Airmark GAW18 Installation & Operating Instructions Manual Download Page 7

 

 

 

 

 

IO-123084-GAW-063017 

- 7 - 

©2017 AirMark 

 

 
Fig. 6. Shows  the components of  a typical TXV 
assembly 
 

TXV BULB

TAIL PIECE

DISTRIBUTOR 

TEFLON O-RINGS

 

 

Fig.6. Components of a typical TXV assembly 

 

CAUTION

  Using a non-bleed expansion valve 

may require the use of a hard-start kit. Follow the 
outdoor unit manufacturer’s guidelines.  
 

Electrical Installation 

 

These units are designed for single or three phase 
208/240 volts, 60 Hz power supply. Wire selection 
and wiring must be in accordance with the 
National Electric Code and/or local codes. Unit 
terminals are designed to accommodate copper 
and aluminum wirings. If aluminum wiring is used; 
please observe special precautions relative to 
sizing, wire connections and corrosion protection.  

 

All models with 5, 8 or 10 kW electric heat are 
arranged for single circuit connections. Models 
larger than 10 kW are arranged for multi-circuit 
protection. Fig. 7 shows the typical electrical 
connections required for the air handler unit.  
 
 
 
 
 
 
 
 
 
 
 

 

 

Fig.7. Typical electrical connections required 

 

System Charging 

 

CAUTION

  An improperly charged system 

may cause degradation in system performance 
and damage the compressor.  
 
After installing the coil, refer to the outdoor unit 
manufacturer’s instructions for charging 
techniques and amount of charge. If outdoor unit 
manufacturers charging instructions are 
unavailable; then  refer  to instructions below to 
charge the system.   
 

1)  Bring airflow up to the maximum CFM 

possible according to Table 2 below.  

2)  Flowrator coils –  Add refrigerant until the 

superheat measured at the outdoor unit 
suction/vapor line matches the superheat 
listed in Table 2. 

Expansion valve coils – Add refrigerant until the 
subcooling measured at the outdoor unit liquid line 
matches the subcooling recommendation of the 
outdoor manufacturer (typically 7º – 10º F). 

If 

chart is unavailable, charge unit to a subcooling 
value of 8ºF +/- 1ºF."

 

 

 

 

 

 

Summary of Contents for GAW18

Page 1: ..._________________ SERIAL ____________________________________________________ INSTALLER __________________________________________________ INSTALLATION DATE _________________________________________ T...

Page 2: ...modification of the unit to operate with alternative power sources Inspection On receiving the product visually inspect it for any major shipping related damages Shipping damages are the carrier s re...

Page 3: ...determined by the designer of the duct system and should not necessarily be the size of the duct flange openings of the unit These models have a bottom or front return Discard the drain access panel...

Page 4: ...poor system performance and possible compressor damage During some installations a piston change may be required If so the installer MUST change the piston As stated earlier use piston sizes recommend...

Page 5: ...tion of the TXV bulb has a major influence on the system performance CAUTION Ensure that the TXV bulb is in direct contact with the suction vapor line Gaps between the bulb and tube should be avoided...

Page 6: ...box and note the location of the inlet side threaded male port and the outlet side female swivel nut port 6 After ensuring that the white Teflon seal is still in place inside the flowrator body screw...

Page 7: ...10 kW are arranged for multi circuit protection Fig 7 shows the typical electrical connections required for the air handler unit Fig 7 Typical electrical connections required System Charging CAUTION...

Page 8: ...et and outlet For outlet measure temperature of each main trunk at a location far enough away to avoid heater radiation and read the average temperatures Table 3 below shows the CFM that should be ach...

Page 9: ...current protection in the form of circuit breakers Have your contractor identify the circuits and the location of over current protection so that you will be in a position to make inspections or repla...

Page 10: ...IO 123084 GAW 020113 2013 AirMark WARNING HIGH VOLTAGE disconnect all power sources prior to servicing Failure might lead to safety hazard Wiring diagram for GAW models...

Reviews: