhesive (polyvinyl chloride) 
so that there is no leakage.
Always heat insulate the indoor side of the drain hose.
Use a drain pipe that matches the size of the drain hose.
•  Do not perform a rise, trap and air bleeding.
•  Provide a downward gradient (1/100 or more).
•  Provide supporters when long pipes are installed.
•  Use an insulation material as needed, to prevent the pipes from freezing.
•  Install the pipes in a way that allows for the removal of the control box.

Pipe size

Drain pipe

Φ

 3/4 in. (19 mm) [I.D.], 

Φ

 1-1/16 in. (27 mm) [O.D.]

When using the drain port on the left side of the unit, remove the drain cap and install it to 
the right side drain port.
(Only when suspended from the ceiling)

Drain cap

Unit

INSTALL THE DRAIN HOSE

Working procedure
1)   Install the attached drain hose to the drain port of the body. Install the hose band 

from the top of the hose within the graphic display area. Secure 

fi

 rmly with the hose 

band.

2)   Use vinyl adhesive agent to glue the drain piping (PVC pipe) / [

Φ

 3/4 in. (19 mm) I.D. 

Φ

 1-1/16 in. (27 mm) O.D.] which is prepared on site or piping socket. (Apply color 

adhesive agent evenly until the gauge line and seal)

3)   Check the drainage. 
4)   Install the heat insulation.
5)   Use the attached heat insulation to insulate the drain port and band parts of the body.

Top view

Drain hose
(Accessories)

13/32 to 19/32 in. (10 to 15 mm)

Hose Band
   (Accessories)

Soft PVC side

Ensure there is no space

Drain pan

Side view

Applying 
area of 
adhesive

Hard PVC side

Joint pipe 
(Field supply)

Drain pipe (Field supply)

Φ

 3/4 in. (19 mm) [I.D.], 

Φ

 1-1/16 in. (27 mm) [O.D.]

5/32 in. (4 mm) or less 

Wrap the Drain hose insulation around the drain hose connection. 

Top view

Drain pan

Drain hose

3-15/16 in.
(100mm)

Drain hose insulation
(Accessories)

Hose opening view

Wind the attached heat insulation 
around the hose band. Make sure 
the alignment is on top.

A. Floor console type

Be sure to arrange the drain hose so that it is leveled lower than the drain hose connect-
ing port of the indoor unit.

Drain hose

GOOD

Prohibited

Prohibited

Arrange the drain 
hose lower than 
this portion.

 

CAUTION

Do not install the unit so that the drain hose side is too high. Height A should be less 
than 3/16 in. (5 mm).

Drain hose

Prohibited

Prohibited

B. Under ceiling type

Be sure to arrange the drain hose so that it is leveled lower than the drain hose connect-
ing port of the indoor unit.

Drain 
hose

Arrange the drain hose 
lower than this portion.

GOOD

Prohibited

When drain hose is arranged backward.
Secure the drain hose with the VT wire.

Drain hose

VT wire 
hole

VT wire

Pass the drain hose 
through here.

Cut the grille

Intake grille

Base (Bottom)

6. ELECTRICAL WIRING

]

 

WARNING

Electrical work must be performed in accordance with this Manual by a person 
certi

fi

 ed under the national or regional regulations. Be sure to use a dedicated circuit 

for the unit. 
An insuf

fi

 cient power supply circuit or improperly performed electrical work can cause 

serious accidents such as electric shock or 

fi

 re.

Before starting work, check that power is not being supplied to the indoor unit and 
outdoor unit.

Use the included connection cables and power cables or ones speci

fi

 ed by the 

manufacturer. Improper connections, insuf

fi

 cient insulation, or exceeding the allowable 

current can cause electric shock or 

fi

 re.

9367701094-02_IM.indb   Sec1:7

9367701094-02_IM.indb   Sec1:7

12/29/2011   10:50:33 AM

12/29/2011   10:50:33 AM

Summary of Contents for ABUA12RLAV

Page 1: ...type APPAREIL INT RIEUR Type sol plafond UNIDAD INTERIOR Tipo piso techo UNIDADE INTERIOR Tipo ch o teto For authorized service personnel only Uniquement r serv aux techniciens agr s S lo para person...

Page 2: ...o provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause drip ping and water damage to walls and floors In an Area with High Winds Securely a...

Page 3: ...y vacate the premises and thoroughly ventilate the area If the refrigerant comes in contact with a flame it produces a toxic gas 1 2 2 Special tool for R410A WARNING To install a unit that uses R410A...

Page 4: ...ns suspended carbon fibers or flammable dust or volatile inflammables such as paint thinner or gasoline If gas leaks and settles around the unit it can cause a fire Area where animals may urinate on t...

Page 5: ...l set the suspension bolts Note that anchor bolts are M10 bolts to be obtained locally Anchor Bolt Strength 220 to 330 lbf 980 to 1470 N M10 Anchor bolt Field supply Ceiling 25 32 to 1 31 32 20 to 50...

Page 6: ...ditioner using R410A incurs pressure higher than when using conventional R22 refrigerant it is necessary to choose adequate materials Thicknesses of copper pipes used with R410A are as shown in the ta...

Page 7: ...l from getting into the system as this would reduce the lifetime of the units If necessary cut the silencer pipe and use it Silencer pipe Accessories CAUTION Hold the torque wrench at its grip keeping...

Page 8: ...e is no space Drain pan Side view Applying area of adhesive Hard PVC side Joint pipe Field supply Drain pipe Field supply 3 4 in 19 mm I D 1 1 16 in 27 mm O D 5 32 in 4 mm or less Wrap the Drain hose...

Page 9: ...miss operation or breakdown When handling PCB static electricity charged in the body may cause malfunction of the PCB Follow the cautions below Establish an earth ground for the indoor and outdoor un...

Page 10: ...specified cables connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that...

Page 11: ...ponent box cover Remove the 3 tapping screws Electric component box cover Base CAUTION Be careful not to pinch the lead cables between the electric component box and base 4 Wiring When there is 1 tran...

Page 12: ...Wiring methods and specifications A twisted pair cable 22AWG should be used Maximum length of cable is 492 ft 150 m Use an external input and output cable with appropriate external dimension dependin...

Page 13: ...s 492 ft 150 m Use an external input and output cable with appropriate external dimension depending on the number of cables to be installed 3 Connection methods Wire modification Remove insulation fro...

Page 14: ...7 0 7 7 0 7 8 0 8 8 0 8 9 0 9 9 0 9 10 1 0 10 1 0 11 1 1 11 1 1 12 1 2 12 1 2 99 9 9 63 6 3 Do not set the indoor unit address IU AD SW at 64 to 99 It may result in failure 3 Remote controller address...

Page 15: ...t start and stop the indoor unit by this function in normal operation Be sure to operate by the control unit converter or external input device 01 Disable External control 46 00 Start Stop Allow an ex...

Page 16: ...ver the take off part with material putty or the like that will block it off UNDER CEILING TYPE Top Right Rear FLOOR CONSOLE TYPE 1 8 2 Mount the cover plate Right 1 Cut a pipe exit hole in the right...

Page 17: ...r burn damage Is the indoor unit earthed grounded Short circuit Is the connection cable the specified thickness No operation heat or burn damage Are the inlets and outlets free of any obstacles No coo...

Reviews: